background image

GB.FUNKMIRU.121204

Swegon reserves the right to alter specifications.

12     www.swegon.com

10.3 MIRU Control

Seven different alarms can be shown on the display screen 
on the control panel of the MIRU Control.

No. 1 FAN TRIPPED  

 

The motor control system of the MIRUVENT fan has 
tripped and initiated a group alarm. To reset the alarm, see 
Section 10.1 on how to reset alarms.

No. 2. FAN COMM. DEFECTIVE  
MIRU Control cannot establish correct communication 
with the MIRUVENT fan control system. 

Check that power is being supplied to the MIRUVENT fan 
and that the green LED on the motor control system is 
flashing.  
To reset the alarm, isolate the power supply for 2 minutes.

No. 3 FLOW SENSOR DEFECTIVE  
MIRU Control cannot establish correct communication 
with the pressure sensor for flow measurement.

Check that the pressure sensor is set to Address 0, and 
that the communication cable is correctly connected. See 
Section 4.2. 

When everything is correct; the lower LED on the pressure 
sensor should be lit with a steady flow and the upper LED 
should be flashing.

No. 4 PRESSURE SENSOR DEFECTIVE   

 

MIRU Control cannot establish correct communication 
with the pressure sensor for flow regulation.

Check that the pressure sensor is set to Address 1, and 
that the communication cable is correctly connected. See 
Section 4.2. 

When everything is correct; the lower LED on the pressure 
sensor should be lit with a steady flow and the upper LED 
should be flashing.

No. 5 TEMPERATURE SENSOR DEFECTIVE    
The MIRU Control unit cannot establish correct communi-
cation with the outdoor temperature sensor.

Check that the temperature sensor is correctly connected. 
See Section 4.3. 

No. 6 FLOW/PRESSURE DEV.   
The airflow or duct pressure continuously deviates by 
+/-20% from the setpoint. 

Check that the tubes to the pressure sensor are correctly 
connected. See Section 4.2.

To reset alarms.

If any of the above alarms are displayed on the control 
panel, and nothing else is specified on the list of alarms 
above, reset the alarm by pressing the button under the 
RESET text on the MIRU Control panel.

Summary of Contents for MIRU Control

Page 1: ...l via Modbus 2 Material Specification Control of MIRUVENT fan via MIRU Control MIRU Control equipment TBMZ 11 MIRUVENT fan with type code MIRU x xx xx 3 0 or MIRU x xx xx 1 x x model and size codes Pr...

Page 2: ...tions cable not included in supply 3 wire Twisted pair cables are recommended If shield is to be used the shield must be con nected to the AHUs roof fans chassi and not connected to MIRU Control not i...

Page 3: ...requency inverter Place the upper section in the groove designed to receive it in the lower section Connect the communication cable to terminals A B and GND next to the Bus marking See illustration MI...

Page 4: ...white tapping to pressure port on the pressure sensor Set the pressure sensor function selector switch to position 0 See illustration Connect the modular cable to an optional modular con nection in th...

Page 5: ...e DIN rail inside the electrical cubicle of the GOLD unit or on another appropriate loca tion near this cubicle Connect the modular cable between one of the modular connections on the cable adapter an...

Page 6: ...ld be set to the ON position See illustration If several MIRU Control units are connected to the same GOLD unit the MIRU Control that is last in the communi cation loop should have its jumper JP2 TERM...

Page 7: ...y setting m s Fan regulation control MIRU Control is factory preset for pressure regulation Press reg sensor ON Pressure regulation requires connection of a pressure sensor set for pressure regulation...

Page 8: ...see menu 2 10 MIRU Control unitsMax 10 units MIRU Control can be connected to one GOLD unit If two to ten MIRU Control units are connected to one GOLD unit the Modbus ID for each MIRU Control must be...

Page 9: ...er to be able to start the fan Operating times via the Miru Control panel Set the current date and time under Time Date in the main menu Four different time channels can be set under Time chan nel If...

Page 10: ...sed by the corresponding rate If EA is selected the extract airflow in the GOLD unit will be decreased by the corresponding rate Under Miru Control Time channel you must select the following for each...

Page 11: ...ncy inverter 5 flashes Phase failure on supply voltage phase lacking 6 flashes Fluctuating supply voltage between phases 10 flashes Communication failure between upper and lower sections 11 flashes Me...

Page 12: ...ng is correct the lower LED on the pressure sensor should be lit with a steady flow and the upper LED should be flashing No 4 PRESSURE SENSOR DEFECTIVE MIRU Control cannot establish correct communicat...

Reviews: