Swegon CoolDX 08-1 Installation And Maintenance Instructions Manual Download Page 4

GB.COOLDX.INST.090301

We reserve the right to alter specifications.

4     www.swegon.com

1.2 Basic function diagram

Operation

There are two refrigerant circuits in the cooling unit. The 
circuits are separate from one another.

Each circuit is equipped with a finned condenser, a finned 
evaporator and a compressor.

The two compressors have different capacity, which ena-
bles control in 3 steps.

The gaseous refrigerant is compressed by compressors M1 
and M2 and from there moves on to condenser COND, 
where it is chilled by the extract air and is condensed to 
liquid form. 

The pressure and the temperature decrease as the refri-
gerant in fluid form flows through expansion valves VET1 
and VET2.

COND Condenser
VSH1 Overpressure protection
VSH2 Overpressure protection
BP1-3 Pressure limiting switch for high pressure 26 bar
BP1

Pressure limiting switch for low pressure 2,5 bar

BP2-3 Pressure limiting switch for high pressur

26 bar

BP2

Pressure limiting switch for low pressure 2,5 bar

BP1-2 Alarm pressure switch for high pressure

28 bar

BP2-2 Alarm pressure switch for high pressure

28 bar

M1

Compressor

M2

Compressor

VSL1

Underpressure protection

VSL2

Underpressure protection

EVAP

Evaporator

VET1

Expansion valve with thermostat

VET2

Expansion valve with thermostat

IPL1

Sight glass, refrigerant circuit 1

IPL2

Sight glass, refrigerant circuit 2

FD1

Filter drier

FD2

Filter drier

From the expansion valves the refrigerant moves on to 
evaporator EVAP, where the refrigerant evaporates and 
chills the outdoor air. 

From evaporator EVAP, the evaporated refrigerant is con-
veyed further to the suction side of the compressors where 
it is again compressed. 

Control

The cooling capacity is regulated in three binary steps by 
having one or two compressors in operation.

The cooling compressors are controlled from the GOLD 
unit via relays on the IQnomic Plus module mounted in the 
CoolDX.

Step 1:

 When cooling is needed, Compressor M1 is start-

ed.

Step 2:

 If more cooling is needed, Compressor M2 starts 

and at the same time Compressor M1 stops. An adjust-
able time delay (a step duration of 300 seconds) ensures 
that Compressor M2 will not start until Compressor M1 is 
operating at full capacity.

Step 3:

 If even more cooling is needed, Compressor M1 is 

restarted and is run at the same time as Compressor M2. 
This third cooling step is also delayed by a preset time de-
lay setting. In addition, the restarting time (480 seconds) 
for Compressor M1 shall have expired.
If less cooling is needed and the compressors are subse-
quently switched out step-by-step, there will be no delay 
between compressors.  The restarting time (480 seconds) 
for Compressor M1 shall have expired to enable it to start 
again in Step 1 after it has been operated in Step 3.
If any compressor is stopped, the restarting time must 
expire before a restart can take place. The restart time is 
calculated from one start to the next start.
Low pressure switches BP1/BP2 and high pressure switches 
BP1-3/BP2-3 (in-service pressure switches for the respec-
tive circuit) ensure that the system pressure is within pre-
determined limits.
If the pressure in the cooling circuit becomes too low, or 
if the pressure in the condenser circuit becomes too high, 
the compressor is stopped and the text PRESSURE LIMIT-
ING is displayed alternately in the hand-held micro termi-
nal of the GOLD air handling unit.
When the restart time has expired, the compressors will try 
to restart.
If the pressure increases more, high pressure switches 
BP1-2 and BP2-2 will trip and stop the GOLD unit and the 
CoolDX cooling unit.
Alarms 85 and 86 will be displayed in the hand-held micro 
terminal of the GOLD unit.
Pressure switches BP1-2 and BP2-2 can be manually reset 
by pressing a button under each protective sock on the 
upper side of the pressure switch. This can be done with-
out removing the protective sock.

COND

VSH2

M1

M2

VSL2

VSL1

EVAP

VET1

VET2

IPL1

IPL2

FD1

FD2

BP2

HP

BP2-3

LP

HP

BP1

HP

BP1-3

LP

HP

BP2-2

BP1-2

Summary of Contents for CoolDX 08-1

Page 1: ...GB COOLDX INST 090301 CoolDX COOLING UNIT Installation and Maintenance Instructions Sizes 08 60 ...

Page 2: ...te drainage from cooling coil 9 3 3 7 Supply air filter 9 3 3 8 Condensation barrier mat 10 4 Electrical connections 11 4 1 Connection to power supply 11 4 2 To connect the communication cable 11 5 Commissioning 12 5 1 Preparations 12 5 1 1 Before initial start up 12 5 1 2 Starting up 12 5 1 3 In service pressure switches 12 5 1 4 Phase sequence monitor 12 5 1 5 Remedial action if wrong phase sequ...

Page 3: ...ENERAL SURVEY 1 1 General Cooling unit CoolDX Cooling unit CoolDX is a complete cooling unit for com fort cooling in air handling systems All the components are fully wired have fully connected refrigeration circuits and are collected inside a common casing The casing is fabricated of aluminium profiled sections held together by plastic corner pieces The panels are of sandwich design and consist o...

Page 4: ...the CoolDX Step 1 When cooling is needed Compressor M1 is start ed Step 2 If more cooling is needed Compressor M2 starts and at the same time Compressor M1 stops An adjust able time delay a step duration of 300 seconds ensures that Compressor M2 will not start until Compressor M1 is operating at full capacity Step 3 If even more cooling is needed Compressor M1 is restarted and is run at the same t...

Page 5: ...ersonnel since they contain gas under high pressure Risk areas where exposure to refrigerant could occur Practically the whole area inside the cooling unit is a risk area For particulars on how to deal with leakage see Section 7 2 Type R 407C refrigerant is used Warning The inspection door of the GOLD unit may not be ope ned while the unit is in operation Positive pressure in side the unit will ca...

Page 6: ...of the cooling unit and two under the underside of the pallet or under the cooling unit and lift in the pallet or in the base frame of the cooling unit if the unit is not delivered on a pallet See sketch 3 2 Arrangement Position the CoolDX cooling unit at suitable place in the fan room Allow an open space around the safety isolating switch mains power switch for servicing in accordance with appli ...

Page 7: ...nection to size 08 60 GOLD air handling units For a list of the cooling unit sizes and capacities that match a given size of GOLD unit see Section 10 General Technical Data CoolDX 08 CoolDX 12 60 Right hand version Left hand version Cooling coil in lower level GOLD fan arrangement 1 Cooling coil in upper level GOLD fan arrangement 2 Cooling coil in upper level GOLD fan arrangement 1 Cooling coil i...

Page 8: ...100 mm high support feet The support feet can be removed or left on the unit Applicable when cooling coil in lower level If a water trap accessory is fitted the GOLD unit and the cooling unit must be raised at least 50 mm above the base beams to provide space for the water trap This can appro priately be done by leaving the factory fitted support feet on the base beams Or you can replace them with...

Page 9: ...outdoor air and exhaust air connections respectively See the installation instructions for the GOLD as well If the CoolDX is to be docked directly against the GOLD unit Use a forklift truck or a hand truck to position the CoolDX against the GOLD unit as described in Section 3 3 Docking Configurations Make sure that the connections on the GOLD unit and the CoolDX unit are in alignment and are close...

Page 10: ...GOLD air han dling unit and the CoolDX as illustrated below to prevent condensate from reaching metallic surfaces The condensation barrier mats are self adhesive Open the inspection doors on the GOLD air handling unit and install the mats from this side Open the inspection doors Fit the condensation barrier mat onto the interior surfaces of the connections between the GOLD unit and the CoolDX A A ...

Page 11: ...ect the cable to an optional bus connection on the control unit Adjust the length of cable inside the electrical cubicle and adjust its position through the cable gland Refit the cable gland back to its correct position An extra outdoor air temperature sensor is required if any of the following functions are activated in the GOLD air handling unit outdoor compensation cooling step blocking cooling...

Page 12: ...re and one for high pressure If the operating pressure in any of the circuits exceeds or drops below a limit value the relevant compressor is switched off The text CoolDX PRESSURE LIMITING is displayed in the hand held terminal until the pressure comes within the limit values again The compressor is permitted to restart when the restart delay has expired 5 1 4 Phase sequence monitor The size 60 Co...

Page 13: ...other way becomes superheated in the atmosphere poisonous gases can form Important Charging with refrigerant must be carried out according to the recommendations of the refrigerant producer Avoid direct skin contact with the refrigerant Use close fitting protective eyeglasses protective gloves and protective work clothing that cover the whole body Provide adequate ventilation local extraction In t...

