SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Page 22 of 52
7.1.1 BACnet Settings
– Additional Information
Enter the following details into the web configuration as seen in
•
Name
– Enter a name for the ProtoAir.
•
Location
– Enter the location of the ProtoAir.
•
Network Number
– Leave as default unless instructed by BMS integrator.
•
Baud Rate (BACnet MS/TP only)
– Select a value of 9600, 19200, 38400, or 76800.
7.1.1.1 Setting the MAC Address for the BACnet MS/TP Network
NOTE: Only 1 MAC Address is set for the ProtoAir regardless of how many devices are connected
to the ProtoAir.
Set the BACnet MS/TP MAC Address of the ProtoAir to a value between 1 to 127 (MAC Master Addresses);
this is so that the BMS Front End can find the ProtoAir via BACnet auto-discovery.
NOTE: Never set a BACnet MS/TP MAC Address from 128 to 255.
Addresses from 128 to 255 are
Slave Addresses and can not be discovered by BMS Front Ends that support auto-discovery of
BACnet MS/TP devices.
Figure 13: BACnet MS/TP Settings Window