background image

GB.TBLAMT.141001

Swegon reserves the right to alter specifications.

2     www.swegon.com

3. Installation

For the installation of air heaters in duct systems, see the 
individual instructions entitled: Installation Instructions for 
Duct Accessories. 

The capacity of the air heater with Thermo Guard is inde-
pendent on the direction of airflow through the air heater. 
See Fig. 1.

The return pipe must always be connected to the connec-
tion marked Thermo Guard. See figure. 2.

Use a pipe wrench to restrain the pipe connections of the 
air heater when tightening the external pipe connections 
to avoid damaging the tubes in the air heater.

Always fill the air heater with liquid from the lower con-
nection. Vent the system before you commission it.

The supply flow temperature should be between 55-70°C.

The available pump pressure must not be higher than 25 
kPa if the inlet flow temperature is higher than 65°C. If 
the inlet flow temperature is between 55°C and 65°C, the 
available pump pressure should be between 12–40 kPa. 

If the inlet flow pressure substantially exceeds the rec-
ommended pressure, a pressure limiting device, which 
reduces the pressure to the recommended level, may be 
necessary.  

A pressure limiting device should not be installed in venti-
lation systems that utilize hot water supplied from a dis-
trict heating plant, since such a device could contribute to 
high recirculated water temperatures.

4. Operation 

Thermo Guard frost damage protection

Frost damages in the air heater most often cause the tube 
bends to burst. 

Research has shown that the tubes in the air stream are 
the first ones to freeze. When an ice plug forms inside a 
tube, it expands longitudinally along the tube and this 
increases the water pressure in the bend causing it to 
burst.  Hence, it is not the ice itself that causes the bend 
to burst, but the high water pressure in the bend brought 
about by the ice inside the tube.

Thermo Guard frost-damage-protected air heaters operate 
according to the principle that involves relieving abnormal 
pressure rise in tube bends by draining water from the 
tube bends to the return pipe of the air heater.

This enables the air heater to cope with freezing without 
damage.   However it is important to note that possible 
valves installed in the return pipeline must not be closed 
since doing so will put the Thermo Guard function out of 
action.

Thermo Guard frost damage protection is the only one of 
its kind on the market that offers frost damage protection 
in the event of a power failure and similar service disrup-
tions.

Fig. 1

TBLA connections with Thermo Guard

Thermo

Guard

Swegon

Thermo Guard  
connection

T piece

Frost guard sensor

Shut-off valve (must not be 
closed if freezing is likely – 
to relieve pressure).

Pressure limiting device, 
if required

Heating 
water

Shut-off valve

Control 
valve

Fig. 2

AB

 

A

5. Electrical connections

For particulars of the electrical connections of the valve 
actuator and circulation pump, see the separate instruc-
tions for the TBVL/TBVA valve kit.

Reviews: