background image

S

Y

S

T

E

M

 

S

E

N

S

O

R

Addressable System Smoke
Detector

System smoke detectors,

which, in addition to providing alarm and trouble indica-
tions to a control unit, are capable of communicating a
unique identification (address).

Air Sampling-type Detector

A sampling-type detector consists of piping or tubing distri-
bution from the detector unit to the area(s) to be protected.
An air pump draws air from the protected area back to the
detector through the air sampling ports and piping or tub-
ing. At the detector, the air is analyzed for fire particulate.

Alarm (Signal) Notification Appliance

An electromechanical appliance that converts energy into
audible or visible signal for perception as an alarm signal.

Alarm Signal

A signal indicating an emergency requiring immediate
action, such as an alarm for fire from a manual box, a
waterflow alarm, or an alarm from an automatic fire alarm
system, or other emergency signal.

Alarm Verification Feature

A feature of automatic fire detection and alarm systems to
reduce unwanted alarms, wherein automatic fire detectors
must report alarm conditions for a minimum period of time
or confirm alarm conditions within a given time period,
after being reset, to be accepted as a valid alarm initiation
signal.

Annunciation

A visible and/or audible indication of system status.

Automatic Fire Alarm System

A system of controls, initiating devices and alarm signals in
which all or some of the initiating circuits are activated by
automatic devices such as smoke detectors.

Class A Circuit (Loop)

An arrangement of supervised initiating device, signaling
line, or indicating appliance circuits that prevents a single
open or ground on the installation wiring of these circuits
from causing loss of the system’s intended function.

Class B Circuit (Loop)

An arrangement of supervised initiating device, signaling
line, or indicating appliance circuits, which does not pre-
vent a single open or ground on the installation wiring of
these circuits from causing loss of the system’s intended
function.

Combination Smoke Detector

A smoke detector that combines two or more smoke or fire
sensing technologies.

Detector Coverage

The recommended maximum distance between adjacent
detectors or the area that a detector is designated to protect.

Drift Compensation

The capability of a detector to automatically adjust its
alarm sensitivity to compensate for any changes over time
in the factory settings for smoke and/or fire detection. In
analog systems, this may be done by the panel.

End of Line

A device such as a resistor or diode placed at the end of a
Class B wire loop to maintain supervision.

Appendix 1

Glossary of Terms

End of Line Relay

Device used to supervise power (for four-wire smoke
detectors) and installed after the last device on the loop.

False Alarms

An unwanted alarm caused by non-smoke contaminants
such as dust or insects.

Fire

A chemical reaction between oxygen and a combustible
material where rapid oxidation results in the release of
heat, light, flame and/or smoke.

Flame Detector

A device that detects the infrared, ultraviolet, or visible
radiation produced by a fire.

Four-wire Smoke Detector

A smoke detector which initiates an alarm condition on
two separate wires (initiating loop) apart from the two
power leads.

Heat Detector

A device that detects abnormally high temperature or rate-
of-temperature rise.

Initiating Circuit

A circuit which transmits an alarm signal initiated manu-
ally or automatically, such as a fire alarm box, smoke, heat,
or flame sensing device, sprinkler waterflow alarm switch
or similar device or equipment to a control panel or any
similar device or equipment which, when activated, caus-
es an alarm to be indicated or retransmitted. An Initiating
Device Circuit (Loop) is a circuit to which automatic or
manual signal initiating devices are connected where the
signal received does not identify the individual device
operated.

Initiating Device

Any manually operated or automatically operated equip-
ment which, when activated, initiates an alarm through an
alarm signaling device.

Intelligent (Analog, Smart) System Smoke Detector

A system smoke detector capable of communicating infor-
mation about smoke conditions at its location to a control
unit. This type of detector typically communicates a
unique identification (address) along with an analog (data)
signal, which indicates the level of smoke at its location.

Ionization Smoke Detector

An ionization smoke detector has a small amount of
radioactive material that ionizes the air in the sensing
chamber, thus rendering it conductive and permitting a
current to flow between two charged electrodes. This gives
the sensing chamber an effective electrical conductance.
When particles of combustion enter the ionization area,
they decrease the conductance of the air by attaching
themselves to the ions, causing a reduction in mobility.
When the conductance is less than a predetermined level,
the detector responds in a fire alarm condition.

Light Scattering

The action of light being reflected and/or refracted by
smoke particles for detection by a photoelectric smoke
detector. The action of light being refracted or reflected.

Listed

Equipment or materials included in a list published by an
organization (e.g., Underwriters Laboratories) acceptable
to the “authority having jurisdiction” and concerned with

17

Summary of Contents for A05-1003-002

Page 1: ...A P P L I C A T I O N S G U I D E System Smoke Detectors ...

Page 2: ...ectors Have Limitations 5 Section 3 Typical System Layout 5 Electrical Supervision 5 Class B Circuits 5 Class A Circuits 6 Wireless Circuits 6 General Zoning Guidelines 6 Fire Safety Functions 6 Smoke Detector Installation 6 Wiring Installation Guidelines 6 Typical Wiring Techniques 6 Wireless Systems 8 Installation Do s and Don ts 8 Wiring and System Checkout 8 Section 4 Proper Detector Applicati...

Page 3: ...e Council ICC for the purpose of combining the codes produced by the above three organizations into a single set of model building and fire codes ICC s International Building Code and International Fire Code were first published in 2000 and have been adopted by some states Testing Laboratories Testing laboratories test smoke detectors control panels and other components of fire alarm systems to ve...

Page 4: ... number of ionized particles in the chamber is reduced This reduction in the ionized particles results in a decrease in the chamber current that is sensed by elec tronic circuitry monitoring the chamber When the current is reduced by a predetermined amount a threshold is crossed and alarm condition is established Changes in humidity and atmospheric pressure affect the chamber current and create an...

Page 5: ...f insects dirt drywall dust and other forms of contamina tion into the sensing chamber can also reflect light from the light source onto the photosensitive device Electrical transients and some kinds of radiated energy can affect the circuitry of both ionization and photoelectric smoke detectors and be interpreted by the electronic cir cuitry to be smoke resulting in nuisance alarms The allowable ...

Page 6: ...ors such as flame detectors heat detectors and other detection devices may be used The application of these special types of detectors should be based on an engineering survey and used in accordance with the manufacturer s installation instructions provided Smoke Detectors Have Limitations Smoke detectors offer the earliest possible warning of fire They have saved thousands of lives in the past an...

Page 7: ...our hours General Zoning Guidelines The faster the source of an alarm can be pinpointed the faster action can be taken Although formal rules for zon ing are not given in fire protection codes except for wire less devices where each smoke detector must be individu ally identified it is always sensible to zone any system that contains more than a small number of detectors Experienced detector instal...

Page 8: ...installation wiring loop beyond the T tap however the detector would not function and no trou ble condition would occur NOTE T tapping may be permitted with some intelligent fire alarm systems Refer to manufacturer s recommendations Figure 13 illustrates the correct installation wiring method for smoke detectors None of the connections can be bro ken without opening the circuit causing loss of sup...

Page 9: ...instructions to assure proper radio communication between the smoke detector and the control panel Observe polarity when required Protect detectors against contamination during con struction or renovation Carefully follow the manufacturer s installation instructions Don t T tap smoke detectors or circuit conductors except when specifically permitted by the manufacturer as part of an intelligent ad...

Page 10: ...tor incorporates a microprocessor controlled air intake fan and filter that allows the unit to be installed in areas where ordinary detectors cannot be used Filtrex is an intelligent smoke detector that removes airborne particles before they reach the sensing chamber It is ideal for textile mills dusty manufacturing facilities paper mills and recycling centers For more information see System Senso...

Page 11: ... the sys tem into alarm after the alarm condition was cleared System detectors latch in alarm They do not reset until power is momentarily disconnected This makes it conven ient to identify the location of a detector that caused the control panel to alarm In addition system detectors are specifically designed to connect to a panel Two wire detec tors require a UL compatibility review to verify tha...

Page 12: ...and on intermediate levels of the racks adjacent to alternate pallet sections shown in NFPA 72 1999 A 2 3 6 5 A consultant s judgement may be required for specific installations Partitions Partitions and many types of large tall equipment standing on the floor can block the flow of smoke toward detectors Any partition or similar obstruction that is less than 18 inches 45 cm from the ceiling should...

Page 13: ...if the contents are espe cially valuable for example sophisticated and expen sive machinery or irreplaceable records detectors should be placed closer together Detectors in Air Handling and Air Conditioning Systems See NEMA Guide for Proper Use of Smoke Detectors in Duct Applications and NFPA 72 National Fire Alarm Code for more specific information Detectors in Above Ceiling Plenum Areas Includin...

Page 14: ... unit specified range then follow the manufacturer s recom mended procedure Restore zone or system at the completion of testing Notify the proper authorities that testing has been com pleted and the system is again operational Refer to paragraph 7 4 1 of NFPA 72 for additional infor mation To assure that each smoke detector is within its listed and marked sensitivity range it should be tested usin...

Page 15: ... silenced the problem unit located and the alarm system controls reset so that the effectiveness of the detection system is restored Make sure that all the detectors in the zone or pinpointed device s that show an alarm are checked before deciding that it is a false alarm If a fire does exist more than one detector may be in the alarm state although no signs of fire may be evident in the vicinity ...

Page 16: ...en to protect detectors from dust whenever maintenance requires sawing sanding drilling or other dust producing operations in the vicinity of the detector heads to prevent false alarms due to the dust get ting into the detector sensing chambers In new construc tion applications drywall dust contamination affects all types of smoke detectors To help overcome this problem it is strongly recommended ...

Page 17: ...o the owners for a specified break in period after installation in case problems develop Helping the owner set up appropriate Detector Maintenance and Alarm Logs for the system Providing initial instruction and training to the owner s personnel or outside organization which will be monitoring and maintaining the system Providing troubleshooting assistance if nuisance alarm problems cannot be solve...

Page 18: ...t the end of a Class B wire loop to maintain supervision Appendix 1 Glossary of Terms End of Line Relay Device used to supervise power for four wire smoke detectors and installed after the last device on the loop False Alarms An unwanted alarm caused by non smoke contaminants such as dust or insects Fire A chemical reaction between oxygen and a combustible material where rapid oxidation results in...

Page 19: ...utside of its listed sensitivity Smoke Detector A device that detects the visible or invisible particles of combustion Smoothing Algorithms A method of smoothing out a detector s interpretation of sudden short duration increases in obscuration within the sensing chamber intended to reduce the occurrence of nui sance alarms Spot Point Detector A device whose detecting element is concentrated at a p...

Page 20: ...tallation Date Installing Contractor Inspection and Test Date Inspection and Test Performed By Check one Location Action Taken By Date Time Recorded By Fire Trouble Bldg Zone Det Probable Cause Action Taken Name and Date Appendix 2 Fire Alarm Log ...

Page 21: ... 2002 System Sensor The company reserves the right to change specifications at any time A05 1003 002 ...

Reviews: