Sure Flame ID 100 Instruction Manual Download Page 5

 

EN

 

TROUBLESHOOTING 

 

OBSERVED FAULT 

CAUSE 

REMEDY 

• Motor does not start, no ignition 

• No electrical current 

• Check mains 

• Check proper positioning and functioning of 

switch 
• Check fuse 

• Wrong setting of room thermostat or 

other control 

• Check correct setting of heater control. If 

thermostat, make sure selected temperature is 

higher than room temperature 

• Thermostat or other control defective  • Replace control device  
• Electrical motor defective 

• Replace electrical motor 

• Electrical motor bearings defective 

• Replace electrical motor bearings  

• Burned out condenser 

• Replace condenser 

• Motor starts, no ignition or cuts out 

• Electric ignitor defective 

• Check connection of H.T. Ieads to electrodes 

and transformer 
• Check electrodes setting (see scheme 

“POSITIONING OF ELECTRODES”) 
• Check electrodes for cleanliness 
• Replace H.T. transformer 

• Flame control box defective 

• Replace control box  

• Photocell defective 

• Clean or replace photocell  

• Not enough or no fuel at all at burner 

• Check state of motor-pump plastic coupling  
• Check fuel line system including fuel filter for 

 possible leaks 

• Clean or replace oil nozzle  

• Solenoid defective 

• Check electrical connection 
• Check thermostat LI 
• Clean or replace solenoid 

• Motor starts, heater emits smoke 

• Not enough combustion air 

• Make sure air inlet and outlet are free 
• Check setting of combustion air flap 
• Clean burner disc 

• Too much combustion air 

• Check setting of combustion air flap 

• Fuel contaminated or contains water  

• Drain fuel in tank with clean fuel 
• Clean oil filter 

• Air leaks in fuel circuit 

• Check the seals on the ducts and the diesel 

filter 

• Not enough fuel at burner 

• Check pump pressure 
• Clean or replace fuel nozzle 

• Too much fuel at burner 

• Check pump pressure 
• Replace nozzle 

• Heater does not stop 

• Solenoid defective 

• Replace solenoid coil or complete solenoid 

 

 

If the heater is still not working properly, please contact your nearest authorized dealer. 

 

 

Summary of Contents for ID 100

Page 1: ...CONSTRUCTION HEATERS GENERATEURS D AIR CHAUD L L 103 02 SU ID 100 ID 200 ID 300 INSTRUCTION MANUAL LIVRET D ENTRETIEN...

Page 2: ...FUEL TANK R SERVOIR COMBUSTIBLE 13 RESET BUTTON OF THE ELECTRONIC EQUIPMENT BOUTON DE REARMEMENT DE L APPAREILLAGE 14 MAIN SWITCH INTERRUPTEUR MARCHE ARRETE 15 ROOM THERMOSTAT PLUG PRISE THERMOSTAT D...

Page 3: ...ding on the function mode off heater is in stand by waiting for heating call steady green heater functioning normally steady red heater in safety stop To restart heating after a safety stop push reset...

Page 4: ...similar equipment In this case make sure that the ropes and or chains are securely attached and that they are in perfect condition before you start to move the heater MAINTENANCE To ensure correct he...

Page 5: ...efective Replace control box Photocell defective Clean or replace photocell Not enough or no fuel at all at burner Check state of motor pump plastic coupling Check fuel line system including fuel filt...

Page 6: ...t d une cellule photo lectrique de contr le de la flamme d un thermostat de surchauffe pour le contr le de la temp rature maximale et d un pressostat de l air Le bo tier lectronique g re les temps de...

Page 7: ...ionnement de la machine Le g n rateur peut tre fourni en version mobile muni de roues ou en version suspendue mont sur une structure de support avec des ancrages pour le fixage qui doit tre effectu av...

Page 8: ...mplacer Le fuel n arrive pas au br leur ou arrive en quantit insuffisante Contr ler l efficacit du raccord moto pompe Contr ler qu il n y ait pas d infiltrations d air dans le circuit du fuel en v rif...

Page 9: ...MOIN D ALIMENTATION LI1 OVERHEAT THERMOSTAT THERMOSTAT DE SURCHAUFFE EV1 SOLENOID VALVE I Stage ELECTROVANNE I Stade CO CAPACITOR CONDENSATEUR MV FAN MOTOR MOTEUR DU VENTILATEUR FUA FUSE 6 3 A FUSIBLE...

Page 10: ...THERMOSTAT DE SURCHAUFFE EV1 SOLENOID VALVE I Stage ELECTROVANNE I Stade CO CAPACITOR CONDENSATEUR MV FAN MOTOR MOTEUR DU VENTILATEUR FUA FUSE 6 3 A FUSIBLE 6 3 A RV CONTROL SWITCH COMMUTATEUR PA AIR...

Page 11: ...eiling 2 m Floor combustible LEGENDE A Minimum 1 m B Minimum 1 m C Le plus court possible D Egal superieur au diam tre de la chemin e du g n rateur E Minimum 1 m 1 Accessoire anti refoulement 2 Passag...

Page 12: ...ique W 440 785 1 330 A 4 05 7 65 11 80 Nozzle Gicleur USgal h 0 55 80 W 1 10 80 W 1 50 80 W Pump pressure Pression pompe psi 196 174 174 Static pressure Pression statique in WC 0 5 0 5 0 5 Adjustment...

Reviews: