5. Installation and location

Position the smoke detector in the direction of flow, accord-
ing to the arrow on the cover. The smoke detector is loca-
tion-independent and can be installed on any side of the 
duct.
In the event of large temperature differences, e.g. outside 
or in cold attics, the detector must be insulated from the 
surrounding air (due to the risk of condensation build-up in 
the detector housing).
To ensure optimum combustion gas detection the smoke 
detector must be positioned so that the distance 

to

 the 

nearest interfering source in the duct (see example of inter-
fering sources below), in the direction of airflow, is the 
same as 3 x the duct’s hydraulic diameter. Nearest location 

after

 an interfering source must be at least 5 x the duct’s 

hydraulic diameter.

       

MIN 3xdh

MIN 5xdh

GX

GX

MIN 3xdh

MIN 5xdh

GX

GX

MIN 3xdh

MIN 5xdh

GX

GX

MIN 3xdh

MIN 5xdh

GX

GX

MIN 3xdh

MIN 5xdh

GX

GX

MIN 5xdh

GX

M

IN 3xd

h

GX

MIN 5xdh

GX

M

IN 3xd

h

GX

GX

MIN 3xdh

GX

GX

MIN 3xdh

MIN 5xdh

d  = D

Ø D

h

d  = 

h

2xHxB

H+B

H

B

Hydraulic diameter
  CIRCULAR DUCT 

 

 

  RECTANGULAR DUCT

MIN 3xdh

MIN 5xdh

GX

GX

MIN 3xdh

MIN 5xdh

GX

GX

MIN 3xdh

MIN 5xdh

GX

GX

MIN 3xdh

MIN 5xdh

GX

GX

MIN 3xdh

MIN 5xdh

GX

GX

MIN 5xdh

GX

M

IN 3xd

h

GX

MIN 5xdh

GX

M

IN 3xd

h

GX

GX

MIN 3xdh

GX

GX

MIN 3xdh

MIN 5xdh

d  = D

Ø D

h

d  = 

h

2xHxB

H+B

H

B

Examples of sources of disturbance

FAN

DAMPER

SILENCER

COIL

BEND

BRANCH

ADAPTER

EXTRACT AIR

SUPPLY AIR

AIR HANDLING UNIT

Summary of Contents for TBLZ-1-49-a GOLD

Page 1: ...cket when installing on circular or insulated ducts 2 Function When combustion gas is detected the LED on the detector lights red and the alarm signal is forwarded to the control unit If the smoke detector becomes dirty it becomes more sen sitive and switches to alarm mode more slowly To prevent false alarms if dirty the detector is equipped with a service alarm green LED This indicates that the d...

Page 2: ...he duct see example of inter fering sources below in the direction of airflow is the same as 3 x the duct s hydraulic diameter Nearest location after an interfering source must be at least 5 x the duct s hydraulic diameter MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh GX GX MIN 3xdh MIN 5xdh MIN 5xdh GX MIN 3xd h GX MIN 5xdh GX MIN 3xd h GX GX MIN 3xdh G...

Page 3: ...tector on the duct Secure the detector box at 3 points at the markings of the arrows Important IMPORTANT The direction arrows see the shape of the detector s base or the top of the housing must point in the same direction as the air flow in the duct End plug Stop screw Seal 5 Flow indicator The detector is equipped with an indicator a red plastic tab which when the detector is correctly installed ...

Page 4: ...resistance is 2 2kΩ from the control unit Check that the control unit is OK by installing the 2 2kΩ resistor in the smoke detector output on the control unit Use a voltmeter to check that 21 24 VDC with the cor rect polarity is in terminal 1 and terminal 2 10 8 9 The installation bracket is supplied flat The installation bracket is easy to bend shape so that it fits circular or flat ducts Secure t...

Reviews: