13
in the previous item. For example, if you wanted a forth bank to
power on first and off last, you should select A as the Aux Output and
set this delay time to be shorter than the delay that you set for Main
Bank A On (the Aux Delay On can be set to zero in this case); or if
you wanted a forth bank to power on last and off first, you should
select C as the Aux Output and set this delay time to be longer than
the delay that you set for Main Bank C On.
Aux Delay Off
Set the delay time in seconds for the auxiliary relay opening. This
delay time begins with the same internal trigger as the bank selected
in Aux Output. For example, if you wanted a forth bank to power on
first and off last, you should select A as the Aux Output and set this
delay time to be longer than the delay that you set for Main Bank A
Off; or if you wanted a forth bank to power on last and off first, you
should select C as the Aux Output and set this delay time to be shorter
than the delay that you set for Main Bank C Off (the Aux Delay Off
can be set to zero in this case).
5.5
Front Panel Push Button
The front panel push button allows the unit to be powered up or powered down from the front
panel. There is one menu item associated with the push button which allows it to be disabled or
to operate only after a one second delay. The delay option prevents the unit inadvertently
powering on or off if the push button is accidentally bumped. Note that the push button cannot be
used in conjunction with applied voltage or latching type remote control inputs.
Fr. Panel Button
Select “Enable” for normal operation, “Delay” to operate only after a
one-second delay, and “Disable” to prevent operation from the front
panel.
5.6
Out-of-Range AC Voltage Shut Down
The XQ515 has built-in line voltage monitoring and out-of-range shut down. The default limits
are 90V at the low end and 150V at the high end, and the shut down XQ515uence begins if the
line voltage remains outside the set limits for 1 second or more. These limits are adjusted by
using two menu items, with the low limit adjustable from 90V to 110V and the high limit
adjustable from 130V to 150V. If the unit has shut down due to an out-of-range line voltage and
the line voltage subXQ515uently returns to normal, the power up XQ515uence will only resume
if the Power Fail Restore option (section 5.8) has been set to “Enable”.
Low-V Shut Down
Set the low voltage shut down limit from 90V to 110V
High-V Shut Down
Set the high voltage shut down limit from 130V to 150V