3.3.1 Height adjustment to height of GOLD/
water trap
CoolDX, size 08
In combination with GOLD RX 08
The design of the GOLD unit makes it necessary to mount
it on a stand or some other form of support, so that its
inspection doors can be opened. The stand is available as
an accessory.
A corresponding stand is also available as accessory for the
CoolDX.
The heights of the stands are matched to one another and
also provide space for a water trap, if required, for connec-
tion at the lower section (right-hand version).
In combination with the GOLD PX 08
The air handling unit is supplied on a 180 mm high base
frame.
A corresponding base frame is also available as an ac-
cessory for the CoolDX. The heights of the base frames
are matched to one another and also provide space for a
water trap, if required, for connection at the lower section
(right-hand version).
CoolDX, sizes 12-40
The GOLD air handling unit and the cooling unit CoolDX
are supplied with 100 mm high base beams.
Applicable to cooling coil in lower level:
If a water trap (accessory) is fitted, the GOLD unit and
the cooling unit must be raised at least 50 mm to provide
space for the water trap. Adjustable support feet (acces-
sories) can be appropriately fitted to the base beams for
this purpose.
CoolDX, sizes 60
The GOLD air handling unit and the cooling unit CoolDX
are supplied with 100 mm high support feet. The support
feet can be removed or left on the unit.
Applicable when cooling coil in lower level:
If a water trap (accessory) is fitted, the GOLD unit and the
cooling unit must be raised at least 50 mm above the base
beams to provide space for the water trap. This can appro-
priately be done by leaving the factory-fitted support feet
on the base beams. Or you can replace them with adjusta-
ble feet (accessory).
3.3.2 Connection to GOLD Units, CoolDX Size 08-12
Insert rubber ring seals (2 rings, not included in the supply)
into the circular outdoor air and exhaust air connections of
the GOLD unit respectively. See the installation instructions
for the GOLD, as well.
If the CoolDX is to be docked directly against the GOLD
unit:
Use a forklift truck or a hand truck to position the CoolDX
against the GOLD unit as described in Section 3.3 Dock-
ing Configurations. Make sure that the rubber seals on
the GOLD unit engage into the duct connections on the
CoolDX unit. See sketch!
Important!
Be careful to prevent damage to the unit and
the rubber ring!
Distance, GOLD/CoolDX
If the CoolDX is to be located at another place:
Position the CoolDX at an appropriate place in the fan
room. Insert rubber ring seals (2 rings, not included in the
supply) into the relevant circular duct connections on the
CoolDX. See Section 3.3 Docking Configurations.
Connect the ducts between the GOLD unit and the
CoolDX unit.
It may be necessary to extend the communication cable
and necessary tubing (not included in the supply) de-
pending on the distance between the GOLD unit and the
CoolDX unit.
CoolDX
GOLD
50
CoolDX
GOLD
Rubber ring seal