System
login
System
time
setup
Start
Number
Purpose
Notation
0
Not use
1
Open door control
(electric lock DO preset)
2
Doorbell contact output
(relay DO preset)
3
Burglar alarm output
Deploy and withdraw controlled
4
Alarm contact output
Use withdraw to cancel alarm
5
Anti-force contact output
Use[FUN][4][4]to cancel anti-force alarm
Action time set “0” for keeps action until relief
※
Example
DI
FUN +
+
+
+
+ EN
DO
FUN +
+
+
+
+ EN
:【
】
:
6 1 1 2 0
:
7 1 2 1 0 0 3
set up expand open door button, action time 3seconds (set up DI and DO together)
7. System Group and Timer Control Function Operation
this function needs to operate under
login status
【
】
SY120SA SINGLE DOOR CONTROLLER
System
login
System
output
setting
Group
time
setup
Timer
setup
System
logout
System
logout
END
END
Start
6. System DO Function Setup this function needs to operate under login status
【
】
Enter FUN +
+
K
+
F
+
TTT
+ EN .
K
The DO sequent number which wants to set up;
K = 1 as electric lock DO,
K = 2 as relay DO,
K = 3 as expand relay DO,
K = 4 as pre-save DO
F
DO purpose number, please refer the below DO purpose table.
TTT
DO action time set up, range: 000
255, unit: second; default electric lock DO for 5
seconds, relay DO for 2seconds.
7 1 【 】 【 】 【
】
:
:
:
~
DO Purpose Table
- 5 -