D500-46-00
4
I56-2175-002R
©2006 System Sensor
Please refer to insert for the Limitations of Fire Alarm Systems
System Sensor warrants its enclosed product to be
free from defects in materials and workmanship under
normal use and service for a period of three years from
date of manufacture. System Sensor makes no other
express warranty for the enclosed product. No agent,
representative, dealer, or employee of the Company
has the authority to increase or alter the obligations or
limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the replacement of
any part of the product which is found to be defec-
tive in materials or workmanship under normal use
and service during the three year period commencing
with the date of manufacture. After phoning System
Sensor’s toll free number 800-SENSOR2 (736-7672)
for a Return Authorization number, send defective
units postage prepaid to: System Sensor, Returns
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device
may not cause harmful interference, and (2) this device must accept any interference received, including interference that
may cause undesired operation.
NOTE:
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in ac-
cordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee
that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
Department, RA #__________, 3825 Ohio Avenue, St.
Charles, IL 60174. Please include a note describing
the malfunction and suspected cause of failure. The
Company shall not be obligated to replace units which
are found to be defective because of damage, unrea-
sonable use, modifications, or alterations occurring
after the date of manufacture. In no case shall the
Company be liable for any consequential or incidental
damages for breach of this or any other Warranty, ex-
pressed or implied whatsoever, even if the loss or dam-
age is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation
of incidental or consequential damages, so the above
limitation or exclusion may not apply to you. This
Warranty gives you specific legal rights, and you may
also have other rights which vary from state to state.
Three-Year Limited Warranty
Specifications:
Operating Voltage/Contact Ratings (Resistive): 6 – 125 VAC / 3A
6 – 28 VDC / 1A
125 VDC / 0.3A
250 VDC / 0.1A
Maximum Installation Temperature:
Models 5601P, 5603, 5621, and 5623: 100°F (38°C)
Models 5602, 5604, 5622, and 5624: 150°F (65.6°C)
Alarm Temperature:
Models 5601P, 5603, 5621, and 5623: 135°F (57°C)
Models 5602, 5604, 5622, and 5624: 194°F (90°C)
Rate-of-Rise Threshold:
15°F (8.3°C) per minute
(models 5601P, 5602, 5621, and 5622 only)
Operating Humidity Range:
5 to 95% RH non-condensing
Input Terminals:
14 – 22 AWG
Back Box Mounting:
3
1
⁄
2
″ octagonal
4″ octagonal
Single gang
4″ square with a square to round plaster ring
Dimensions with mounting bracket:
Diameter: 4.57 inches (11.6cm)
Height: 1.69 inches (4.3cm)
Weight:
6 oz. (170 grams)
CAUTION
To prevent the activation of the fixed temperature element, the shipping and storage temperature must not
exceed 122°F (50°C).