4. Function

The hand-held micro terminal communicates with the 
motor control system via Modbus commands. 

Factory and user settings are stored in the control system. 
The settings are preserved in the memory even if the line 
voltage is switched off or if the hand-held micro terminal 
is removed. 

If the hand-held micro terminal is not used for more than 
10 minutes, the system automatically switches back to the 
main menu. This reduces the risk of unintentional entry of 
settings. 

The possible settings and displays are shown in the table 
on the next page. Scrolling up and down in the menu 
is done by turning the adjusting knob on the hand-held 
micro terminal, and selections are entered by pressing on 
the adjusting knob. Modification of the selected values 
is done by turning the adjustment knob. Select "Exit" to 
leave the menu.

Standard Modbus address is Address = 54.  
Standard baudrate is set to 38.4 Kbit/s.

The Modbus address and other motor parameters can be 
changed in the hand-held micro terminal. 

The standard Modbus address and baudrate can be 
changed with the hand-held micro terminal in the follow-
ing way:  
With the function selector switch (See illustration) set to 
”0”, set the parameters to the required values with the 
hand-held micro terminal. When the new values have 
been set, set the function selector switch to position "1". 
This activates the user-preset parameters.

The hand-held micro terminal will not work if the 
baudrate is changed from the standard setting of 38.4 
kBit/s and if the hand-held micro terminal is disconnected 
from contact "C".

If the standard baudrate is changed from 38.4 Kbit/s and 
the hand-held micro terminal is disconnected from its con-
nection, it will only be possible to restart communication 
with the hand-held micro terminal if the function selector 
switch is set to position "0". The baudrate will then be 
set to 38.4 Kbit/s. If the function selector switch is subse-
quently set to position "1", the user-preset parameters 
will be activated again.