Actionair DWFX-F Installation Guide
Vertical Damper Installation in
a Masonry Wall
Actionair SmokeShield PTC - [AA/F12493]
Actionair FireShield - [AA/F10707]
Installation Method
1.
Drill clearance holes in the damper flange at 150mm
centres.
2.
Install the damper and fix through flange using fire
rated fasteners, min ø4mm.
3.
Back fill and complete penetration seal as per the
installation drawing
4. Connecting ductwork omitted for clarity. Ductwork
must be independently supported. There must be an
appropriate break-away joint between the damper and
connecting ductwork on both sides of assembly. Alu-
minium rivets or plastic cleats, clips, clamps and bolts
etc. should be used for this, unless fire resisting duct-
work is being used where fire resisting fixings should
be used. A minimum of 200 mm between fire dam
-
pers installed in separate ducts and 75 mm between
fire damper and a construction element (wall/floor).
Comments:
Rev:
Drawn By:
M. Bushell
Approved By:
Kimberley.M
1 of 2
Reference No:
Gore.S
Date:
Date:
By:
Date:
13/04/2022
21/08/2018
13/04/2022
Date:
B
Checked By:
Sheet
Rev
AAF12493
Description:
If your proposed installation details differ from
that shown here, please discuss this with the
authority having jurisdiction, referencing this
documentation.
Deviation from this drawing requires approval
of the relevant authority.
Connecting ductwork omitted for clarity.
Ductwork must be independently supported.
There must be an appropriate break-away
joint between the damper and the connecting
ductwork on both sides of the installation.
A minimum of 200mm between fire dampers
installed in separate ducts and 75mm between
fire damper and construction elements/edges
needs to be observed unless otherwise
specified in the drawing.
Installation Detail
³
.
EC1879
MJB 23-08-18
Damper Size Range (mm)
VERTICAL APPLICATION
SMOKE DWFX-F WITH
PATTRESS IN MASONRY WALL
200 X 200 to 1000 x 1000
VERTICAL BLADES;
Damper can be installed with the blades in the
vertical orientation with the actuator mounted at
either the top or bottom. For cleat
© Swegon Air Management Limited
South Street, Whitstable, Kent CT5 3DU
Tel: +44 (0)1227 276100
Email: [email protected]
www.swegon.com/uk
A
ECN5134
MJB 05-02-21
Please refer to the DoP
for latest classifications
for CE/UKCA
compliance and the
Installation, Operation
and Maintenance Guide
SCAN ME