LED INDICATORS 
 

There are four LED indicators located on the front panel. Their function is as follows: 
 

Surge SELF TEST (Green):

  When illuminated, the surge suppression circuitry is functioning correctly. 

 

Status LED and Alarm Table 

UPS Status 

Green LED 

Yellow LED 

Red LED 

Alarm 

UPS Self-Test 

All LEDs cycle (each LED blinks 1/1.5 Seconds) 

1-Beep/5-sec 

AC Mode 

Normal 

On 

Off 

Off 

Off 

Boost 

1-Blink/1.5sec 

Off 

Off 

Off 

Buck 

2-Blinks/sec 

Off 

Off 

Off 

Self Low Battery 

On 

Off 

2-Blinks/sec 

3-Beeps/30-sec 

Overload 

On 

Off 

2-Blinks/sec 

2-Beeps/sec 

Battery Mode

 

Normal 

Off 

On 

Off 

1-Beep/5-sec 

Overload 

Off 

On 

2-Blinks/sec 

2-Beeps/sec 

Low Battery 

Off 

2-Blinks/sec 

Off 

2-Beeps/5-sec 

Short/Fault Mode 

Off 

Off 

On 

Continuous 

Over-Bat/Bat Fault 

Off 

Off 

2-Blinks/sec 

3-Beeps/5-sec 

 

 
ALARMS 
 
On Battery

 – When the UPS is operating on the batteries, the On Battery LED will illuminate and the audible 

alarm will sound once every five seconds. The alarm will stop once the UPS returns to the AC normal mode. 
 

Low Battery Warning - 

The UPS will sound two beeps every five seconds when the battery reserve runs low. 

This condition will continue until the AC returns or the UPS shuts down from battery exhaustion. 
 

Weak/Bad Battery – 

The UPS automatically tests the battery’s condition and will illuminate the BAD 

Battery/Overload/Fault LED and sound the alarm. This alarm will be repeated until the batteries pass a self test. 
If the battery is weak, bad, or disconnected, the Bad Battery/Overload/Fault LED will illuminate and the alarm 
will beep three times every thirty seconds until the battery is reconnected or replaced. It is recommended that 
the UPS be allowed to charge overnight before performing a battery test to confirm a Weak/Bad Battery 
condition. 
 

Overload – 

When the amount of load attached to the UPS exceeds its power rating, the Bad 

Battery/Overload/Fault LED will illuminate and the UPS will sound 1 beep every half second (AC and Battery 
modes). This alarm will remain on until the excess load is removed or the UPS’s self protection circuit shuts the 
UPS down. 
 

UPS Fault – 

When the UPS detects a hardware fault, the Bad Battery/Overload/Fault LED will illuminate and 

the UPS will sound a constant alarm. The fault condition, in some instances, may be reset by turning the UPS 
off and then on. 

Summary of Contents for SU1000Li

Page 1: ...USER MANUAL SurgeX SU1000Li Line Interactive 1000VA UPS with Automatic Voltage Regulation Surge Eliminator Power Conditioner...

Page 2: ...YOUR EQUIPMENT 2 USB COMMUNICATIONS PORT CONNECTION 3 PHONE FAX MODEM NETWORK PROTECTION CONNECTION 3 OPERATION 3 CHARGING THE BATTERY 3 TURNING THE UNIT ON OFF 3 USB COMMUNICATIONS PORT 3 POWER MONI...

Page 3: ...tion To reduce the risk of fire connect only to a circuit provided with 20 amperes maximum branch circuit over current protection in accordance with the National Electric Code ANSI NFPA 70 Plug the UP...

Page 4: ...is connected to an AC source and there is an acceptable AC voltage present 90 150VAC It is recommended that the UPS s batteries be charged for a minimum of 4 hours before use The UPS may be used immed...

Page 5: ...eeps every five seconds when the battery reserve runs low This condition will continue until the AC returns or the UPS shuts down from battery exhaustion Weak Bad Battery The UPS automatically tests t...

Page 6: ...does not provide expected runtime The batteries may be weak or at the end of useful service life Charge the batteries for 8 hours and retest If the runtime is still less than expected the batteries m...

Page 7: ...and boots 4 Do not lay tools or other metal parts on top of the batteries 5 Disconnect the charging source prior to connecting or disconnecting the battery terminals 6 Determine if the battery is inad...

Page 8: ...d Capability 110 5 minutes 120 immediate shutdown Output Voltage Regulation 120VAC 12 5 to 8 4 Waveform Same as Input Boost Mode Voltage Buck mode voltage Nominal 16 Nominal 14 Line Mode Voltage Range...

Page 9: ...C62 41 1991 Category B3 pulses 1kV 500 000 3 kV 10 000 6 kV 1000 General Specifications Warranty USA and Canada only 10 year limited warranty Battery Warranty 2 years Monitoring Software Includes Sent...

Reviews: