background image

SuperiorFireplaces.us.com

901010-00_C

8

AIR FOR COMBUSTION AND VENTILATION  

Continued

   ______ Btu/Hr (maximum the space can support) 
   ______ Btu/Hr (actual amount of Btu/Hr used)
 

Example:

 63,360 Btu/Hr (maximum the space can support)

   

 79,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the example is a confined space because the actual Btu/

Hr used is more than the maximum Btu/Hr the space can support. 

You must provide additional fresh air. Your options are as follows:
A.  Rework worksheet, adding the space of an adjoining room. If the 

extra space provides an unconfined space, remove door to adjoining 

room or add ventilation grills between rooms. See Ventilation Air 

From Inside Building.

B.  Vent room directly to the outdoors. See Ventilation Air From 

Outdoors.

C.  Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room 

unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space 

can support, the space is an unconfined space. You will need no ad-

ditional fresh air ventilation.

 WARNING: If the area in which the heater may be 

operated does not meet the required volume for indoor 

combustion air, combustion and ventilation air shall 

be provided by one of the methods described in the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54, the 

International Fuel Gas Code, or applicable local codes.

VENTILATION AIR
Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When 

ventilating to an adjoining unconfined space, you must provide two 

permanent openings: one within 12" of the ceiling and one within 12" 

of the floor on the wall connecting the two spaces (see options 1 and 

2, Figure 4). You can also remove door into adjoining room (see option 

3, Figure 4 ). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 

54, Air for Combustion and Ventilation for required size of ventilation 

grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must 

provide two permanent openings: one within 12" of the ceiling and 

one within 12" of the floor. Connect these items directly to the out-

doors or spaces open to the outdoors. These spaces include attics 

and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/

NFPA 54, Air for Combustion and Ventilation for required size of 

ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air 

into attic if attic has a thermostat-controlled power vent. 

Heated air entering the attic will activate the power vent.

Figure 4 - Ventilation Air from Inside Building

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills Into

Adjoining 

Room,

Option 1

12"

12"

Figure 5 - Ventilation Air from Outdoors

Outlet

Air

Ventilated

Attic 

Outlet

Air

Inlet

Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Summary of Contents for VRE6036

Page 1: ...In addition to instructing you on how to install and maintain your appliance it also contains information that will enable you to obtain replacement parts or accessory items when needed Keep it with...

Page 2: ...ING Anychangetothisfireboxoritscontrols can be dangerous WARNING Do not allow fans to blow directly into the firebox Avoid any drafts that alter burner flame patterns Ceiling fans can create drafts th...

Page 3: ...ve type unvented room heaters Physical size limitations apply Refer to minimum firebox requirements supplied with log heater It requires no outside venting or chimney making installation easy and inex...

Page 4: ...ces us com 901010 00_C 4 PRODUCT SPECIFICATIONS 36 MODELS Figure 1 VRE6036 36 HEARTH 29 30 1 2 30 36 54 3 4 11 1 8 45 1 4 36 3 8 35 1 4 22 1 2 9 1 2 3 3 8 7 3 8 11 1 8 20 1 4 Ref 1 1 4 19 50 1 8 3 3 4...

Page 5: ...s com 901010 00_C 5 PRODUCT SPECIFICATIONS Continued 42 MODELS Figure 2 VRE6042 42 HEARTH 21 3 4 8 3 4 3 3 8 9 1 2 26 3 8 41 3 8 4 7 8 1 1 4 3 3 4 32 3 8 36 3 8 11 1 8 7 7 8 51 1 4 7 42 13 50 1 8 54 3...

Page 6: ...s com 901010 00_C 6 Figure 3 VRE6050 21 3 4 1 1 4 8 3 4 9 1 2 3 3 8 13 50 1 8 50 7 30 34 3 8 38 3 8 4 7 8 49 3 8 36 3 8 59 1 4 54 3 4 11 1 8 3 3 4 32 3 8 7 7 8 23 Ref 50 HEARTH PRODUCT SPECIFICATIONS...

Page 7: ...fresh air See Ventilation Air From Outdoors page 8 If your home does not meet all of the three criteria above proceed to Determining Fresh Air Flow For Firebox Location Confined and Unconfined Space...

Page 8: ...AIR Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space When ventilating to an adjoining unconfined space you must provide two permanent openings one wit...

Page 9: ...ttom of your firebox except where standoff spacers are integrally attached If standoff spacers are attached to your firebox these spacers can be placed directly against wall or framing materials Use t...

Page 10: ...low all minimum clearances shown in this manual NOTICE Ifyourinstallationdoesnotmeettheminimum clearances shown you must do one of the following raise the mantel to an acceptable height remove the ma...

Page 11: ...es This firebox may be installed using a cabinet mantel against a wall in your home The firebox and cabinet mantel can be installed directly on the floor Mantels may be available from your retailer or...

Page 12: ...and Leading Brick panels Hearth Panel Side leading brick Panel 3 Install the left and right firebrick walls There is a bracket with 2 tabs on the bottom of each firebrick wall Angle the wall into the...

Page 13: ...l to avoid spilling Place a wet towel over the bucket making sure it is directly on the surface of grout mixture This will keep the mixture moist and it will not dry out before use 5 Grout all joints...

Page 14: ...rnace cement Install the gas appliance or cap off gas line if desired A gas line or gas log lighter may be installed for the purpose of installing a vent free decorative gas appliance incorporating an...

Page 15: ...r or dealer Parts will be shipped at prevailing prices at time of order CAT NO MODEL DESCRIPTION OPTIONAL AIR KITS F1091 AK4F Outside Air Kit For Floor Installation F1094 AK4 Outside Air Kit For Sidew...

Page 16: ...SuperiorFireplaces us com 901010 00_C 16 11 10 11 13 14 15 16 14 3 20 20 21 1 19 5 14 15 16 13 12 11 9 7 6 8 17 2 12 18 4 PARTS 36 42 AND 50 MODELS...

Page 17: ...12 J5329 BRACKET F P HANDLE 4 13 J6900 PLATE OUTSDE AIR COVER 36E44 6 2 14 J6934 COVER GAS CONDUIT PLATE 36E 4 15 J4368 GAS CONDUIT ONE 2 16 J4369 GAS CONDUIT TWO 2 17 HEAT SHIELD SUPPORT 1 18 FIREBO...

Page 18: ...0342 Mosaic42WRFS Masonry 42 Warm Red Full Stacked F0343 Mosaic42WRSS Masonry 42 Warm Red Split Stacked F0346 Mosaic42WRFH Masonry 42 Warm Red Herr Full F0347 Mosaic42WRSH Masonry 42 Warm Red Herr Spl...

Page 19: ...ned to burn either natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could resul...

Page 20: ...ealer name P901010 00 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and produ...

Reviews: