SymCom MotorSaver 250600 Installation Instructions Download Page 2

SETTINGS

POWER-UP

Turn on the power to the motor.  The MotorSaver

®

 then goes through its restart 

delay and the LED will flash green (see Table 1).  After the restart delay, the 

MotorSaver

®

 will energize its output contacts and the RUN LIGHT will turn solid 

green.  If the contacts do not energize and the RUN LIGHT does not turn solid 

green, then see the TROUBLESHOOTING section.

07/16/03   

 

                              -2-

1.LINE VOLTAGE ADJUSTMENT:  Rotate the LINE VOLTAGE ADJUSTMENT to  

   the nominal three-phase secondary voltage of the potential transformer.

2.TIME DELAY RESTART (RESTART DELAY):  Rotate the RESTART DELAY to  

   the desired position.  The restart delay is the time between the MotorSaver

®

 

   seeing acceptable power and the MotorSaver

®

 closing its output contacts.  The  

   restart delay should be set appropriately for the individual application.   If the  

   RESTART DELAY is in the MAN (manual) position, then the unit will not 

   automatically restart until it is turned out of the MAN position.

Figure 2: Typical Alarm Wiring Diagram

Table 1: Diagnostic Indicator Lights

RUN
RESTART DELAY
REVERSE PHASE
UNBALANCE / SINGLE PHASE
HIGH / LOW VOLTAGE

Summary of Contents for MotorSaver 250600

Page 1: ...ay to the circuitry to be controlled see Figure No 1 and Figure No 2 A To control a motor connect the normally open contact in series with the magnetic coil of the motor starter as shown in Figure 1 B To sound an alarm connect the normally closed contact in series with the alarm as shown in Figure 2 The Model 250600 is a three phase voltage monitor designed to protect motors regardless of horsepow...

Page 2: ...o the nominal three phase secondary voltage of the potential transformer 2 TIME DELAY RESTART RESTART DELAY Rotate the RESTART DELAY to the desired position The restart delay is the time between the MotorSaver seeing acceptable power and the MotorSaver closing its output contacts The restart delay should be set appropriately for the individual application If the RESTART DELAY is in the MAN manual ...

Page 3: ...3 There is a 50 50 chance of connecting L1 L2 and L3 correctly the first time Re apply the three phase power Red light is blinking After the motor has been previously running The incoming lines have been reverse phased The MotorSaver is preventing the motor from running backwards Correct the phase sequence Red light is blinking in this pattern The voltage is unbalanced or single phased Measure the...

Page 4: ...t 93 High Voltage of setpoint Trip 110 Reset 107 Voltage Unbalance NEMA Trip 6 Reset 4 5 Trip Delay Time Low High Voltage Faults 4 Seconds Unbalance Phasing Faults 2 Seconds Restart Delay Time After a fault or complete power loss Adjustable Manual 2 300 Seconds Output Contact Rating DPDT Pilot Duty 480 VA 240 VAC General Purpose 10 A 240 VAC Transient Protection IEC 1000 4 5 1995 6 kv Power Consum...