Actionair DWFX-F Installation Guide

6

Swegon reserves the right to alter specifications.       20210408 - LNNN00354 (3.0)                                                                   

Vertical Damper Installation (Top 

Flange Remo ved) In A Masonry Wall 

Under Concrete Slab 

Actionair SmokeShield - [AA/F12493]
Actionair FireShield - [AA/F12827]

Installation Method

1. Measure the overall Fire damper casing size width x 

height,  but for Smoke Shield  include the PTC Shroud 

(28mm) in the width but do not include any of the 

peripheral flange.

2. Calculate hole size...
3. 

For Fire Shield calculate the finished hole size by adding 

10-80mm to the case width and 5-40mm for the 

height as the head of the damper will be against the 

slab.

4. 

For Smoke Shield calculate the finished hole size adding 

10-57mm to the width and 5-30mm to the height as 

the head of the damper will be against the slab.

5. 

Drill clearance holes in the three damper flange's side 

and bottom at 150mm centres.

6. Apply a bead of low pressure intumescent mastic 

along top edge of damper as a gap filler and install 

the damper and fasten through flange using fire rated 

fasteners, min ø4mm.

7. Dampers are supplied with cleats and only need to be 

used to help/assist with the installation before faste-

ning the flange to the wall.

8. 

Back fill with mineral/stone wool and to retain this use 

Section A-A

Section B-B

 - DRIVE SIDE DETAIL

Section C-C

Section D-D

A

A

B

B

C

C

D

D

1

1

2

2

3

3

4

4

5

5

6

6

A

A

B

B

C

C

D

D

Comments:

Rev:

Drawn By:

M. Bushell

Approved By:

Kimberley.M

1  of 2 

Reference No:

Gore.S

Date:
Date:

By:

Date:

13/04/2022

01/05/2018

13/04/2022

Date:

D

Checked By:

Sheet

Rev

AAF12394

Description:

If your proposed installation details differ from 

that shown here, please discuss this with the 

authority having jurisdiction, referencing this 

documentation.  

 

Deviation from this drawing requires approval 

of the relevant authority. 

 

Connecting ductwork omitted for clarity. 

Ductwork must be independently supported.  

There must be an appropriate break-away 

joint between the damper and the connecting 

ductwork on both sides of the installation. 

 

A minimum of 200mm between fire dampers 

installed in separate ducts and 75mm between

fire damper and construction elements/edges 

needs to be observed unless otherwise 

specified in the drawing.

Installation Detail

A

A

B

B

C

C

D

D

VERTICAL BLADES;

The damper can be installed with the 

blades in the vertical orientation with the 

actuator mounted at the bottom.  For 

cleat locations of motors mounted on the 

bottom refer to drawing AA-SS-2011.

Supporting 

Construction











Actuator

Interface

Interface

shroud

Damper

Dampers supplied with cleats

welded to side flanges to assist

with installation only

Min. 30kg/m³ stone mineral wool

 insulation filing gaps on three sides.

5-

30

m

m

. in

fill

 o

n

 n

on

 d

riv

sid

e

 a

nd

 b

ot

to

m

.

Block/masonry wall

Damper Size Range (mm)

VERTICAL APPLICATION

SMOKE SHIELD DWFX-F, IN

MASONRY WALL AGAINST

SUPPORTING CONSTRUCTION

200 x 200 to 1000 x 1000

 

EC1843

MJB 08-05-18

12.5mm. thick 150mm. gypsum fire

boards type F (EN520) on sides and

bottom, fixed with suitable fire resisting 

steel fixing (min Ø 4 x 40mm) to suit 

supporting construction.

Up to 55mm.

infil on actuator

side only.

A

ECN1922

MJB 12-04-19

DWFX-F angle flange (welded to damper 

casing) on sides and bottom fixed with 

suitable fire resisting steel fixing min 

dia. 4mm at least 40mm long to suit

supporting construction (@150mm. ctrs).

















Cleat

B

ECN1940

MJB 01-07-19

 

 

 

 

© Swegon Air Management Limited

South Street, Whitstable, Kent CT5 3DU

Tel:  +44 (0)1227 276100

Email: [email protected]

 www.swegon.com/uk

C

ECN5134

MJB 05-02-21

Min 100mm thick

Please refer to the DoP

for latest classifications

for CE/UKCA

compliance and the

Installation, Operation

and Maintenance Guide

 SCAN ME

D

ECN2227

JPM 13/04/22

a 150mm pattress down to the damper spigot/duct 

line.  Fasten with fire rated fasteners, min ø4mm at 

300mm centres on the sides and bottom. Measure the 

gap for the top pattress and fix this pattress to the wall 

either side of the damper, (do not fix at 300ctr to the 

damper case).

9. Connecting ductwork omitted for clarity. Ductwork 

must be independently supported. There must be an 

appropriate break-away joint between the damper and 

connecting ductwork on both sides of assembly. Alu-

minium rivets or plastic cleats, clips, clamps and bolts 

etc. should be used for this, unless fire resisting duct-

work is being used where fire resisting fixings should 

be used. A minimum of 200 mm between fire dampers 

installed in separate ducts and 75 mm between fire 

damper and a construction element (wall/floor).

Summary of Contents for actionair DWFX-3F

Page 1: ... Care must be taken when installing and inspecting dampers as they are likely to close without warning due to loss of electrical power or a temperature rise in the ductwork This is their prime function Do not insert any items fingers or limbs between the blades Larger dampers must be handled in accordance with current regula tions and good practice due to weight Drawings Please visit our website t...

Page 2: ...ndard install is requi red talk to us as early as possible in the project to get important stakeholders engaged and ensure an instal lation solution can be found The instructions are based on the tested method using Actionair SmokeShield PTC and FireShield products Our SmokeShield dampers are designed to be used with fire separating elements to maintain fire compart ments The SmokeShield is an act...

Page 3: ...Rev Drawn By J Mount Approved By 1 Reference No Checked By AAF10704 Description If your proposed installation that shown here please disc authority having jurisdiction documentation Deviation from this drawing of the relevant authority Connecting ductwork omitte Ductwork must be independ There must be an appropria joint between the damper an ductwork on both sides of th A minimum of 200mm betwe in...

Page 4: ...o pull into the stud and track around the hole Fix the top pattress into the track at the sides 11 Connecting ductwork omitted for clarity Ductwork must be independently supported There must be an appropriate break away joint between the damper and connecting ductwork on both sides of assembly Alu minium rivets or plastic cleats clips clamps and bolts etc should be used for this unless fire resist...

Page 5: ...te ducts and 75 mm between fire damper and a construction element wall floor Comments Rev Drawn By M Bushell Approved By Kimberley M 1 o Reference No Gore S D D D Checked By She AAF12493 Description If your proposed installation de that shown here please discus authority having jurisdiction ref documentation Deviation from this drawing req of the relevant authority Connecting ductwork omitted fo D...

Page 6: ...truction ele needs to be observed unless ot specified in the drawing Installation D A A B B C C D D VERTICAL BLADES The damper can be installed with the blades in the vertical orientation with the actuator mounted at the bottom For cleat locations of motors mounted on the bottom refer to drawing AA SS 2011 Supporting Construction Actuator Interface Interface shroud Damper Dampers supplied with cle...

Page 7: ... are only available for 72 C For Dampers where alternative thermal link temperatures are required a chain link can be offered in place of a cassette Electrical release is only available with a cassette i e 72 C Please refer to Actionair Sales Office Please note For dampers with dimensions of 150mm and below ensure that there is adequate access to enable re setting Self Latching Removable Release M...

Page 8: ...ion Both screws should be tightened fully to ensure that both sections of the ETR are closed together It is a safety feature if both sections are not closed the unit will not operate For ductless installations the ETR should be fitted onto the damper spigot not casing above the damper interface shroud and in accordance with the fitting instructions If the ETR is not fitted in the exact manner desc...

Page 9: ...nths A comprehensive example of the maintenance pro cedure is given in Annex D of the standard Some automatic systems may allow more frequent testing 48hr or less and this may be required by a national standard Approved Document B Volume 2 Clause 10 12 states adequate means of access must be provided to allow inspection testing and maintenance of both fire damper and its actuating mechanism BS 999...

Page 10: ...MPER MADE BETWEEN 4 6 M FULLY OPEN AC DC 230V 50 60 Hz 14 VA 12 4 W 30 C 50 C CONTINUOUS TF 72 C AC 250V 6 3 A N CONTINUITY WITH COMMON ELECTRICAL THERMAL RELEASE ETR MUST BE FITTED TO DUCTING FOR DAMPER OPERATION SPRING BIASED TEST SWITCH WHEN DAMPER CLOSED CONTINUITY WITH COMMON WHEN DAMPER OPEN CONTINUITY WITH COMMON WHEN DAMPER CLOSED CONTINUITY WITH COMMON WHEN DAMPER OPEN Supply Off Damper s...

Page 11: ...GHT DUCT DIA 245mm FOR DUCT DIAMETERS BET EEN 970mm 1000mm OVERALL WIDTH OF FLAN E WIDTH IS 1198mm OVERALL HEIGHT OF INSTALLATION FRAME IS 1195mm OVERALL FLANGE WIDTH DUCT DIA 248mm OVERALL FLANGE HEIGHT DUCT DIA 245mm FOR DUCT WIDTHS BETWEEN 970mm 1000mm OVERALL WIDTH OF INSTALLATION FRAME IS 1198mm Flat Oval Dampers Series 701 C Circular Dampers Series 601 FOR DAMPERS 100 150MM 2 FOR IRCULAR DAM...

Page 12: ...ts OVERALL FLANGE WIDTH DUCT WIDTH 198mm OVERALL FLANGE HEIGHT DUCT HEIGHT 195mm For Ducts with widths and heights of 200 1000mm FOR DUCT WIDTHS 200MM 1000MM WITH HEIGHTS OF 100 199MM OVERALL FLANGE WIDTH IS 398mm UCT WIDTHS A OVERALL FLANGE HEIGHT IS 395mm FOR D ND HEIGHTS OF 100 150MM FOR DUCT WIDTHS AND HEIGHTS OF 151 199MM OVERALL FLANGE WIDTH IS 448mm OVERALL FLANGE HEIGHT IS 445mm FOR OVERAL...

Page 13: ...tion Guide Actionair FireShield Base Dampers Dampers with DWFX F Series 101 FireShield Dampers with blades partly in airstream Damper spigots stream Series 201 spigots 5mm under duct size 100 249 high use Series 101 Damper as Series 301 spigots 3mm under duct size Series 401 spigots 3mm under duct size ...

Page 14: ...y wired Check wiring in accordance with procedures The ETR cables have been damaged or tampered with Replace with new mode Control Mode operates but limited or no movement of damper blades is observed The mode is not correctly synchronised with the interface Remove motor from interface Check motor in fully released state Set position of interface and refit motor with label upmost include motor loc...

Page 15: ...ess permitted under the respective DoP 6 Is access through the ductwork to the damper unob structed Unobstructed space should be provided for safe access to the damper This must include access through ceiling voids and ad jacent services Damper installer to advise the system designer if problems are foreseen 7 Has the space around the damper and within the opening been left clear and not been used...

Reviews:

Related manuals for actionair DWFX-3F