GB.PREHEAT.130225

Specifications are subject to change without notice.

6     www.swegon.com

INSTALLATION

FUNCTIONS

*FUNCTIONS*
TEMPERATURE
FLOW/PRESSURE
FILTER
OPERATION
HEATING
COOLING
MOISTURE
ReCO2

IQNOMIC PLUS

*IQNOMIC PLUS*
NO. 8 BOOSTER TERMINAL

NO. 9 PREHEAT

NO. A XZONE HEATING

DEACTIVATE 

EL AIR HEATER P/P
EL AIR HEATER 0-10 V
W. COIL WITH FP
W. COIL WITHOUT FP

*PREHEAT*
FUNCTION, OFF/ON

SETTINGS

*PREHEAT*
TEMPERATURE 5.0°C.

5. Adjustment

For basic facts on how to use the hand-held micro termi-
nal, see the Operation and Maintenance Instructions for 
the GOLD unit. 

The PREHEAT function must be manually activated, under 
INSTALLATION – FUNCTIONS – IQNOMIC PLUS in the 
hand-held terminal.

Select PREHEAT. 

Under ”FUNCTION, OFF/ON”, select the type of air heater 
connected. 

Under “SETTINGS”, select the desired setpoint in

*PREHEAT*

FUNCTION, OFF/ON

SETTINGS

Summary of Contents for Gold TBLE Series

Page 1: ...an also be installed in an exhaust air or extract air duct Preheating is interlocked to follow the supply air flow This means that the function cannot be used in the exhaust air or extract air duct while the supply air fan is switched off and the extract air fan alone is operating The preheating function has a relay function for control ling a circulation pump if required 2 Material Specification ...

Page 2: ...e settings as those for the air heater for postheat ing The preheating function does not include any capacity reduction feature for unit operation in the low airflow mode An overheating protection with normally closed contacts monitors the state of the air heater If the contacts open an alarm is initiated Air heater for hot water with anti frost monitor The heat retaining function is automatically...

Page 3: ...rol unit of the air handling unit Digital temperature sensors require correct polarity they are con nected Communication cable to the control unit of the air handling unit where it should be connected to one of the connections for the Internal EIA 485 The function selector switch must be set to the 9 position Air heater for hot water T1 GR R1 RD Jack for wall moun ting 019611 Brown White S S 1 6 3...

Page 4: ... 24 21 20 22 23 L1 L2 456 7 8 9 A B C D E F 0 1 2 3 Temp sensor for preheated air 0 10 V Electric air heater Swe gon Standard with control cable 8 pole G0 Overheating protection S Communication cable to the control unit of the air handling unit where it should be con nected to one of the connec tions for Internal EIA 485 Function selector switch in Position 9 S R1 RD Jack for wall mounting 8 pole ...

Page 5: ...se Control 1 6 3 2 4 5 7 12 9 8 10 11 13 18 15 14 1617 19 24 21 20 22 23 L1 L2 456 7 8 9 A B C D E F 0 1 2 3 Temp sensor for preheated air 0 10 V Electric air heater G0 S Communication cable to the control unit of the air handling unit where it should be connec ted to one of the connections for Internal EIA 485 Function selector switch in Position 9 S R1 RD T1 GR Jack for wall moun ting 019611 Ove...

Page 6: ...EATER 0 10 V W COIL WITH FP W COIL WITHOUT FP PREHEAT FUNCTION OFF ON SETTINGS PREHEAT TEMPERATURE 5 0 C 5 Adjustment For basic facts on how to use the hand held micro termi nal see the Operation and Maintenance Instructions for the GOLD unit The PREHEAT function must be manually activated under INSTALLATION FUNCTIONS IQNOMIC PLUS in the hand held terminal Select PREHEAT Under FUNCTION OFF ON sele...

Page 7: ...m the GOLD unit s control unit A flashing light emitting diode L1 indicates correct com munication with the GOLD unit s control unit Temperature sensor Current temperatures can be read under INSTALLATION READINGS IQNOMIC PLUS PREHEAT If the tempera ture readings are reasonable wiring has been carried out correctly 1 6 3 2 4 5 7 12 9 8 10 11 13 18 15 14 1617 19 24 21 20 22 23 L1 L2 456 7 8 9 A B C ...

Page 8: ...GB PREHEAT 130225 Specifications are subject to change without notice 8 www swegon com ...

Reviews: