SurgeX SU1000Li Manual Download Page 3

SU1000Li Manual                                                                                                                                            

 

 

 

INTRODUCTION 

 
The SU-1000Li is a 1000 VA line interactive uninterruptible power supply, surge eliminator, and power conditioner in a magnetically 
shielded steel enclosure. It operates from 120 volts AC and has a 6-foot, grounded, 3-wire #14 line cord. It has 4 grounded AC 
receptacles and two of these provide battery back-up protection. Overall dimensions are 3.5” H x 19.0” W x 10.5” D. Weight is 32.0 
pounds.  
 
The SU-1000Li has a load rating of 15 amps at 120 volts, a self-test circuit with visual indicator, and provides EMI/RFI filtering. It 
meets Federal Grade A, Class 1, Mode 1 guidelines for power line surge suppressors and withstands at least 1000 occurrences of surge 
pulse voltages, up to 6000 volts. SentryPlus™ auto shutdown and monitoring software is also included with SU-1000Li hardware. 

 
INSTALLATION 

 
The SurgeX SU 1000Li is designed to be installed in a 19 inch equipment rack and requires two units (2-U) of 
rack space. Remove the product from its packaging and slide it into place in the rack being careful to feed the 
power cord into the rack first and guide it so that it does not get caught or jammed as the product is installed. 
Use the four screws provided with the product to secure the rack ears to the rack rails. These screws can be 
tightened by hand and do not require tools. 
 

120 Volt Connections 

 
Connect power to the unit by plugging the cord into a 120V ac receptacle.  
 
Caution – To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch 
circuit over-current protection in accordance with the National Electric Code, ANSI/NFPA 70. Plug the UPS 
into a two pole, three wire, grounded receptacle only. Do not use extension cords, adapter plugs, or surge strips. 
 
The SU 1000Li has a total of 6 receptacles: 2 UPS/surge protected outlets, 4 surge protection only outlets. Each 
receptacle is rated for a maximum load of 15 amps, but the total load also must not exceed 15 amps. Plug the 
equipment cords into the UPS/surge outlets or the surge protection only outlets. Note that the UPS outlets 
should not be used when equipment load is expected to exceed 1000VA (600W).  
 

Battery Connection 
 

The SU 1000Li is shipped with the batteries disconnected. Batteries must be connected before use. To connect, 
remove the two screws from the battery access panel on rear of unit. Slide battery pack out partially and attach 
the red wires/connectors together (these wires can be found sitting on top of the batteries). Carefully slide the 
battery back into the chassis until it is flush with the chassis edge and replace the battery access panel using the 
two screws in the right side of the panel.

 

 
Connecting Your Equipment 
 

Plug the mission critical equipment into the UPS/Surge output receptacles on the rear panel of the UPS. Plug 
the non-critical equipment into the Surge Only output receptacles on the rear panel of the UPS. Do not use 
extension cords, adapter plugs or surge strips on the output of the UPS. Ensure that you do not exceed the 
maximum output rating of the UPS. 
 
 

Summary of Contents for SU1000Li

Page 1: ...USER MANUAL SurgeX SU1000Li Line Interactive 1000VA UPS with Automatic Voltage Regulation Surge Eliminator Power Conditioner...

Page 2: ...YOUR EQUIPMENT 2 USB COMMUNICATIONS PORT CONNECTION 3 PHONE FAX MODEM NETWORK PROTECTION CONNECTION 3 OPERATION 3 CHARGING THE BATTERY 3 TURNING THE UNIT ON OFF 3 USB COMMUNICATIONS PORT 3 POWER MONI...

Page 3: ...tion To reduce the risk of fire connect only to a circuit provided with 20 amperes maximum branch circuit over current protection in accordance with the National Electric Code ANSI NFPA 70 Plug the UP...

Page 4: ...is connected to an AC source and there is an acceptable AC voltage present 90 150VAC It is recommended that the UPS s batteries be charged for a minimum of 4 hours before use The UPS may be used immed...

Page 5: ...eeps every five seconds when the battery reserve runs low This condition will continue until the AC returns or the UPS shuts down from battery exhaustion Weak Bad Battery The UPS automatically tests t...

Page 6: ...does not provide expected runtime The batteries may be weak or at the end of useful service life Charge the batteries for 8 hours and retest If the runtime is still less than expected the batteries m...

Page 7: ...and boots 4 Do not lay tools or other metal parts on top of the batteries 5 Disconnect the charging source prior to connecting or disconnecting the battery terminals 6 Determine if the battery is inad...

Page 8: ...d Capability 110 5 minutes 120 immediate shutdown Output Voltage Regulation 120VAC 12 5 to 8 4 Waveform Same as Input Boost Mode Voltage Buck mode voltage Nominal 16 Nominal 14 Line Mode Voltage Range...

Page 9: ...C62 41 1991 Category B3 pulses 1kV 500 000 3 kV 10 000 6 kV 1000 General Specifications Warranty USA and Canada only 10 year limited warranty Battery Warranty 2 years Monitoring Software Includes Sent...