8. Optional Communication Cards
8.1.
R2E (second RS-232) card
8.1.1. CN1 is for RS-232 DB9.
8.1.2. For interface settings and pin assignments please refer to section 3.4.1.
8.1.3. Installation Position: Optional Slot
8.2.
USE (USB) card
8.2.1. CN1 is for USB.
8.2.2. For the communicaiton protocol definition please refer to section 8.4.3.
8.2.3. Installation Position: Optional Slot
29
8.3.
DCE (Dry Contact) card
8.3.1. Pin assignments of 10-Pin terminal:
1
Æ
UPS in Bypass mode (Bypass)
2
Æ
Utility Normal (normally closed contact)
3
Æ
Utility Normal (normally open contact)
4
Æ
Inverter On
5
Æ
Battery Low
6
Æ
Battery Bad or Abnormal
7
Æ
UPS Alarm
8
Æ
Common
9
Æ
Shutdown UPS positive (+) signal
10
Æ
Shutdown UPS negative (-) signal
8.3.2. The shutdown function will be activated after +6-25 VDC is applied
between pin 9 and pin 10 for 5 seconds.
8.3.3. The capacity of each relay contact is 40 VDC/25 mA.
8.3.4. Installation Position: Optional Slot
8.3.5. Flexible signal output for N.C. (Normally Closed) or N.O. (Normally Open)
contact by shorting pins1-2 or pins 2-3 from JP1-5
8.3.6. The shutdown function will be enabled 1 minute after blackout occurs if
pins 1-2 of both CN1 and CN6 are shorted. Otherwise the shutdown
function can be enabled only by pins 9-10 of CN3 if pins 2-3 of both
CN1 and CN6 are shorted.