Page 14: ... across the condensor Excessively high exhaust air temperature The high pressure switch is defective Check the airflow Check the exhaust air temperature Check replace Significant freezing on the evaporator The expansion valve is defective or incorrectly set No airflow or too low airflow across the evaporator Check Replace or adjust setting Check the airflow 8 2 Leakage Tracing As a preventive meas...

Page 15: ...width mm H height mm Duct connection mm 08 1250 990 1086 Ø 400 46 46 50 50 K CoolDX size L length mm B width mm H height mm K mm Duct connection mm 60 1250 2253 2353 2075 1600 x 800 46 46 50 50 K Supplied on 100 mm high support feet Can be removed or left on when the unit is in place Has provision for adjustable support feet CoolDX size L length mm B width mm H height mm K mm Duct connection mm 12...

Page 16: ...2 2 2 0 46 3 phase 400V 16A 257 12 1 1 14 4 95 1 3 2 7 0 68 3 phase 400V 16A 305 12 2 2 20 6 94 1 4 2 9 0 9 3 phase 400V 20A 332 20 1 1 14 4 95 1 3 2 7 0 68 3 phase 400V 16A 323 20 2 2 20 6 94 1 4 2 9 0 9 3 phase 400V 20A 351 20 3 3 26 9 88 2 3 3 3 0 9 3 phase 400V 25A 373 30 1 1 27 9 00 2 0 4 2 1 25 3 phase 400V 25A 440 30 2 2 32 10 66 2 2 4 7 1 5 3 phase 400V 32A 486 30 3 3 45 16 47 3 4 5 6 1 5 ...

Page 17: ...trol circuit fuse 6 IQnomic Plus control unit 7 Phase sequence monitor applies to size 60 capacity variant 2 only 8 Transformer 400 230 V for control voltage 9 Fuse 230 V operating voltage 1 2 3 45 6 7 8 9 0 P1 L1 L2 6 3 2 4 5 7 12 9 8 10 11 13 18 15 14 1617 19 24 21 20 22 23 5 2 1 3 4 6 Sizes 08 20 all capacity variants Size 30 capacity variant 1 1 2 3 45 6 7 8 9 0 P1 L1 L2 6 3 2 4 5 7 12 9 8 10 ...

Page 18: ...NTERNAL WIRING DIAGRAM 12 1 CoolDX 08 40 all capacity variants and size 60 capacity variant 1 Q Electrical circuit load separator connection point for supply voltage Mx Compressor PSC Controls for phase sequence BPx Low and high pressure switch BPx x High pressure switch Hx Crankcase heater ...

Page 19: ... 12 2 CoolDX 60 Capacity variant 2 Q Electrical circuit load separator connection point for supply voltage Mx Compressor PSC Controls for phase sequence BPx Low and high pressure switch BPx x High pressure switch Hx Crankcase heater TP Thermal overload protection for scroll compressor ...

Page 20: ... 12 3 CoolDX 60 Capacity variant 3 Q Electrical circuit load separator connection point for supply voltage Mx Compressor PSC Controls for phase sequence BPx Low and high pressure switch BPx x High pressure switch Hx Crankcase heater TP Thermal overload protection for scroll compressor ...

Page 21: ...pproved Done Remarks Installation according to instructions Condensate drain correctly connected water trap filled with water Supply air filter in GOLD unit dismantled Air hoses for filter in CoolDX fitted according to instructions Electrical connections installed according to instructions Control cable from CoolDX to GOLD connected according to instructions Direction of rotation of compressor 2 c...

Page 22: ...ressor 1 08 1 5 0 A Protective motor switch Compressor 2 7 5 A 08 2 6 0 A 10 0 A 12 1 5 0 A 10 0 A 12 2 7 5 A 12 0 A 20 1 5 0 A 10 0 A 20 2 7 5 A 12 0 A 20 3 10 0 A 15 5 A 30 1 9 5 A 15 5 A 30 2 9 5 A 22 0 A 30 3 15 5 A 27 0 A 40 1 12 0 A 22 0 A 40 2 12 0 A 27 0 A 40 3 22 0 A 36 0 A 60 1 15 5 A 36 0 A 60 2 22 A 35 0 A 60 3 36 0 A 50 0 A Function selector switch IQnomic Plus Position 6 ...

Reviews: