Section II
General Product Information
006-0006205
UPS-1500 Series
Rev ZC
11 of 60
05/28/2019
• The AC output can be configured with its neutral wire internally grounded to the chassis of the UPS or left
floating for shipboard applications
• The Electronic Breaker option adds fault tolerant, glitch free operation multi-unit for N+1 or N+M redundancy.
This option also allows up to 32 units total in Single Phase, Split Phase, or 3-Phase system.
• The initial set-point frequency of the AC OUTPUT voltage can be 50 Hz, 60 Hz or 400 Hz. Regardless of the
initial set-point frequency, the actual frequency can be set through the communications/control port.
• There is an optional DC INPUT that is specified to comply with MIL-STD-704F and MIL-STD-1275D for 28 V systems.
• Two optional DC OUTPUT capabilities are available: DC1 with up to 500 W capability, and DC2 with up to 1250
W capability an optional droop share.
• RS232 serial port and logic-level I/O communication are included in the standard model. An Ethernet port
providing web and SNMP interfaces is also included in the standard model.
Product Specifications
The following three pages show the electrical and mechanical specifications of the UPS-1500S-1U
high and the UPS-1500E-2U Series of products. Data sheets showing these specifications and
other information can be found at the web site
.
Air intakes
Status Indicator Panel
Status LED
On/Off
17.00"
1.73"
1U
UPS-1500-S-1U
DC1
Output
Option
Ethernet
Port
AC
Output
Exhaust
Fan
Exhaust
Fan
I/O
Port
User
Config
Port
Ground
Stud
(1/4-20)
DC
Input
Option
AC
Input
AC
Circuit
Breaker
UPS-1500-S-1U with DC Input/DC1 Output Option
DC2
Output
Option
UPS-1500-S-1U with DC1 Output/DC2 Output Option
DC1
Output
Option
Ethernet
Port
AC
Output
Exhaust
Fan
Exhaust
Fan
I/O
Port
User
Config
Port
Ground
Stud
(1/4-20)
AC
Input
AC
Circuit
Breaker