iControl Manual
29
SNMP
Up to four SNMP managers can be set. Each manager will receive Trap notifications for outlet
changes, autoping, voltage alarms, and current alarms. Set the SNMP manager IP addresses
using the
set snmp <n> ipaddress <dotted decimal>
command. Enable or Disable SNMP for
any manager with the
set snmp <n> enable <yes/no>
command. Also see
“iControl q110630.285.mib” for more information.
The iControl also supports the following elements of MIB-II:
mgmt [1.3.6.1.2]
|
-> [ 1] -BR- mib-2
|
-> [ 1] -BR- system
|
-> [ 1] *RO* DisplayString
sysDescr
-> [ 2] *RO* OBJECT IDENTIFIER
sysObjectID
-> [ 3] *RO* TimeTicks
sysUpTime
-> [ 4] *RW* DisplayString
sysContact
Truncated to 128 Char
-> [ 5] *RW* DisplayString
sysName
Truncated to 128 Char
-> [ 6] *RW* DisplayString
sysLocation
Truncated to 128 Char
-> [ 7] *RO* INTEGER
sysServices
FIRMWARE UPGRADES
The iControl can be upgraded via the network if the upload feature has been enabled using the
set upload enable yes
command on the console interface. To upgrade the iControl, download the
latest version of the firmware and upgrade utility from the SurgeX website.
The recessed reset pushbutton located on the front panel below the Self Test LED performs two
functions: CPU Reboot and Password Reset.
Pressing the reset button once quickly will reboot the iControl’s CPU. Outlet states are not
affected.
Holding the reset button on the front panel of the iControl for 5 seconds or longer will initiate a
password recovery mode. Once the reset button is released, the user has 30 seconds to log in to
the CLI using the username
admin
and password
admin
. Upon accessing the CLI, change the
username and password for User 1 as desired.