User Manual
© 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / surgex.com
16
e. Settings Mode
The Settings mode enables the specification of the user-configurable
parameters of Next Gen. When this mode is entered, it displays the
parameters currently in use. Firmware versions prior to 1.53 (120V models)
and 1.02 (208-240V models) do not support the Auto Transmit feature.
i. Auto Transmit: Enables/Disables the automatic transmission of status
information every 30 minutes. Primarily intended for use with Remote
Portal RP-IP.
ii. Update ID: Sets the product identifier specified in the text box. 10
character limit. This is a temporary setting intended to set an ID for
saved reports.
iii. Update Limits: Sets the voltage thresholds specified by the voltage
threshold selection fields. Press
Default
to select factory default limits.
Note:
Restore points may not be specified for Next Gen PCS.
x
. Language: Select the software’s display language.
xi. Save: Save the current settings for reference.
Limit
When Activated
Action
Factory Default
120V
208/240V
Over Voltage
Shutdown
V > OV
Shutdown
Outlets turned
Off
and
event recorded
150
260
Over Voltage
Record
OV
Shutdown
> V > OV
Record
Outlets stay
On
and
event recorded
135
260
Over Voltage
Restore
V < OV
Restore
After OV
Shutdown
Outlets turned
On
140
250
Under Voltage
Restore
V > UV
Restore
After UV
Shutdown
Outlets turned
On
105
190
Under Voltage
Record
UV
Shutdown
< V < UV
Record
Outlets stay
On
and
event recorded
100
180
Under Voltage
Shutdown
V < UV
Shutdown
Outlets turned
Off
and
event recorded
0
(Disabled)
140