background image

GB.ELQZ613.050901

Specifications are subject to alteration without notice.

www.swegon.se    

8

0-10V

1

+24V DC

2

+15V DC

3

+10V DC

4

GND

5

GND

6

0-10V

7

GND

P2

P1

General

The ELQZ-4-613-0 changeover switch is intended for use 

together with type BCRW or BCRWD BASIC Wing  

direct-driven fans with a fan motor with integrated  

frequency converter.
The unit has two potentiometers for manually setting the 

fan speed. It can be used for two-speed control of one 

fan, or for single-speed control of two fans. 
The  changeover  switch  is  equipped  with  fasteners  for 

mounting  it  on  a  35  mm  DIN  rail  and  is  designed 

for  installation  inside  a  cubicle  or  a  similar  enclosure.

 

                   

                  

Technical data

Installation of the ELQZ-4-613-0 Fan speed changeover switch

Power supply   

24 V DC,15 V DC or 10V DC

Power consumption 

2 x 12 mA

Signal output   

0 - 10 V DC

 

 

(Corresponds to 0 - 100% on the pot.)

Permissible ambient

temperature 

 

-10 – +40 °C

Mounting bracket 

35 mm DIN rail

Enclosure class IP 20
Dimensions (WxHxD)  68 x 82 x 34 mm
Weight   

 

0,085 kg

Electrical wiring

The electrical wiring must be carried out by a qualified 

electrician  in  accordance  with  local  regulations.  The 

control cable between the fan motor and the cubicle, in 

which the unit is mounted, must be shielded.
See the wiring example as well.

Summary of Contents for ELQZ-4-613-0

Page 1: ... with fasteners for mounting it on a 35 mm DIN rail and is designed for installation inside a cubicle or a similar enclosure Technical data Installation of the ELQZ 4 613 0 Fan speed changeover switch Power supply 24 V DC 15 V DC or 10V DC Power consumption 2 x 12 mA Signal output 0 10 V DC Corresponds to 0 100 on the pot Permissible ambient temperature 10 40 C Mounting bracket 35 mm DIN rail Encl...

Page 2: ...le speed control of two fans Two speed control of one fan Shielded terminal box Shielded terminal box GND Common Alarm output 0 10V input 10V DC out BCRWD 004 Start GND Common Alarm output 0 10V input 24V DC out Start Conductors in motor cable Conductors in motor cable Conductors in motor cable Shielded terminal box GND Common Alarm output 0 10V input 10V DC out BCRWD 004 Start Contact for changeo...

Page 3: ...tor cable Conductors in motor cable In operation output In operation output Alarm output Alarm output Start GND earth 0 10V input 0 10V input 10V DC out max 10mA GND earth Alarm reset In operation output In operation output Alarm output Alarm output Start GND earth 0 10V input 0 10V input 10V DC out max 10mA GND earth Alarm reset In operation output In operation output Alarm output Alarm output St...

Page 4: ...erminal box Shielded terminal box Shielded terminal box Conductors in motor cable Conductors in motor cable Conductors in motor cable GND Common Alarm output 15V DC out Start 0 10V input 0 10V input 10V DC out max 10mA Reset GND Common Alarm output 15V DC out Start 0 10V input 0 10V input 10V DC out max 10mA Reset GND Common Alarm output 15V DC out Start 0 10V input 0 10V input 10V DC out max 10mA...

Reviews: