11
Installation
•
Connect a diode to both ends of the power input as shown in the figure below when installing a deadbolt or a
door strike. Make sure to connect the Cathode (direction to the stripe) to the + part of the power while paying
attention to the direction of the diode.
•
Do not connect the relay of the Input Module in duplicate to the device connected to the relay port of the
master device.
Supervised Input Connection
You can connect a fire sensor, heat sensor, security sensor, door sensor, exit button, or etc. The SUPERVISED INPUT 0
to 11 pins detect the voltage flowing through the circuit to monitor device disconnection, short, on, and off conditions,
and can also be used as a general TTL input. With BioStar 2, you can set the behavior according to the Supervised Input
status, and you can monitor the status of each input.
EMERGENCY
•
Do not connect the input of the Input Module in duplicate to the device connected to the input port of the
master device.
•
The Input Module can be used by connecting 1 kΩ, 2.2 kΩ, 4.7 kΩ, or 10 kΩ resistors. After connecting the
resistor corresponding to the input device of the connection, set the same resistance value in BioStar 2.
•
To learn how to operate it depending on the supervised input status, refer to the manual of BioStar 2.
Motion Sensor
Motion Sensor
Smoke Sensor
Emergency
Button
Exit
Button
Door Sensor