background image

Accessories

Commissioning box:

ALS. The ALS box is made of galvanized sheet steel and contains 
a removable commissioning damper, fixed measurement tappings 
and sound absorbing material*

)

 with reinforced surface layer.

The ALS commissioning box is available with one or two differences 
in dimension between the inlet and the outlet and also a version 
for low installation where a low overall height is required. The ALS 
commissioning box is then supplied without outlet branch.
*Fire resistance rated to B-s1,d0 in accordance with EN ISO 11925-2.

Frame:

SAR K. For aesthetic installation of a lowered air diffuser.

Adapter:

ADAPTER, for adaptation to various variants and makes of 
systemized false ceilings: Ecophon, Gyproc, Dampa etc. Also 
used for adaptation to optional sizes of lay-in ceilings, for 
instance 625 x 625 or 675 x 675.

Installation

To dismantle the diffuser face, insert a thin object, for example a 
Quick Access card or the equivalent, in between the diffuser face 
and the diffuser backing box in order to release the springs. Move 
the card from the centre out towards the corner, see Figure 2.
The inlet spigot of the air diffuser backing box can be secured to 
the connecting duct by means of self-tapping screws or a blind 
rivets. For flush-mounting in fixed false ceiling constructions, 
secure the terminal by means of screws into place in the frame-
work through either the sides or top of the diffuser backing box. 
The air diffuser and commissioning box in the version for low 
installation height must be centred and jointed together using the 
locking strip supplied. Secure the air diffuser in the correct posi-
tion with self-tapping screws or pop rivets in the underside of the 
commissioning box.
For mounting in modular false ceilings, it is advisable to select air 
diffusers with outer dimensions of 595 x 595 mm. Position these 
directly down in the T-bar framework, and then secure them to 
the duct system or to the commissioning box.
If an ALS commissioning box is used, it must be secured to the 
building structure by means of hangers or mounting brackets. 
The distance between the commissioning box and the air diffuser 
can be increased by as much as 500 mm with an ordinary circular 
duct without having to lengthen the measuring tubes and damper 
adjustment cords. See Figures 3 and 4.

Commissioning

Commissioning should be carried out with the air diffuser face 
mounted. Pull the measuring tubes and damper adjustment cords 
out through the air diffuser face. Then connect the manometer to 
the correct measuring tube. The red and the blue tubes respectively 
from the ALS commissioning box of the one or two-step version 
are used for supply air. For extract air, always use the transparent 
tube. The rated coefficient of performance of the air diffuser can 

Figure 1. Commissioning.

Quick 

Access

HAWK CEILING

Tomelilla

Sweden

200-600

+ALS 160 -200/125 -200

k

q

k = XX / XX

P

TILLUFT / SUPPLY AIR

TILLUFT / SUPPLY AIR

FRÅ

NLU

FT /

 EXTR

ACT AI

R

k

P

q

=

k

P

q

=

 

 

(    )

2

be used in a calculation to determine the required commissioning 
pressure. Conclude commissioning by adjusting the damper to the 
correct blade position, tie a commissioning knot in the damper 
cords to indicate the damper position. See Figure 1.
Measurement accuracy and requirement on straight duct before 
the commisioning box, see Figure 3. The requirements of straigh 
duct depends on the type of disturbance before the commis-
sioning box. Figure 3 shows a bend, a dimensional change and a 
T-piece. Other types of disturbances requires at least 2xD straight 
(D = connection dimension) for measurement accuracy of ± 10% 
of the flow.
The rated coefficient of performance (K-factor) is specified on the 
identification label of the product and in the relevant commission-
ing instructions at www.swegon.com.

Maintenance

The air diffuser can be cleaned, if necessary, using lukewarm water 
with dishwashing detergent added or by vacuum cleaning using a 
brush nozzle. The duct system can be reached for cleaning after 
opening the air diffuser face. If a type ALS commissioning box is 
used, swing the air diffuser face to the side on its hinges so that 
you then can grip the handle of the tubular damper casing and 
rotate it out of its holder. See Figure 6.

q

 = flow reading l/s

p

 = current pressure reading (Pa)

k

 = commissioning factor

k-factor

HAWK 

Ceiling a

Installation – Commissioning – Maintenance

20180814

Summary of Contents for HAWK Ceiling a

Page 1: ...kets The distance between the commissioning box and the air diffuser can be increased by as much as 500 mm with an ordinary circular duct without having to lengthen the measuring tubes and damper adjustment cords See Figures 3 and 4 Commissioning Commissioning should be carried out with the air diffuser face mounted Pull the measuring tubes and damper adjustment cords out through the air diffuser ...

Page 2: ... commissioning box with low installation height Figure 3 Installation alternatives Figure 2 Quick Access Installation Figure 5 To dismantle the damper 0xD 5 0xD 5 2xD 10 HAWK Ceiling 2 Swegon reserves the right to alter specifications 20180814 ...

Page 3: ...1 250 600 595 504 332 199 250 354 311 315 600 595 622 388 249 315 395 352 400 600 595 767 488 314 400 455 Size F1 F2 G1 G2 H K Weight kg 125 600 113 70 175 132 270 80 5 5 160 600 113 70 188 145 315 80 6 2 200 600 113 70 205 162 375 100 7 0 250 600 113 70 225 182 465 115 8 7 315 600 93 50 230 187 575 140 11 8 400 600 93 262 712 175 15 0 HAWK Ceiling with ALS 2 steps Size A B C ØD Ød E1 E2 160 600 5...

Page 4: ...ue 200 250 250 500 28 4 Red 200 250 250 600 32 5 28 5 Red 200 315 315 500 30 3 Blue 250 315 315 500 31 8 Red 200 315 315 600 37 0 34 2 Blue 250 315 315 600 39 4 35 3 Red 315 400 400 600 50 9 Red Number of measuring tubes 1 Extract air ALSd HAWK C extract air Size Size Standard Colour of the tube 200 250 250 600 19 1 Transparent 250 315 315 600 25 4 Transparent 315 400 400 600 34 9 Transparent Numb...

Reviews: