13 -
1/05
ANSI/IEEE
C62.41 Surge and Ring Wave Compliance to a
level of 6kV line-to-line
Hi-potential Test
Meets UL508 (2 x rated V +1000V for 1 minute)
Vibration
IEC 68-2-6, 10-55Hz, 1mm peak-to-peak, 2
hours, 3 axis
Shock
IEC 68-2-27, 30g, 3 axis, 11ms duration, half-
sine pulse
Mechanical
Dimensions
3.0"H x 5.1 " D x 3.6"W
Terminal Torque
7 in. lbs.
Enclosure Material
Polycarbonate
Weight
1.2 lbs
Maximum Conductor Size Through 777
0.65" with insulation
Environmental
Temperature Range
Ambient Operating: -20°-70° C (-4°-158°F)
Ambient Storage: -40°-80° C (-40°-176°F)
Pollution Degree
3
Class of Protection
IP20, NEMA 1
Relative Humidity
10-95%, non-condensing per IEC 68-2-3
Programmable Operating Points Range
LV- Low Voltage Threshold
170V (450V*) - HV Setting
HV- High Voltage Threshold
LV Setting - 528V (660V*)
UB- Voltage Unbalance Threshold
2-15% or 999%
MULT- # of Conductors
or CT Ratio (XXX:5)
1-10 Conductors or 100-800 Ratio
OC- Overcurrent Threshold
(20-100A) ÷ MULT or 80-120% of CT
Primary
UC- Undercurrent Threshold
(0, 10-98A) ÷ MULT or 40-100% of CT
Primary
CUB- Current Unbalance Threshold
2-25% or 999%
TC- Overcurrent Trip Class **
5, J5, 10, J10, 15, J15, 20, J20, 30, J30
RD1- Rapid Cycle Timer
0, 2-500 Seconds
RD2- Restart Delay After All Faults Except
Undercurrent (motor cool-down timer)
2-500 Minutes
RD3- Restart Delay After Undercurrent
(dry-well recovery timer)
2-500 Minutes
#RU- Number of Restarts After
Undercurrent
0, 1, 2, 3, 4, A (Automatic)
ADDR- RS485 Address
A01- A99
#RF-Number of Restarts After All Faults
Except Undercurrent
*** 0, 1, oc1, 2, oc2, 3, oc3, 4, oc4, A, ocA
UCTD- Undercurrent Trip Delay
2-60 Seconds
GF- Ground Fault Current Threshold
(3-20A) ÷ MULT or 10-30% of CT Primary
or OFF
NOTES:
SymCom's overload relay can be preprogrammed prior to installation by applying 120VAC
between the L1 and L2 terminals (except 575 volt model). Power applied must be 110VAC or greater.
* 575 volt Model.
** If J Prefix is displayed in trip class setting, jam protection is enabled.
*** If "oc" is displayed in the #RF setting, then overcurrent will be included as a normal fault and the
relay will automatically restart after RD2 expires, otherwise, manual reset is required after an
overcurrent fault.