Function Guide for the GOLD,  
Preheating

1. General

When it is cold outside and the humidity is high, preheat-
ing the incoming outdoor air will prevent condensation 
from forming on outdoor air filter surfaces in the air han-
dling unit. 

Preheating the air also reduces the risk of frosting in the 
heat exchanger. 

Preheating the outdoor air may also be required during 
periods of extremely low temperatures outside. If the air is 
preheated to -20°C, for instance, this prevents the pres-
sure sensor and the frequency inverter from having to 
operate under excessively low ambient temperature condi-
tions. 

The preheating function

 can control the air heater as fol-

lows:
– Electric air heater, pause/pulse control signal.
– Electric air heater, 0–10 V.
– Air heater for hot water, 0-10 V control signal, with anti-
frost monitor/heat retaining function.
– Air heater for hot water, 0-10 V control signal, without 
anti-frost monitor/heat retaining function. 

Type TBLF air heaters for preheating are designed for 
installation in an outdoor air duct, however they can also 
be installed in an exhaust air or extract air duct. 

Preheating

 is interlocked to follow the supply air flow. This 

means that the function cannot be used in the exhaust air 
or extract air duct while the supply air fan is switched off 
and the extract air fan alone is operating.

The preheating function

 has a relay function for control-

ling a circulation pump, if required.

2. Material Specification

Air handling unit  

 

All types of GOLD

 

Option 1

Air heater, water, for preheating  

TBLF-1-aaa-aaa

 

The TBLZ-1-53-1 Control of air heater for preheating is 
included. 

or

 

Air heater, water,  

 

for preheating (not size 50-120) 

TCLF-1-aa 

The TBLZ-1-53-1 Control of air heater for preheating is 
included.

Option 2

Electric air heater, type Swegon standard,  

 

for preheating (not size 50-120) 

TBLE

 

Control of air heater for preheating.    

TBLZ-1-53-0

Consists of: IQnomic Plus, TBIQ-2-1
 

 

Temperature sensor (set) for duct mounting,    

  

TBLZ-1-30.

 

 

Communication cable, BC1-1 (L = 250 mm).

  

Without anti-frost monitor sensor

Jack, modular/terminal block  

TBLZ-1-55

Option 3

Air heater of other type than TBLF/TCLF or TBLE. 

Control of air heater for preheating.    

TBLZ-1-53-a

Consists of: IQnomic Plus, TBIQ-2-1
 

 

Temperature sensor (set) for duct mounting,    

  

TBLZ-1-30.

 

 

Communication cable, BC1-1 (L = 250 mm).

Code: 

a = 0

  without anti-frost monitor sensor

 

    

a = 1

  with anti-frost monitor sensor 

Summary of Contents for Gold TBLE Series

Page 1: ...an also be installed in an exhaust air or extract air duct Preheating is interlocked to follow the supply air flow This means that the function cannot be used in the exhaust air or extract air duct while the supply air fan is switched off and the extract air fan alone is operating The preheating function has a relay function for control ling a circulation pump if required 2 Material Specification ...

Page 2: ...e settings as those for the air heater for postheat ing The preheating function does not include any capacity reduction feature for unit operation in the low airflow mode An overheating protection with normally closed contacts monitors the state of the air heater If the contacts open an alarm is initiated Air heater for hot water with anti frost monitor The heat retaining function is automatically...

Page 3: ...rol unit of the air handling unit Digital temperature sensors require correct polarity they are con nected Communication cable to the control unit of the air handling unit where it should be connected to one of the connections for the Internal EIA 485 The function selector switch must be set to the 9 position Air heater for hot water T1 GR R1 RD Jack for wall moun ting 019611 Brown White S S 1 6 3...

Page 4: ... 24 21 20 22 23 L1 L2 456 7 8 9 A B C D E F 0 1 2 3 Temp sensor for preheated air 0 10 V Electric air heater Swe gon Standard with control cable 8 pole G0 Overheating protection S Communication cable to the control unit of the air handling unit where it should be con nected to one of the connec tions for Internal EIA 485 Function selector switch in Position 9 S R1 RD Jack for wall mounting 8 pole ...

Page 5: ...se Control 1 6 3 2 4 5 7 12 9 8 10 11 13 18 15 14 1617 19 24 21 20 22 23 L1 L2 456 7 8 9 A B C D E F 0 1 2 3 Temp sensor for preheated air 0 10 V Electric air heater G0 S Communication cable to the control unit of the air handling unit where it should be connec ted to one of the connections for Internal EIA 485 Function selector switch in Position 9 S R1 RD T1 GR Jack for wall moun ting 019611 Ove...

Page 6: ...EATER 0 10 V W COIL WITH FP W COIL WITHOUT FP PREHEAT FUNCTION OFF ON SETTINGS PREHEAT TEMPERATURE 5 0 C 5 Adjustment For basic facts on how to use the hand held micro termi nal see the Operation and Maintenance Instructions for the GOLD unit The PREHEAT function must be manually activated under INSTALLATION FUNCTIONS IQNOMIC PLUS in the hand held terminal Select PREHEAT Under FUNCTION OFF ON sele...

Page 7: ...m the GOLD unit s control unit A flashing light emitting diode L1 indicates correct com munication with the GOLD unit s control unit Temperature sensor Current temperatures can be read under INSTALLATION READINGS IQNOMIC PLUS PREHEAT If the tempera ture readings are reasonable wiring has been carried out correctly 1 6 3 2 4 5 7 12 9 8 10 11 13 18 15 14 1617 19 24 21 20 22 23 L1 L2 456 7 8 9 A B C ...

Page 8: ...GB PREHEAT 130225 Specifications are subject to change without notice 8 www swegon com ...

Reviews: