GB.EXCHSILV2.141119

We reserve the right to alter specifications.

2     www.swegon.com

2. Technical data

Power supply 

50-60 Hz,  

 

 

 

1x230 V AC    

 

 

-10%/+15 %

Rated motor shaft power: 

0.38 kW

Motor current cons. (max. load) 

4.5 A

Maximum fuse protection 

10 A

Ambient air temp., operation 

-40/+40 °C

Ambient air temperature, storage  -40/+70 °C
Enclosure class 

IP54

Control voltage 

0-10 V DC

Weight 

4.9 kg

3. Function

General

The motor control system advantageously replaces the 
traditional solution with gear motor. The step motor has 
uniform torque across the entire rpm range, in contrast 
to gear motors that lose torque at low and high speeds 
of rotation respectively. The step motor's constant torque 
curve provides an essentially greater operating range 
where the speed of rotation can be controlled with preci-
sion. It is therefore possible to control the heat recovery in 
an energy-optimum manner and achieve a more accurate 
temperature.

The heat exchanger control system is controlled with 0 – 
10 V signals.

The step motor is controlled in micro steps with sinusoidal 
constant current for ensuring motor shaft rotation with 
uniform torque throughout the revolution. This prevents 
torque pulses and at the same time provides quieter 
operation.

Rotation monitor

The rotation monitor consists of an inductive sensor. 

When the rotation monitor is mounted correctly, the sen-
sor's LED flashes yellow each time the detection surface 
passes the rotation monitor. 

Operation

LED indications

The junction box has 2 integrated LEDs located under the 
cover. They are therefore not visible when the cover is 
mounted.

The green LED is constantly lit when voltage is supplied.. 

The red LED is lit if at least one active alarm has been initi-
ated.

Warning 

 The chassis on the heat exchanger control 

system can become very warm!

 

Warning! Do not repair the heat exchanger con-
trol system at the site. Never attempt to repair a 
defective control system unit. 

Contact the supplier to obtain a replacement unit.

Fig. 1. Dimensions

Summary of Contents for SILVER C RX

Page 1: ...ntil the entire air handling unit where the above mentioned heat exchanger control system is integrated has been declared to conform to relevant regulations in Machinery Directive 98 37 EEC and to exi...

Page 2: ...more accurate temperature The heat exchanger control system is controlled with 0 10 V signals The step motor is controlled in micro steps with sinusoidal constant current for ensuring motor shaft rota...

Page 3: ...ing sector To reverse the motor s direction of rotation transpose two optional conductors to Motor Terminal V U W See Fig 6 Automatic restart after alarm The heat exchanger control system automaticall...

Page 4: ...reset lowest and highest speeds See Fig 3 and 4 The Control with 0 10 V DC function is described in Section 3 Function Connect the start stop signal cable leads in the junction box to Ter minals 7 Sta...

Page 5: ...ER C units the heat exchanger control system is located inside the fan or filter section to the left of the centre section in the lower level viewed from the inspection side For access open the inspec...

Page 6: ...op Fig 5 There is no 0 10 V DC control signal Check that the 0 10 V DC control signal is correctly connected to Terminals 13 and 14 in the heat exchanger control system junction box marked GND and 0 1...

Page 7: ...Help to protect the environment by ensuring correct disposal of the packaging and use the products in accord ance with applicable environmental regulations Disposal of the product Products with this m...