30
9
Specifications
Operational Voltage Range:
90 to 150 Volts AC
Current rating:
20 Amps
Power Rating:
2,400 Watts
Maximum Load Inrush Energy:
1400 Joules total during power-up
Surge Let-through Voltage:
Zero let-through Voltage for a 6000 Volt surge
Meets Federal Guidelines:
Grade A, Class 1, Mode 1 (CID A-A-55818)
EMI/RFI Filter, Normal Mode:
40 dB @ 100 KHz, 50dB @ 300 KHz, 50 dB @ 3 MHz,
50 dB @ 30 MHz (50 Ohm load)
EMI/RFI Filter, Common Mode:
18dB @ 300 KHz, 30 dB @ 1 MHz, 50 dB @ 5 MHz, 50
dB @ 20 MHz (50 Ohm load)
Maximum Applied Surge Voltage:
6,000 Volts *
Maximum Applied Surge Current:
Unlimited (due to current limiting) *
Maximum Applied Surge Energy:
Unlimited (due to current limiting) *
Endurance:
(C62.41-1991 category B3 pulses), 1 KV > 500,000;
3 KV > 10,000; 6 KV > 1000
Number of Outlets:
14
Number of Banks:
3
Delay Time per Bank:
1 to 40 seconds in 1 second increments
Remote Control Voltage:
5 to 30 Volts dc
Remote Control Current Draw:
4 mA maximum
Contact Closure Max. Resistance:
100 Ohms
Auxiliary Relay Contact Rating:
30 Volts dc at 1 Amp
12 Volt Output Max. Current:
40 mA
AC Voltmeter Accuracy:
+/- 2%
Dimensions:
19” W x 10.5” D x 3.5” H
Weight:
16 lbs (7.2kg)
Temperature Range:
5C to 35C
Humidity Range:
5% to 95% R.H. Non-condensing
Agency Listings:
ETL and cETL (UL 1449, Second Edition; CSA C22.2 No.8-M1986, R2000)
* 1.2 x 50 microsecond industry standard combination wave surge as per IEEE C62.41
0208A
Summary of Contents for XQ515