![SurgeX SX-BDL-1500 User Manual Download Page 30](http://html1.mh-extra.com/html/surgex/sx-bdl-1500/sx-bdl-1500_user-manual_1407291030.webp)
© SurgeX | Technical Support: 800-645-9721 | surgex.com
Page 29
On-Line UPS
User Manual
Models: UPS-1500-OL, UPS-2000-OL, UPS-3000-OL
SX-BDL-1500, SX-BDL-2000
EXTENDED BATTERY
PACK MODELS
UPS-BPX 1500
UPS-BPX-2000
INPUT
Voltage
120 VAC
AC Current
2.2A
4A
Frequency
50/60 Hz auto sensing
Input Protection
circuit breaker
CHARGER
OUTPUT
DC Voltage
55.0 ±0.5V
110.0 ±0.5V
DC Current
2.5A (max)
Output Protection
Fuse
BATTERY
Battery Type
sealed, non-spillable, maintenance free, valve regulated, lead
acid
Extended Battery Packs EBP2
EBP3
Battery Type (EBP)
2 strings of (4) 12V 7.2 AH /
48V
2 strings of (8) 12V 7.2 AH /
96V
Recharge Time
< 4 hours to 90%
< 6 hours to 90%
PHYSICAL
Dimensions
W x D x H (inches)
Unit Dimensions
17.3" x 25.6" x 3.4"
17.3" x 21.7" x 5.2"
Shipping Dimensions
22.3" x 31.4" x 9.2"
22.3" x 27.4" x 11.0"
Unit Weight
75.0 lbs
113.6 lbs
Shipping Weight
86.0 lbs
125.7 lbs
Line Cord
5-15P
Included in box
EBP, User Manual, DC cable, AC input cord
EXTENDED BATTERY
PACK MODELS
UPS-BPX 1500
UPS-BPX-2000
WARRANTY
Warranty
Three years electronics /
Three
year
s
batter
y
APPROVALS
North America
UL cUL FCC
INDICATORS &
ALARMS
LED Visual Display
Charging LED, Battery test LED