I56-6500-000 

 

 10-05

WIRING

WARNING

Before working on the FAAST XT PRO system, notify all required authorities 
that the system will be temporarily out of service. Make sure all power is 
removed from the system before opening the unit. All wiring must be in ac-
cordance with local codes.

POWER CABLES

Use the power ratings of the unit to determine the required wire sizes for each 
connection. Use the power ratings of the connected products to determine the 
wire size.

CONDUIT USAGE

If electrical conduit is used for system wiring, terminate the conduits at the 
cable entry ports on the top or bottom of the unit, using the appropriate con-
duit connectors.

1.  Run all wiring, both power and alarm, through the conduit and into the 

left side of the unit enclosure, as seen in Figure 3.

2.  Attach the appropriate wires to the supplied Euro connector. Follow 

appropriate local codes and electrical standards for all cabling.

3.  Plug the appropriate connector into the mating connector on the unit.

CABLING REQUIREMENTS

The FAAST XT PRO system provides a series of Euro style pluggable terminals, 
located behind the left side door of the unit. Refer to Table 1 for the proper 
electrical connections to the unit. Refer to Figure 4 for a typical connection for 
monitoring the FAAST XT PRO system at a Fire Alarm Control Panel (FACP).

FIGURE 3. POWER AND ALARM CONNECTION BLOCK

FIGURE 4. FACP WIRING DIAGRAM

TABLE 1. TERMINAL DESIGNATIONS

TERMINAL 

BLOCK

T1

External Power – Powers Aspirating Smoke Detector

T2

Not used.

T3

RS 485 Rx 

Rx and Tx can be wired in a half duplex configuration

T4

RS 485 Tx

Rx and Tx can be wired in a half duplex configuration

T5

Alert Relay – Maintains state on loss of power

T6

Action1 Relay – Maintains state on loss of power

T7

Action2 Relay – Maintains state on loss of power

T8

Fire1 Relay – Maintains state on loss of power

T9

Fire2 Relay – Maintains state on loss of power

T10

Minor Fault Relay – Maintains state on loss of power

T11

Urgent Relay – Always reverts to reset on loss of power

T12

Isolate Relay – Maintains state on loss of power

T13

External Monitor 

N.C.

N.O.

C.

Fire2 Relay

 

Contact

s

(T9)

Fire Panel (FACP) typical connection 

FAAST XT

Fire Alarm Aspiration Sensing Technology®

for monitoring of device

Alarm

Short = Fire

Open = Fault

EOL

N.C.

N.O.

C.

Fire1 Relay

 

Contact

s

(T8)

Alarm

Short = Fire

Open = Fault

N.C.

N.O.

C.

Action2

 

Rela

y

Contacts 

(T7)

Alarm

Short = Fire

Open = Fault

N.C.

N.O.

C.

Action1

Rela

y

Contacts 

(T6)

Alarm

Short = Fire

Open = Fault

N.C.

N.O.

C.

Alert Relay 

Contacts 

(T5)

Alarm

Short = Fire

Open = Fault

N.C.

N.O.

C.

Isolate Relay 

Contact

s

(T12

)

Supervisory

Short = Isolate

Open = Fault

N.C.

N.O.

C.

Urgent Relay 

Contacts

(T11

)

Short = Urgent Fault
Open = Fault

N.C.

N.O.

C.

Minor Relay 

Contacts 

(T10)

Short = Minor Fault

Open = Fault

FACP

Supervisory

Supervisory

EOL

EOL

EOL

EOL

EOL

EOL

EOL

External

Monitor

(T13

)

N.C.

B.

B.

A.

N.O.

(Reset)

Panel 

Remote 

Reset

C. 

47k

Ω

ASP114-01

ASP18-24

firealarmresources.com

Summary of Contents for 9440X FAAST

Page 1: ...ce and select Connect Device 5 Select Admin and enter the password the default password is pass word then click Connect 6 Upon connection a green dot will appear on the device icon in the navi gation tree CONNECTING TO FAAST XT PRO VIA ETHERNET Default Device IP Configuration IP Address 192 168 1 10 Subnet Mask 255 255 255 0 Default Gateway 192 168 1 1 Primary DNS 0 0 0 0 Secondary DNS 0 0 0 0 CON...

Page 2: ...ATTENTION Detailed pipe network information and best practices can be found in the Pipe Installation Guide available for download at systemsensor com faast The input and output ports are designed to accept nominal one inch pipe 25mm The input and output ports are tapered to provide fast easy pushfit connection of the sampling pipe to the unit Perform the following procedure to connect the air samp...

Page 3: ...D ALARM CONNECTION BLOCK FIGURE 4 FACP WIRING DIAGRAM TABLE 1 TERMINAL DESIGNATIONS TERMINAL BLOCK T1 External Power Powers Aspirating Smoke Detector T2 Not used T3 RS 485 Rx Rx and Tx can be wired in a half duplex configuration T4 RS 485 Tx Rx and Tx can be wired in a half duplex configuration T5 Alert Relay Maintains state on loss of power T6 Action1 Relay Maintains state on loss of power T7 Act...

Page 4: ...INFORMATION The use of all FAAST products configuration design use and maintenance must be performed in accordance with the technical documentation General Terms and Conditions and local regulations and or directives for design installation and maintenance of fire alarm systems Product Manuals User Guides White Papers CAD Drawings Datasheets Engineering specifications are available from www system...

Reviews: