background image

D400-04-00

3

I56-288-05

CAUTION

Dust covers are an effective way to limit the entry of dust
into smoke detector sensing chambers. However, they may
not completely prevent airborne dust particles from
entering the detector. Therefore, System Sensor recom-
mends the removal of detectors before beginning
construction or other dust producing activity. Be sure to
remove dust covers from any sensors that were left in place
during construction as part of returning the system to
service.

TESTING

NOTE:

Before testing, notify the proper authorities that
the smoke detector system is undergoing mainte-
nance, and therefore will temporarily be out of
service. Disable the zone or system undergoing
maintenance to prevent unwanted alarms.

Detectors must be tested after installation and periodic
maintenance. The 2412AT, 2424AT or 2424AIT may be
tested in the following ways:

NOTE:

Before testing the detector check for the presence
of the flashing LED. If it does not flash, power has
been lost to the detector (check the wiring), or it is
defective (return for repair, see Warranty
information).

A. Recessed Test Switch

1. Push and hold the recessed test switch with a .1 inch

maximum diameter tool.

2. The LED should latch within 5 seconds indicating

alarm and annunciating the panel. The horn should
also sound.

B. Calibrated Test Card (System Sensor  No. R59-18-00)

1. Remove the detector cover by placing a small bladed

screwdriver in the side slot of the detector cover,
twisting it slightly until the cover can be turned
counterclockwise for removal.

2. Insert the NO ALARM end of the test card fully into

the test slot (see Figure 6) then slide it
counterclockwise until it stops.

4

5

4

5

SUGGESTED
EOL
RESISTOR

UL LISTED

TWO OR FOUR

WIRE PANEL

INITIATING

LOOP

+

Figure 4. Additional wiring needed for the isolated thermal unit of the 2424AIT detector thermal units are

wired to a separate loop:

A78-1392-01

TEST MODULE

SOCKET

LED

RECESSED TEST

SWITCH

PUSH RECESSED SWITCH WITH

A .1" MAX. DIAMETER TOOL

Figure 5. Bottom and side views showing position of

test switch:

1410-00

3. The detector should not alarm (wait at least 20

seconds).

4. Remove the test card by sliding it clockwise before

removing, then repeat with the ALARM end of test
card.

5. The LED should latch on within 20 seconds indicating

alarm and annunciating the panel.

6. Put the cover back by gently rotating it clockwise

until it locks in place.

C. Test Module (System Sensor Model No. MOD400R)

The MOD400R is used with an analog or digital
voltmeter to check the detector sensitivity as described
in the test module’s manual.

D. Aerosol Generator (GEMINI 501)

Set the generator to represent 4%/ft. to 5%/ft.
obscuration as described in the Gemini 501 manual.
Using the bowl shaped applicator, apply aerosol until
unit alarms.

E. Direct Heat Method (Hair dryer of 1000–1500 watts)

Direct the heat toward the bi-metallic collector. Hold the
heat source about 12 inches from the detector in order to
avoid damage to the plastic. When the heat rises to
greater than 135

°

F, the detector should latch in alarm.

The detector will reset only after it has had sufficient
time to cool and the power source has been momentarily
interrupted.

Notify the proper authorities tht the system is back on line.

Technical Manuals Online! - http://www.tech-man.com

Summary of Contents for 1412

Page 1: ...ty 10 to 93 Relative Humidity Noncondensing Electrical Ratings System Voltage 12 24 VDC Maximum Ripple Voltage 4 Volts peak to peak Start up Capacitance 0 02 uA Maximum Standby Ratings 8 5 VDC Minimum 35 VDC Maximum 100 uA Maximum Alarm Ratings 4 2 VDC Minimum at 10 mA 6 6 VDC Minimum at 100 mA Alarm current must be limited to 100 mA maximum by the control panel If used the RA400Z Remote Annunciat...

Page 2: ...inal to ensure that the connections are supervised Do NOT loop the wire under the terminals System Sensor smoke detectors are marked with a compat ibility identifier located as the last digit of a five digit code stamped on the back of the product Connect detectors only to compatible control units as indicated in System Sensor s compatibility chart which contains a current list of UL listed contro...

Page 3: ...D400R The MOD400R is used with an analog or digital voltme ter to check the detector sensitivity as described in the test module manual C Aerosol Generator Gemini 501 Set the generator to represent 4 Ft to 5 Ft obscura tion as described in the Gemini 501 manual Using the bowl shaped applicator apply aerosol until the unit alarms Notify the proper authorities that the system is back on line Detecto...

Page 4: ... reasons detectors shall be located on every level and in every bedroom within a building Smoke detectors have sensing limitations too Ionization detectors and photoelectric detectors are required to pass fire tests of the flaming and smoldering type This is to ensure that both can detect a wide range of types of fires Ionization detectors offer a broad range of fire sensing capa bility but they a...

Page 5: ... Reset by momentary power interruption Relay Contact Ratings Resistive or Inductive 60 power factor load Form A 2 0A 30VAC DC Form C 0 6A 110VDC 2 0A 30VDC 1 0A 125VAC 2 0A 30VAC For Canadian installations relay contact rating is 2 0A 30VAC DC Electrical Ratings 1412 1424 System Voltage 12 24 DC 4V Maximum Ripple Supply Voltages 11 3 20 VDC Minimum 17 3 29 VDC Maximum Reset Voltages 73 8 VDC Minim...

Page 6: ...e run to provide system supervision of connections For signal wiring the wiring between interconnected de tectors it is recommended that the wire be no smaller than 18 gauge Wire sizes up to 12 gauge wire may be used For best system performance the power and loop wires should be twisted pair and installed in separate grounded conduit to protect the loop from extraneous elec trical interference Smo...

Page 7: ...ny dust covers before placing system in service Testing NOTE Before testing notify the proper authorities that the smoke detector system is undergoing mainte nance and therefore will temporarily be out of ser vice Disable the zone or system undergoing maintenance to prevent unwanted alarms Before testing the detector look for the presence of the flashing LED If it does not flash power has been los...

Page 8: ...ons detectors shall be located on every level and in every bedroom within a building Smoke detectors have sensing limitations too Ionization detectors and photoelectric detectors are required to pass fire tests of the flaming and smoldering type This is to ensure that both can detect a wide range of types of fires Ionization detectors offer a broad range of fire sensing capa bility but they are so...

Page 9: ... Operating Humidity Range 10 to 93 Relative Humidity Non condensing Maximum Air Velocity 3000 ft min 15m s Locking Alarm Reset by momentary power interruption Electrical Ratings System Voltage 12 24 VDC Maximum Ripple Voltage 4 Volts peak to peak Start up Capacitance 0 02 µF Maximum Standby Ratings 8 5 VDC Minimum 35 VDC Maximum 120 µA Maximum Alarm Ratings 4 2 VDC Minimum at 10 mA 6 6 VDC Maximum...

Page 10: ...g of 2400TH smoke detector on 3 1 2 inch and 4 inch octagonal box Figure 3 Wiring diagram for 2400 smoke detector used with two wire control panel REMOTE ANNUNCIATOR REMOTE ANNUNCIATOR CLASS A OPTIONAL WIRING NOTE IF REMOTE ANNUNCIATOR IS NOT USED POLARITY TO DETECTOR MAY BE REVERSED EOL RESISTOR INITIATING LOOP UL LISTED CONTROL PANEL 3 2 1 3 2 1 A78 1554 00 Make wire connections by stripping abo...

Page 11: ...crewdriver in the side slot of the detector cover twisting it slightly until the cover can be turned coun terclockwise for removal 2 Insert the NO ALARM end of the test card fully into the test slot See Figure 5 then slide it counterclock wise until it stops 3 The detector should not alarm after 20 seconds 4 Remove the test card by sliding it clockwise before re moving then insert the ALARM end 5 ...

Page 12: ...oke detector should be cleaned regularly per NFPA 72 or at least once a year WARNING The Limitations of Property Protection Smoke Detectors Maintenance NOTE Before removing the detector notify the proper au thorities the smoke detector system is undergoing maintenance and therefore will be temporarily out of service Disable the zone or system undergo ing maintenance to prevent unwanted alarms 1 Re...

Page 13: ...ral Description System Sensor 2400AT and 2400AIT photoelectronic smoke detectors listed to UL 268 provide open area protection and are intended for use with UL listed compatible 2 wire control panels The sensor in this detector operates on the light scattering principle and features a unique photo optic sensing chamber that optimizes smoke entry while mini mizing the effects of ambient light These...

Page 14: ...cated in System Sensor s compatibility chart This chart contains a current list of UL listed control units and detector combinations and is avail able from System Sensor upon request CAUTION Dust covers provide limited protection against airborne dust particles during shipping Dust covers MUST be re moved before the smoke detectors can sense smoke Re move sensors before beginning remodeling or hea...

Page 15: ... to represent 4 Ft to 5 Ft obscura tion as described in the aerosol generator manual Using the bowl shaped applicator apply aerosol until the unit alarms E Direct Heat Method Hair dryer of 1000 1500 watts Direct the heat toward the bimetallic collector Hold the heat source about 12 inches from the detector in order to avoid damage to the plastic When the heat rises to greater than 135 F the detect...

Page 16: ...vents that ignite other similar safety hazards arson smoking in bed children playing with matches or lighters etc Smoke detectors used in high air velocity conditions may have a delay in alarm due to dilu tion of smoke densities created by frequent and rapid air exchanges Addi tionally high air velocity environments may create increased dust contamination demanding more frequent detector maintenan...

Page 17: ...umidity 10 to 95 Relative Humidity Non condensing Visual Indicator Solid State LED Locking Alarm Reset by momentary power interruption Audible Signal 85dBA minimum interrupted tone when individual unit is in alarm or when the supply voltage is reversed Electrical Ratings 2412AT 2424AT or 2424AIT Operating Voltage 12VDC 24VDC Full wave Unfiltered Full wave Unfiltered Current Standby 120 µA Max 120 ...

Page 18: ...AB EXTENSION AT SCRIBED LINE A78 1411 00 A78 534 00 Figure 1 Flush mounting of detector on 4 inch octagon box Figure 2 Detector mounting bracket system and all smoke alarms before the panel gives the required battery low signal When the battery low signal is given the battery should be capable of providing power for another 7 days after which the backup battery should have enough energy left to al...

Page 19: ... 2 Insert the NO ALARM end of the test card fully into the test slot see Figure 6 then slide it counterclockwise until it stops 4 5 4 5 SUGGESTED EOL RESISTOR UL LISTED TWO OR FOUR WIRE PANEL INITIATING LOOP Figure 4 Additional wiring needed for the isolated thermal unit of the 2424AIT detector thermal units are wired to a separate loop A78 1392 01 TEST MODULE SOCKET LED RECESSED TEST SWITCH PUSH ...

Page 20: ...ed on every level of a building Smoke detectors have sensing limitations too Ionization detectors of fer broad range fire sensing capability but they are better at detecting fast flaming fires than slow smoldering fires Photoelectronic detectors sense smoldering fires better than flaming fires Because fires develop in different ways and are often unpredictable in their growth neither type of detec...

Page 21: ...ity 3000 Ft Min 15 M S Latching Alarm Reset by momentary power interruption Electrical Ratings 2412 2424 System Voltage 12 24 DC 4V Maximum Ripple Supply Voltage 11 3 20 VDC Minimum 17 29 VDC Maximum Reset Voltage 73 8 VDC Minimum Standby Current 120 120 µA Maximum Alarm Currents 35 21 3 mA Minimum 77 40 6 mA Maximum The alarm and auxiliary relay operate within the specified voltage ratings Start ...

Page 22: ...wire under terminals Break wire run to provide system supervision of connec tions NOTE Contacts are shown in stand by mode and will transfer in alarm condition Wire connections are made by stripping about 3 8 inch of insulation from the end of the wire sliding the bare end of the wire under the clamping plate and tightening the clamping plate screw Tamper resistance Feature This detector includes ...

Page 23: ...g position of recessed test switch A78 1393 00 1 Remove the detector cover by placing a small bladed screwdriver in the side slot of the detector cover twisting slightly until the cover can be turned coun terclockwise for removal 2 Insert the NO ALARM end of the test card fully into the test slot see Figure 5 then slide it counterclock wise until it stops 3 The detector should not alarm after 20 s...

Page 24: ... bedroom within a building Smoke detectors have sensing limitations too Ionization detectors and photoelectric detectors are required to pass fire tests of the flaming and smoldering type This is to ensure that both can detect a wide range of types of fires Ionization detectors offer a broad range of fire sensing capa bility but they are somewhat better at detecting fast flaming fires than slow sm...

Reviews: