Swegon IQlogic+ Function Manual Download Page 8

GB.BlueBox.180415

Swegon reserves the right to alter specifications.

8     www.swegon.com

BT1

MF2

BT40

BT50

G20

G10

BT10

MF10

Modbus

0-10 V

GOLD

Supply 

air

Swegon 
chiller

AQUA Link

AYC  

See the func-
tion guide for 
the AYC.

Comfort 

modules

3.2 Control of cooling energy to the GOLD 
and comfort modules via the Swegon  
chiller and AQUA Link

3.2.1 Control of cooling energy to the GOLD

The cooling capacity of the supply air is controlled via valve 
actuator MF2 and an module (extra regulation 
sequence function, see separate instructions for the TBIQ 
module) preset for cooling (0-10 V). Cooling can 
be activated in the hand-held terminal of the GOLD air 
handling unit (see the Operation and Maintenance Instruc-
tions for the GOLD).

3.2.2 Control of cooling energy  
to the comfort modules

See the function guide for All Year Comfort (AYC).

3.2.3 Swegon chiller and AQUA Link

Communication with the chiller can be activated under 
Functions in the hand-held micro terminal of the GOLD 
unit. See Section 5.

Communication with AQUA Link takes place via the 
IQlogic

+

 module (function selector switch set to 5) which 

controls and manages alarms from pump G20. The 
module is located in the AQUA Links cubicle. 

The chiller’s water temperature setpoint is controlled by 
the GOLD unit and is determined by the cooling load in 
the ventilation system. The temperature setpoint from 
the AYC function is compared with the ordinary cooling 
supply air setpoint and the lowest value of these is trans-
mitted as a setpoint to the chiller. 

Circulation pump G20 located inside the AQUA Link is 
started and stopped via the GOLD unit. When the GOLD 
unit is in operation and valve MF2 or MF10 is open more 
than 5%, circulation pump G20 starts up.

Optimisation function active:

Applies to the supply air cooling setpoint.
To ensure the best functionality when the optimisation 
function is activated, the value for cooling diff.  (2 K*) 
should be set to the same value as that set in the chiller, 
see Section 5.  
If the temperature by temperature sensor BT40 (reference 
water) is within 2K* from the refrigerant  temperature 
setpoint and if it has been so during a continuous period 
of more than 60 seconds* the optimisation function is 
allowed.
If the optimisation function is allowed and valve MF2 is 
fully open (100%*) the controller decreases the refriger-
ant temperature setpoint at a rate of 0.3K/minute*.
If the optimisation function is allowed and valve MF2 is 
open less than 80%*, the controller increases the refriger-
ant temperature setpoint at a rate of 0.6K/minute*.

* Factory setting. The value can be changed.

Summary of Contents for IQlogic+

Page 1: ...nsumption The supply air energy to a water coil is controlled by a valve Optimisation of the valve position so that it always strives to be fully open and instead control the water temperature saves e...

Page 2: ...egulate the flow If the temperature by temperature sensor BT50 is higher than the temperature by temperature sensor BT30 the function does not allow valve MF2 to regulate the flow forces it to close O...

Page 3: ...nsor BT50 is higher than the temperature by temperature sensor BT30 the function allows valve MF1 to regulate the flow If the temperature by temperature sensor BT50 is lower than the temperature by te...

Page 4: ...y open 100 the controller decreases the refriger ant temperature setpoint at a rate of 0 3K minute If the optimisation function is allowed and valve MF1 is open less than 80 the controller increases t...

Page 5: ...emperature by temperature sensor BT50 is higher than the temperature by temperature sensor BT30 the function does not allow valve MF2 to regulate the flow forces it to close If dehumification is activ...

Page 6: ...BT1 calls for heating the function transmits a start signal and heating medium setpoint 40 C to the heat pump via Modbus If the temperature by temperature sensor BT50 is higher than the temperature by...

Page 7: ...on is allowed If the optimisation function is allowed and valve MF1 is fully open 100 the controller decreases the refriger ant temperature setpoint at a rate of 0 3K minute If the optimisation functi...

Page 8: ...Links cubicle The chiller s water temperature setpoint is controlled by the GOLD unit and is determined by the cooling load in the ventilation system The temperature setpoint from the AYC function is...

Page 9: ...us contact on the cable adapter The communication cable between the chiller heat pump control equipment and TBLZ 64 cable adapter should be wired according to one of the alternatives below The cables...

Page 10: ...external SMART Link communications interface Wiring terminals SMART Link communications interface Wiring terminals for the TBLZ 64 cable adapter 1 2 3 4 Wiring terminals junction box chiller heat pum...

Page 11: ...Connection via built in SMART Link communications interface Wiring terminals for the TBLZ 64 cable adapter 1 2 3 4 A4 A2 Wiring terminals SMART Link communications interface Communications interface...

Page 12: ...m 4 1 4 Alternative 4 Connection via internal iPro link communications interface ASM1 iPro link SERI1 485 TTL A2 IC208CX Wiring terminals for the cable adapter 1 2 3 4 SERI1 A2 ASM1 Cable adapter TBLZ...

Page 13: ...ight to alter specifications www swegon com 13 4 1 5 Alternative 5 Connection via external A2 com munications interface RS485 slave Wiring terminals for the TBLZ 64 cable adapter 1 2 3 4 A2 A2 RS485 s...

Page 14: ...19 Heat Cool 20 C 21 NO 22 C 23 NO 24 C 25 NO 26 C 27 NO 28 P 29 G 30 G0 31 G 32 G0 24V AC Sensor 1 Sensor 2 Sensor 4 Sensor 3 Com 6 Com 7 Com 8 Com 9 Com 10 Com 11 33 34 G 35 G0 36 Y 37 U 38 39 40 2...

Page 15: ...temperature of the refrig erant and heating medium returning to the chiller heat pump Set the limit for the outdoor temperature mini mum permitted operating temperature The function for the optimizati...

Reviews: