Installation bracket TBLZ-1-53 for circular ducts or
insulated flat ducts.
The duct diameter can be as small as 100 mm
using the bracket.
• Check that the direction of the arrows is towards the direction of flow.
• Check that the plug for the test hole is properly installed.
• Check that the flow indicator shows flow (rocks).
• Full scale tests with smoke generator are recommended to check the function.
Troubleshooting.
The smoke detector deploys without any smoke
present.
• The smoke detector is faulty, dirty or positioned so that
condensation can build up, see point 8. The detector
insert must be replaced.
Only the control unit triggers an alarm.
• Check that the termination resistor is installed in the last
smoke detector.
• Check that the coil’s resistance is 2.2k
Ω
from the control
unit.
• Check that the control unit is OK by installing the 2.2k
Ω
resistor in the smoke detector output on the control unit.
• Use a voltmeter to check that 21-24 VDC with the cor-
rect polarity is in terminal 1 (-) and terminal 2 (+).
10
8
9
The installation bracket is supplied flat.
The installation bracket is easy to
bend/shape so that it fits circular or
flat ducts.
Secure the bracket’s
legs to the duct.
Hole ø 51
mm.
Rubber
seal
Circular duct.
Insulated flat duct.
Rubber
seal
Final checks
Installing different tubes in different duct widths.
Venturi tube 600 mm.
Venturi tube 1200 mm.
Hole
ø 38 mm
Hole
ø 38 mm
Cut the venturi
tube to the correct
length
The Venturi tube
must go through
the entire duct.
Important!
Hole ø 51 mm
Max. tube of 30 mm outside the duct.
For ducts less than 600 mm use ven-
turi tube of 600 mm, standard.
For ducts between 600 mm and 1400
mm, use venturi tube of 1500 mm.
•
Cut the tube to the
correct length.
•
Insert the end plug.
•
Install the seal
•
Install rubber seal TET
26-35 as a bearing.