Summary of Contents for PumpSaver Plus 234-P

Page 1: ...INSTALLATION Revision B1 INSTRUCTIONS Rapid City SD USA 08 2009 MODEL 234 P II_234 P_B1 2880 North Plaza Drive Rapid City South Dakota 57702 800 843 8848 605 348 5580 fax 605 348 5685...

Page 2: ...is designed to be mounted inside a Grundfos control box to protect 1 3 3hp 2 or 3 wire 230V pumps CONNECTIONS NOTE This product is for installation in a Grundfos control box only 1 Remove the top plas...

Page 3: ...OR START RUN CAPACITOR RELAY REMOVE YELLOW JUMPER YELLOW BLUE RED ORANGE BLACK BLACK L1 SW L2 YEL RED BLK Figure 1 Grundfos Control Box without PumpSaver Plus Installed 2009 SymCom Inc All Rights Rese...

Page 4: ...PACITOR RELAY YELLOW RED ORANGE BLACK BLACK YEL BLK BLU SW L1 L2 YEL RED BLK RESTART DELAY 1 5 to 3hp at 230VAC _ IR LINK Figure 2 Grundfos Control Box with PumpSaver Plus Connections 2009 SymCom Inc...

Page 5: ...ION knob to the desired setting SENSITIVITY The PumpSaver Plus has an adjustment knob to set the underload trip sensitivity Setting SENSITIVITY to the middle position straight up is equivalent to SymC...

Page 6: ...ing the PumpSaver Plus will lock out preventing damage to the pump To reset the PumpSaver Plus remove and re apply power RAPID CYCLING Line Side Upstream Rapid cycling of the line side of the PumpSave...

Page 7: ...will not disable load side detection USING AN INFORMER The PumpSaver Plus is equipped with an infrared LED that will communicate to a SymCom PumpSaver Plus Informer a handheld battery operated diagno...

Page 8: ...DRY RUN DEAD HEAD The PumpSaver Plus has shut the pump off due to a dry run or dead head condition The unit is timing through the restart delay and will try to restart Check for restricted flow or in...

Page 9: ...set DelayTime Over undervoltage 2 seconds All Other Faults Manual 2 225 minutes Input Characterisitcs Supply Voltage 230VAC Load Range 1 3 3hp Frequency 50 1 60Hz Output Characteristics Output Contact...

Page 10: ...2009 SymCom Inc All Rights Reserved 10 NOTES...

Page 11: ...2009 SymCom Inc All Rights Reserved 11 NOTES...

Page 12: ...se see Terms and Conditions at www symcom com Visit us at www symcom com to see our complete product listing Need something special Contact SymCom today for your custom solution 800 843 8848 2009 SymC...