SymCom MotorSaver 250600 Installation Instructions Download Page 3

SymCom warrants its microcontroller based products against defects in material or workmanship 

for a period of five (5) years* from the date of manufacture.  All other products manufactured by 

SymCom shall be warranted against defects in material and workmanship for a period of two (2) 

years from the date of  manufacture.  For complete information on warranty, liability, terms, and 

conditions, please refer to the SymCom Terms and Conditions of Sale document.

* The 520 Series has a one (1) year warranty and the LSRU series has a two (2) year warranty.

 

 

 

                              -3-                                                                 07/16/03

SYMPTOM

LIGHT 

PATTERN

SOLUTION

No lights are on.  The unit 

seems completely dead

N/A

Measure the three line-to-line voltages.  If any of 

the voltages are below 150 VAC, the MotorSaver

 

does not have enough power to operate its internal 

electronics.  This may occur on a single-phased 

system.  If the voltages are correct, call SymCom at 

1-800-843-8848 or 1-605-348-5580.

Red light is blinking 

(On initial installation 

power up).

Turn off the three-phase power.  Swap any two 

leads powering the MotorSaver

 (L1, L2, or L3).  

There is a 50-50 chance of connecting L1, L2, and 

L3 correctly the first time.  Re-apply the three-phase 

power.

Red light is blinking 

(After the motor has been 

previously running).

The incoming lines have been reverse phased.  The  

MotorSaver

 is preventing the motor from running 

backwards.  Correct the phase sequence.

Red light is blinking in this 

pattern.

The voltage is unbalanced or single-phased.  

Measure the incoming line voltages and calculate 

the % unbalance.  If the voltage unbalance does not 

exceed the % unbalance reset value, call SymCom 

at 1-800-843-8848 or 1-605-348-5580.

Red light is on steady.

The voltage is out of tolerance.  Measure the three 

line-to-line voltages.  Calculate the average of 

the three voltages.  If the average is 7% above or 

below the nominal voltage as selected by the LINE 

VOLTAGE ADJUST, the MotorSaver

 is functioning 

properly.  If the voltage is within ±7% of the selected 

line voltage, call SymCom at 1-800-843-8848 or 

1-605-348-5580.

Green light blinks, but 

motor is not running.

The MotorSaver

 is in restart delay.

Green light is on steady, 

but motor does not start.

The MotorSaver

 is in run mode.  Ensure other con-

trol devices are allowing the motor to start.  Check 

control circuit for loose wires or

malfunctioning switches.

TROUBLESHOOTING

Summary of Contents for MotorSaver 250600

Page 1: ...ay to the circuitry to be controlled see Figure No 1 and Figure No 2 A To control a motor connect the normally open contact in series with the magnetic coil of the motor starter as shown in Figure 1 B To sound an alarm connect the normally closed contact in series with the alarm as shown in Figure 2 The Model 250600 is a three phase voltage monitor designed to protect motors regardless of horsepow...

Page 2: ...o the nominal three phase secondary voltage of the potential transformer 2 TIME DELAY RESTART RESTART DELAY Rotate the RESTART DELAY to the desired position The restart delay is the time between the MotorSaver seeing acceptable power and the MotorSaver closing its output contacts The restart delay should be set appropriately for the individual application If the RESTART DELAY is in the MAN manual ...

Page 3: ...3 There is a 50 50 chance of connecting L1 L2 and L3 correctly the first time Re apply the three phase power Red light is blinking After the motor has been previously running The incoming lines have been reverse phased The MotorSaver is preventing the motor from running backwards Correct the phase sequence Red light is blinking in this pattern The voltage is unbalanced or single phased Measure the...

Page 4: ...t 93 High Voltage of setpoint Trip 110 Reset 107 Voltage Unbalance NEMA Trip 6 Reset 4 5 Trip Delay Time Low High Voltage Faults 4 Seconds Unbalance Phasing Faults 2 Seconds Restart Delay Time After a fault or complete power loss Adjustable Manual 2 300 Seconds Output Contact Rating DPDT Pilot Duty 480 VA 240 VAC General Purpose 10 A 240 VAC Transient Protection IEC 1000 4 5 1995 6 kv Power Consum...

Reviews: