WARNING: The combination of different error conditions may cause
damage to the controller. Always remove an error before you continue
connecting the controller!
Error Description
Error
Display
Reason
Remedy
Battery is low
(LED on)
Load will reconnect
as soon as battery is
recharged.
Loads are not
supplied
Overcurrent/
Short circuit
of loads
(LED flashing)
Switch off all loads.
Remove short circuit.
Controller will
switch on load
automatically after
max 1 minute.
Battery is
empty again
after a short
time
Battery has low
capacity
(LED on)
Change battery
Battery is not
being charged
during the day
Solar array
faulty or wrong
polarity
(LED off)
Remove faulty
connection/reverse
polarity
General Safety and Usage Recommendations
Intended Use
The charge controller is intended exclusively for use in photovoltaic systems with 12 V nominal voltage, and
in conjunction with vented or sealed (VRLA) lead acid batteries only.
Safety Recommendations
z
Batteries store a large amount of energy. Never short circuit a battery under any circumstances. We
recommend connecting a fuse (slow acting type) directly to the battery.
z
Batteries can produce flammable gases. Avoid making sparks, using fire or any naked flame under any
circumstances. Make sure that the battery room is ventilated.
z
Avoid touching or short circuiting wires or terminals. Be aware that the voltages on specific
terminals or wires can be up to double the battery voltage. Use isolated tools, stand on dry ground
and keep your hands dry.
z
Keep children away from batteries and the charge controller.
z
Please observe the safety recommendations of the battery manufacturer. If in doubt, consult your
dealer or installer.
Liability Exclusion
The manufacturer shall not be liable for damages, especially on the battery, caused by use other than as
intended or as mentioned in this manual or if the recommendations of the battery manufacturer are neglected.
The manufacturer shall not be liable if there has been service or repair carried out by any unauthorized
person,
Mounting and Connecting Mounting and Connecting
Nominal voltage
12 V
Boost voltage
14.5 V
Float voltage
13.7 V (25°C)
Load disconnect voltage
11.5 V voltage controlled (25°C)
Load reconnect voltage
12.5 V
Temperature compensation
-4 mV/cell*K
Max. solar panel current
CA06-2: 6 A
at 50°C ambient temperature
Max. load current
CA06-2: 6 A
at 50°C ambient temperature
Dimensions
81 x 100 x 37 mm (w x h x d)
Weight
180 grms
Max. wire size
16 mm
2
(AWG #6)