15
CAUSE
CORRECTIVE ACTION
PROBLEM
Solar heating system
is inefficient
There is air in the circuit
Bleed the circuit
The flow rate is too low
or too high
Make sure that the flow rate cor-
responds to about 30l/h per m
2
.
Pressure is low
Check that the cold pressure of
the system is
approximately 3 bar
The storage cylinder
loses a lot of
heat overnight
There is natural circulation
to the collectors
Make sure that the non-return
valve is sealed and closes
properly Replace it if necessary
The storage cylinder
does not reach the
set temperature
The solar controller needs
programming
Make sure that the ΔT between
the collector and the storage
cylinder is not too high or
too low Set a ΔT of 8-10°C
There is lime scale or sludge in
the tank
Check and clean as necessary
The flow rate is too high
Reduce pump speed and turn
the flow rate adjustment screw
on the valve group to set a flow
rate of 30l/h per m
2
of
collector area
The pump does not work, even
if the collector probe detects
a collector temperature higher
than that in the storage cylin-
der
Maximum temperature has been
exceeded in the collector or in
the storage cylinder
The solar controller has reached
maximum temperature and stop-
ped the pump The pump will
start working again as soon as
the temperature drops in
the collectors
There is no electrical power
Check the safety devices and
electrical connections
The temperature differential is
too great for the pump to opera-
te, or the controller is not working
Check the controller and the
temperature sensor, or reduce
the temperature differential
setting