SurgeX XR315 User Manual Download Page 16

 

16 

 
The remote control inputs should be connected to the first unit, and the same control options are 
available as for a single-unit system. If confirmation feedback is required for a central controller, 
use the aux relay contacts on the last unit. 
 
If the low and high voltage shutdown points are narrowed from their defaults of 90V and 150V 
this should be done on the first unit only. The other units should be left set to 90V and 150V.The 
two restore options should only be enabled (if required) on the first unit. 
 
If an over-ride is required connect it to the first unit. 
 

6.5

 

Cascaded System 

 
A cascaded system consists of two or more XR315s connected together such that they turn on 
and off one after another. Connecting a cascaded system together is a little more complicated 
than the other types of system because there must be feedback from each unit to the previous unit 
as well as control from each unit to the next unit. The 12V dc output (terminal 4) is used as the 
feedback source and the over-ride input (terminal 3) is used as the feedback input. Figure 6 
shows how to connect and program each unit in a three-unit system. Note that terminals 5 and 6 
are connected together for all units except the last one. If only two units are to be cascaded 
together then ignore the middle unit in the diagram. If more than three units are to be cascaded 
together then keep the first and last units set up as shown, add units in the middle and set them 
up and connected them in the same way as the middle unit in the diagram. 
 
The remote control inputs should be connected to the first unit, and the same control options are 
available as for a single-unit system. If confirmation feedback is required for a central controller, 
use the aux relay contacts on the last unit. 
 
If the low and high voltage shutdown points are narrowed from their defaults of 90V and 150V 
this should be done on the first unit only. The other units should be left set to 90V and 150V.The 
two restore options should only be enabled (if required) on the first unit. 
 
If an over-ride is required connect it to the last unit and program that unit to accept the type of 
over-ride you need.

Summary of Contents for XR315

Page 1: ...USER MANUAL SurgeX XR315 SurgeX For Surge Eliminator Residential Applications Software Version 1 0 1 1...

Page 2: ...OVER RIDE CONTROL 9 5 3 12V DC OUTPUT 10 5 4 AUXILIARY RELAY 11 5 5 FRONT PANEL PUSH BUTTON 11 5 6 OUT OF RANGE AC VOLTAGE SHUT DOWN 12 5 7 RESTORE FUNCTIONS 12 6 APPLICATIONS 12 6 1 GENERAL POINTS 12...

Page 3: ...button can be disabled if not required The LED incorporated into the button indicates the status of the unit When the LED is off the unit is fully powered down when it is on the unit is fully powered...

Page 4: ...rogrammable 12 Volt dc output can be used to control other SurgeX products Auxiliary relay or 12 Volt dc output can be programmed to provide confirmation feedback products or drive LEDs Built in AC Vo...

Page 5: ...e such as a relay or by a switch In this manual the terms momentary and latching are used when describing switches A momentary switch is considered to be a switch which provides a connection only whil...

Page 6: ...ng Note The front panel button will not operate with options a b or f 3 2 2 Over Ride Input The XR315 has the option of adding an over ride function for purposes such as providing fire safety over rid...

Page 7: ...n the XR315 is powered up and will be zero when the XR315 is powered down Program 12V dc Output for Confirm Note that the XR315 common terminal is shared between the inputs and the 12V dc output If yo...

Page 8: ...ion by rotating Adjust 4 If you have connected an LED to the 12V dc output for remote signaling step through the menu until you reach 12V dc Output Then advance Adjust to select LED This selection wil...

Page 9: ...t up turn Select counter clockwise until the display tells you to press the power button again Doing so saves the new set up information in non volatile memory and puts you back into normal operation...

Page 10: ...ution product to drive LEDs or to provide feedback to the previous XR315 in a cascaded chain Please see the applications section for full details on setting up an expanded system There are three menu...

Page 11: ...SurgeX Gang or Cascade is selected when two or more XR315s are ganged or cascaded together All these options are covered in detail in the applications section Aux Delay On Set the delay time in secon...

Page 12: ...d voltage or latching type remote control inputs Pwr Fail Restore Select Enable if you want the XR315 to power up after a power failure or out of range AC condition and the XR315 was powered up when t...

Page 13: ...ith multiple control locations they are intended primarily for a small system or for hook up to a central controller The front panel push button will not work with a latching switch contact closure or...

Page 14: ...d together This is covered in the section on cascaded systems If an over ride is required with a ganged system use the over ride input on the first XR315 If an over ride is required with a cascaded sy...

Page 15: ...ontrolled by the same inputs as a single unit system Figure 3 shows how the two units are wired together using the aux relay contacts The aux relay contacts on the XR315 terminals 6 7 are connected to...

Page 16: ...edback source and the over ride input terminal 3 is used as the feedback input Figure 6 shows how to connect and program each unit in a three unit system Note that terminals 5 and 6 are connected toge...

Page 17: ...R315 Single Unit System Controlled by Momentary Switches Location 3 Location 2 Location 1 Mixer Signal Processing Amplifier Use an LED and 1K W resistor at each location Program Up Down Inputs Momenta...

Page 18: ...4 5 6 7 XR315 Mixer Signal Processing Amplifier Single Unit System Controlled by Central Controller Program Up Down Inputs Latching Aux Output Confirm Confirmation Feedback Controller Low Voltage Cont...

Page 19: ...4 5 6 7 XR315 A On Switched 1 2 3 4 5 6 7 SX1120 RT LED and 1K 1 4W Resistor Confirmation If Required Program Up Down Inputs Momentary 12v dc Output LED Aux Output A B or C Aux Delay On Set as Needed...

Page 20: ...acles 1 2 3 4 5 6 7 XR315 A On Switched 1 2 3 4 5 6 7 SX1120 RT Confirmation If Required Program Up Down Inputs Momentary 12v dc Output A B or C 12V Delay On Set as Needed 12V Delay Off Set as Needed...

Page 21: ...1 2 3 4 5 6 7 XR315 Receptacles 1 2 3 4 5 6 7 XR315 Program Up Down Inputs One Mom 12V dc Output LED Aux Output Gang Confirmation If Required Program Up Down Inputs Latching Aux Output Gang Program Up...

Page 22: ...ired LED and 1K 1 4W Resistor Program Up Down Inputs One Mom Over Ride Input 5 30 Vdc Over Ride Func Master 12V dc Output LED Aux Output Cascade Program Up Down Inputs Latching Over Ride Input 5 30 Vd...

Page 23: ...rtain that power is being supplied to the unit consult the factory for assistance Unit will not power up from remote control connection If you have performed initial checks as above and the unit will...

Page 24: ...e you can get into the programming mode 8 Error Codes Error codes are displayed on the second line of the display Error 05 The calibration of the AC voltmeter is no longer accurate The unit is otherwi...

Page 25: ...ry B3 pulses 1 KV 500 000 3 KV 10 000 6 KV 1000 Number of Outlets 8 Remote Control Voltage 5 to 30 Volts dc Remote Control Current Draw 4 mA maximum Contact Closure Max Resistance 100 Ohms Auxiliary R...