background image

11

The discharge quantity must be able to be absorbed 
by the discharge pipe or the collecting vessel!

The plug may only be loosened during this phase, 
never completely unscrewed!

The magnetic separator may only be cleaned 
during backwashing!

• 

Lead the end of the hose to the drain. 

• 

Alternatively, you can use a collecting vessel.

• 

Turn the plug completely out with the magnetic rod. 
The metallic sediments are wiped off and rinsed out 

during the ongoing backwashing process.

• 

Loosen the plug by means of a slotted screwdriver so 
far that free rotation of the handle is ensured.

Note: During the backwashing process, the pressure 

of the heating system must be kept constant. We 

recommend the FillingCombi BA 6628 according to 
DIN EN 1717.

• 

Turn the handle according to the imprinted marking 

in the direction of the arrow as far as possible 
(approximate four complete turns).

• 

The backwashing process has now started

image 7

image 5

image 6

image 8

• 

Turn the handle according to the imprinted marking 
as far as possible (approximate four complete turns).

• 

The backwashing process is completed.

image 9

Summary of Contents for 3425.25.000

Page 1: ...Bedienungsanleitung Instruction manual HF 3425 compact...

Page 2: ...3 Einbau 3 4 R cksp lung Wartung 3 5 Demontage 5 6 Technische Daten 6 7 Abmessungen 7 8 Ersatzteile 8 9 Zubeh r 9 Table of contents 2 1 Range of use 10 2 Overview 10 3 Installation 10 4 Backwashing m...

Page 3: ...aufnehmen Der Filter ist zum Flansch 360 drehbar Richten Sie die Hauptachse senkrecht aus Bild 2 Bild 3 3 Einbau 3 Einbau A Stopfen mit Magnetstab B R cksp lung C Drehbarer Heizungsflansch D B gel un...

Page 4: ...s laufendenR cksp lvorganges abge streift und ausgesp lt L sen Sie den Stopfen mittels Schlitzschraubendre her so weit dass eine freie Drehbarkeit des Griffes gew hrleistet ist Hinweis W hrend des R c...

Page 5: ...der Austausch des Filterelementes erforderlich werden Ersatzteil Bestellnummer 3425 00 900 L sen Sie die Schlauchschelle und entfernen Sie den Schlauch Drehen Sie die Kappe incl Dichtung fest Bild 13...

Page 6: ...ur 10 C 110 C Medium Heizungswasser Min Druck R cksp lung 1 5 bar Einbaulage Hauptachse senkrecht Maschenweite 100 m Durchflussleistung 2 56 m h bei p 0 1 bar 3 20 m h bei p 0 15 bar 3 60 m h bei p 0...

Page 7: ...7 7 Abmessungen 7 Abmessungen B2 B1 A A H B3 Typ Heizungsfilter HF 3425 compact Nennweite DN 25 Bauma e A Rp 1 H 218 mm B1 110 mm B2 176 mm B3 100 mm...

Page 8: ...ition Ersatzteil Benennung Bestellnummer 1 Schraubkappe mit Filtereinheit incl Montageschl ssel 3425 00 900 2 L nette 3425 00 901 3 B gel 3425 00 902 4 Kappe mit Dichtung 3425 00 903 8 Ersatzteile 2 3...

Page 9: ...9 9 Zubeh r AnschlussCenter 3200 3200 15 010 F llCombi BA 6628 20 008...

Page 10: ...360 to the flange Align the main axis vertically images 2 3 3 Installation 3 Installation A Plug with magnetic rod B Backwashing C Rotatable heating flange D Bracket and bezel with month marking Depen...

Page 11: ...g backwashing process Loosen the plug by means of a slotted screwdriver so far that free rotation of the handle is ensured Note Duringthebackwashingprocess thepressure of the heating system must be ke...

Page 12: ...benecessary toreplacethefilterelement Spare part order number 3425 00 900 Loosen the hose clamp and remove the hose Screw the cap incl seal tight image 13 image 10 image 11 image 14 image 15 5 Disasse...

Page 13: ...r Min pressure backwashing 1 5 bar Installation position main axis vertical Mesh width 100 m Flow rate 2 56 m h at p 0 1 bar 3 20 m h at p 0 15 bar 3 60 m h at p 0 18 bar Kvs value 8 0 Installation an...

Page 14: ...14 7 Dimensions 7 Dimensions B2 B1 A A H B3 Type Heating filter HF 3425 compact Nominal size DN 25 Dimensions A Rp 1 H 218 mm B1 110 mm B2 176 mm B3 100 mm...

Page 15: ...15 Position Spare part designation order number 1 Screw cap with filter unit incl mounting key 3425 00 900 2 Bezel 3425 00 901 3 Bracket 3425 00 902 4 Cap with seal 3425 00 903 8 Spare parts 2 3 4 1...

Page 16: ...subject to changes Hans Sasserath GmbH Co KG Hans Sasserath GmbH Co KG Tel 49 2161 6105 0 Fax 49 2161 6105 20 M hlenstra e 62 D 41352 Korschenbroich info SYR de www SYR de 9 Zubeh r Connecting Center...

Reviews: