1
I56-6500-000
10-05
SPECIFICATIONS
Electrical Characteristics
External Supply Voltage
18 – 30 VDC
Remote Reset Time
External monitor must be pulled low for a minimum of 100 msec
Power Reset
1 sec
Relay Contact Ratings
3.0A @ 30VDC, 0.5A @125VAC
Environmental Ratings
Operating Temperature
32°F (0°C) to 100°F (38°C) – Factory tested to 131F (55C)
Sampled Air Temperature
-4°F (-20°C) to 140°F (60°C)
Humidity
10 to 95% non-condensing
IP Rating
IP30
9440X FAAST
Fire Alarm Aspiration Sensing Technology
®
INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-65
00-000
3825 Ohio Avenue, St. Charles, Illinois 60174
1.800.SENSOR2; Fax: 630.377.6495
www.systemsensor.com
The purpose of this document is to provide practical information for
mounting and connecting to FAAST XT PRO. For full product informa-
tion, which includes installation guidelines, instructions for safe use,
smoke sector identification procedures, and warranty and safety informa-
tion, refer to the FAAST XT PRO Comprehensive User Guide available at
systemsensor.com/iFAASTXTPROuserguide or by scanning the QR code.
ITEMS INCLUDED WITH UNIT
• FAAST XT PRO (9440X) unit
• Mounting bracket and hardware
• Installation and Maintenance Instructions
• USB interface cable
• PipeIQ® software, comprehensive manual, and other helpful documents
may be downloaded at systemsensor.com/faast
CONNECTING TO FAAST XT PRO
FAAST XT PRO requires a configuration download from PipeIQ in order to ini-
tialize. This connection can be achieved using either the USB port located on
the front of the device, or the Ethernet port located inside the wiring cabinet.
CONNECTING TO FAAST XT PRO VIA USB
NOTE: In order to connect your computer to the FAAST XT PRO using a USB
connection, a USB driver must first be installed. The driver installation oc-
curs during the installation of PipeIQ version 2.0 or later. Once the driver is
installed, connect to the device using the following steps.
1. Launch PipeIQ. (Download from systemsensor.com/faast.)
2. Create a new project and select FAAST XT PRO device, or open an existing
project.
3. Expand the tree view in the left side navigation pane to reveal the device.
4. Right click on the device and select ‘Connect Device’.
5. Select ‘Admin’ and enter the password – the default password is ‘pass-
word’ – then click ‘Connect’.
6. Upon connection, a green dot will appear on the device icon in the navi-
gation tree.
CONNECTING TO FAAST XT PRO VIA ETHERNET
Default Device
IP Configuration
IP Address:
192.168.1.10
Subnet Mask:
255.255.255.0
Default Gateway: 192.168.1.1
Primary DNS:
0.0.0.0
Secondary DNS: 0.0.0.0
CONFIGURE YOUR PC
Your PC will need to be sitting on the same local area network as the FAAST XT
PRO device in order to establish communication. Change your PC’s IP address
to 192.168.1.15 by:
1. Accessing your network setting in your PC’s control panel.
2. Open ‘Local Area Connection’ settings and select ‘Properties’.
3. Select ‘Internet Protocol Version 4 (TCP/IPv4) and then select ‘Properties’.
4. Select ‘Use the following IP address and enter 192.168.1.15. If the sub-
net mask does not automatically populate, enter 255.255.255.0 into the
subnet mask field.
5. Click OK, and close out of the network menus.
Important Note:
Before changing your PC’s IP address, be sure to take note of
whether your IP is currently dynamically set, or is a static IP address. If your PC is
assigned a static IP address, make note of the IP address and subnet mask so that
you can change back to the proper settings after the FAAST XT PRO is configured.
CONNECT USING PIPEIQ
1. Launch PipeIQ. (Download from systemsensor.com/faast.)
2. Create and save a new project, or open an existing project.
3. Expand the tree view in the left side navigation pane to reveal the device
4. Right click on the device and select ‘Connect Device’.
5. Select Host/IP and type in the device’s IP address - default is 192.168.1.10.
6. Select ‘Admin’ and enter the password – the default password is ‘pass-
word’ – then press ‘Connect’.
7. Upon connection, a green dot will appear on the device icon in the navi-
gation tree.
INSTALLATION
This equipment must be installed in accordance with all local and national
codes and regulations.
PIPE INSTALLATION
The pipe layout is designed using the PipeIQ software package. Refer to the
Comprehensive Instruction Manual to design the pipe network. All pipe must
be installed in accordance with local and national codes and regulations. The
pipe network should be complete before proceeding with the physical and
electrical system installation.