LOCUS
4
Swegon reserves the right to alter specifications. 22/12/2022
Connection
LOCUS is connected to controller URC1 with the help of RJ12.
Slave loop, port 24 or 25.
Modbus
Modbus settings/Properties
ID:
247
Protocol:
RS-485 Modbus RTU
Bus speed/Baud rate:
38400 bit/s
Data bits:
8
Parity:
none
Stop bits:
1
Configuration can be performed via the LOCUS panel by
going to the “Parameters” menu.
There, you can access all Modbus settings for the URC
controller.
|
1
2
|
3
4
|
5
6
|
7
8
|
9
10
11
12
|
|13
14
15
|16
17
18
|1
9
20
21
|
| 2 2 | 2 3 | 2 4 | 2 5 |
Figure 5. Controller URC1.
Figure 4. Room unit LOCUS.
Commissioning
Note: Check all settings and parameters during
commissioning. In this way, you can guarantee that
the selected application will work correctly.