Heatseeker Nova+ Inverter Heat Pump
Troubleshooting
Troubleshooting - Heatseeker Nova+
Error Code Displayed on LED Controller
MALFUNCTIONS
ERROR REASONS
SOLUTIONS
Inlet water temperature sensor
failure
PP01
The sensor has an open or short
circuit
Check or change the sensor
Outlet water temperature sensor
failure
PP02
The sensor has an open or short
circuit
Check or change the sensor
Condenser sensor failure
PP03
The sensor has an open or short
circuit
Check or change the sensor
Gas return sensor failure
PP04
The sensor has an open or short
circuit
Check or change the sensor
Ambient temperature sensor failure
PP05
The sensor has an open or short
circuit
Check or change the sensor
Gas exhaust sensor failure
PP06
The sensor has an open or short
circuit
Check or change the sensor
Antifreeze protection in winter
PP07
Ambient temperature or
water inlet temperature is
too low
1. The first grade antifreeze
protection condition: when
6°C<T1 water in temperature
<10°C and T5 ambient
temperature 3°C, water pump
should operate 30 minutes, then
stop 30 minutes in this cycle.
When ambient temperature
T5>5°C or T1 water in
temperature 15°C, water pump
stop operating will activate the
antifreeze protection.
2. The second grade antifreeze
protection condition; T1 water in
temperature 6°C and T5 2°C, it
goes into the second antifreeze
protection, the heat pump
should go into Smart mode for
water heating will to T1>15°C or
T5>7°C.
Remarks: The water pump and heat
pump must be turned ON or in
standby status.