3
I56-6500-000
10-05
WIRING
WARNING
Before working on the FAAST XT PRO system, notify all required authorities
that the system will be temporarily out of service. Make sure all power is
removed from the system before opening the unit. All wiring must be in ac-
cordance with local codes.
POWER CABLES
Use the power ratings of the unit to determine the required wire sizes for each
connection. Use the power ratings of the connected products to determine the
wire size.
CONDUIT USAGE
If electrical conduit is used for system wiring, terminate the conduits at the
cable entry ports on the top or bottom of the unit, using the appropriate con-
duit connectors.
1. Run all wiring, both power and alarm, through the conduit and into the
left side of the unit enclosure, as seen in Figure 3.
2. Attach the appropriate wires to the supplied Euro connector. Follow
appropriate local codes and electrical standards for all cabling.
3. Plug the appropriate connector into the mating connector on the unit.
CABLING REQUIREMENTS
The FAAST XT PRO system provides a series of Euro style pluggable terminals,
located behind the left side door of the unit. Refer to Table 1 for the proper
electrical connections to the unit. Refer to Figure 4 for a typical connection for
monitoring the FAAST XT PRO system at a Fire Alarm Control Panel (FACP).
FIGURE 3. POWER AND ALARM CONNECTION BLOCK
FIGURE 4. FACP WIRING DIAGRAM
TABLE 1. TERMINAL DESIGNATIONS
TERMINAL
BLOCK
T1
External Power – Powers Aspirating Smoke Detector
T2
Not used.
T3
RS 485 Rx
Rx and Tx can be wired in a half duplex configuration
T4
RS 485 Tx
Rx and Tx can be wired in a half duplex configuration
T5
Alert Relay – Maintains state on loss of power
T6
Action1 Relay – Maintains state on loss of power
T7
Action2 Relay – Maintains state on loss of power
T8
Fire1 Relay – Maintains state on loss of power
T9
Fire2 Relay – Maintains state on loss of power
T10
Minor Fault Relay – Maintains state on loss of power
T11
Urgent Relay – Always reverts to reset on loss of power
T12
Isolate Relay – Maintains state on loss of power
T13
External Monitor
N.C.
N.O.
C.
Fire2 Relay
Contact
s
(T9)
Fire Panel (FACP) typical connection
FAAST XT
Fire Alarm Aspiration Sensing Technology®
for monitoring of device
Alarm
Short = Fire
Open = Fault
EOL
N.C.
N.O.
C.
Fire1 Relay
Contact
s
(T8)
Alarm
Short = Fire
Open = Fault
N.C.
N.O.
C.
Action2
Rela
y
Contacts
(T7)
Alarm
Short = Fire
Open = Fault
N.C.
N.O.
C.
Action1
Rela
y
Contacts
(T6)
Alarm
Short = Fire
Open = Fault
N.C.
N.O.
C.
Alert Relay
Contacts
(T5)
Alarm
Short = Fire
Open = Fault
N.C.
N.O.
C.
Isolate Relay
Contact
s
(T12
)
Supervisory
Short = Isolate
Open = Fault
N.C.
N.O.
C.
Urgent Relay
Contacts
(T11
)
Short = Urgent Fault
Open = Fault
N.C.
N.O.
C.
Minor Relay
Contacts
(T10)
Short = Minor Fault
Open = Fault
FACP
Supervisory
Supervisory
EOL
EOL
EOL
EOL
EOL
EOL
EOL
External
Monitor
(T13
)
N.C.
B.
B.
A.
N.O.
(Reset)
Panel
Remote
Reset
C.
47k
Ω
ASP114-01
ASP18-24
firealarmresources.com