Your options are:

a. Rework equations adding the space of ad-

joining room(s). If the extra volume provides
an unconfined space, then remove door or
add ventilation grills between rooms. Refer
to National Fuel Gas Code, ANSI Z223.1
1992, Section 5.3.

b. Vent room directly to the outdoors. Refer to

National Fuel Gas Code, ANSI Z223.1 1992,
Section 5.3.

c. Install a lower BTU/Hr heater, to make the

area an unconfined space.

If the actual BTU/Hr used is less than the
maximum BTU/Hr the space can support, then
the space is an unconfined space. You will need
no additional fresh air ventilation for an uncon-
fined space.

LOCATION OF FIREPLACE

Carefully select the best location for installa-
tion of your VF4000 series Unvented Room
Heater. The following factors should be taken
into consideration:

• Clearance to side wall, ceiling, woodwork
and windows.

• Location must not be affected by drafts
caused by kitchen exhaust fans, return air reg-
isters for forced air furnaces/air conditioners,
windows or doors.

• Installation must provide adequate ventila-
tion and combustion air.

• Do not install the VF4000 series heaters in a
sleeping room or bathroom.

• Never obstruct the front opening of the heater
or restrict the flow of combustion and ventila-
tion air.

• This appliance may be installed in an after-
market* manufactured (Mobile) Home, where
not prohibited by state or local codes.
*Aftermarket:  Completion of sale, not for pur-
pose of resale, from the manufacturer.

• Minimize modifications to existing construc-
tion. Refer to 

Figure 1  for location suggestions.

Figure 1

To ensure even heat distribution, it is best to
position the heater centrally against the longest
wall of the room. Make sure there is adequate
ventilation where the heater is installed. The
gas appliance will shut off if the oxygen level
falls below 18%.

These appliances are uniquely suited for instal-
lations requiring a utility shelf positioned di-
rectly above the fireplace.  Utility shelves like
these are commonly used for locating televi-
sion sets and decorative plants.

To provide for the lowest possible shelf sur-
face, combustible materials used to support a
utility shelf directly above these appliances
should be positioned just above the appliance
top spacers. The minimum height from the
base of the VF4000 to the underside of com-
bustible materials used to construct a utility
shelf is 37-1/4” (946 mm).

The appliance should be mounted on a fully
supported base extending the full width and
depth of the unit. The appliance may be located
on or near conventional construction materi-
als. However, if installed on combustible mate-
rials, such as carpeting, vinyl tile, etc., a metal
or wood barrier covering the entire bottom
surface must be used.

If the appliance is to be elevated above floor
level, a solid continuous platform must be
constructed.

WARNING:  MAINTAIN MINIMUM
CLEARANCES.

WARNING: IF THE AREA IN WHICH THE
HEATER MAY BE OPERATED IS SMALLER
THAN THAT DEFINED AS AN UNCON-
FINED SPACE, PROVIDE ADEQUATE
COMBUSTION AND VENTILATION AIR BY
ONE OF THE METHODS DESCRIBED IN
THE NATIONAL FUEL GAS CODE, ANSI
Z223.1 1992, SECTION 5.3 OR APPLI-
CABLE LOCAL CODES.

Use the following equations to determine if you
have a confined or unconfined space.

1. Determine the volume of space — ft

3

.

Length x Width x Height  = _____ ft

3

(Include adjoining rooms with doorless pas-
sageways or ventilation grills between
rooms.)

Example: 20' (L) x 16' (W) x 8' (H) = 2560 ft

3

2. Divide the volume of space by 50 ft

3

 to

determine the maximum BTU/Hr the space
can support.

______ (volume of space – ft

3

)/ 50 ft

3

  =

(Maximum BTU/Hr the space can support)

Example:  2560 ft

3

 / 50 ft

3

 = 51.2

or 51,200 BTU/Hr the space can support.

3. Add the BTU/Hr of all the fuel burning appli-

ances in the space.

Vent-Free heater

_______

BTU/Hr

Gas appliance #1*

_______

BTU/Hr

Gas appliance #2

+ _______

BTU/Hr

Total = _______

BTU/Hr

Example:
VF4000 Vent-free heater 25,000

BTU/Hr

Gas appliance #1

34,000

BTU/Hr

(water heater)

Total =

59,000

BTU/Hr

* Do not include direct-vent gas appliances.
Direct-vent is sealed combustion and draws
combustion air from the outdoors.

4. Compare the maximum BTU/Hr the space

can support with the actual amount of BTU/
Hr used.

_________ BTU/Hr

(max. the space can support)

_________ BTU/Hr

(actual amount of BTU/Hr used)

Example:

51,200

BTU/Hr
(max. the space can support)

59,000

BTU/Hr
(actual amount of BTU/Hr used)

The space in the above example is a confined
space because the actual BTU/Hr used is more
than the maximum BTU/Hr the space can sup-
port. You must provide additional fresh air.

Summary of Contents for VF4000-CHN-2 and

Page 1: ...IREBOX MEETS THE MINIMUM DIMENSIONS REQUIRED FOR THE INSTALLATIONS This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combustion and...

Page 2: ...e page 9 Optional Equipment page 10 Forced Air Kit page 10 Operation and Care page 11 Cleaning and Servicing page 11 Replacement Parts page 11 Accessories Components page 12 Appliance Specifications p...

Page 3: ...ft 3 per 1 000 BTU Hr 4 8 m3 per kw of the aggregate input rating of all appliances installed in that space Rooms communicat ing directly with the space in which the appli ances are installed through...

Page 4: ...above these appliances should be positioned just above the appliance top spacers The minimum height from the base of the VF4000 to the underside of com bustible materials used to construct a utility s...

Page 5: ...Thefollowingstepsrepresentthenormal sequence of installation Each installation is unique however and might require a different sequence CAUTION HEATERSCREATEWARMAIRCUR RENTS THESE CURRENTS MOVE HEAT...

Page 6: ...canresultincorrosionovertime Never use an open flame to check for leaks Figure 4 37 940mm 15 1 2 394mm Outside Wall Back Wall of Chase Enclosure Including Finishing Materials If Any Figure 5 37 940mm...

Page 7: ...gure 12 ensuring that the polarity as determined by the colors of the wires is exactly as shown The black and red wire loop must be left intact with the mating connectors connected Figure 10 VF4000 CM...

Page 8: ...hejunctionbox cover plate Failure to do so will prevent the appliance from operating The appliance must be electrically grounded in accordance with local codes or in the absence of local codes the Nat...

Page 9: ...d 16 Note Instructions are also found on the pull out panel located on the bottom surface of the appliance Figure 16 Figure 18 Standard Manual Version Shown After setting the logs into position as des...

Page 10: ...ive illustrations The appliances covered in this manual are heater rated and produce a great deal of heat Decorative brass trim pieces and hoods may tarnish because of their proximity to the heater op...

Page 11: ...it should be installed along with the appliance Refer to Figure 11 andStep5fordetailedinstallationinstructions Rocker Switch Kit An optional rocker switch kit can be installed directly on VF4000 CMN P...

Page 12: ...as Flex Line Kit FFGC Refractory Liner Kit VF5RLK Decorative Volcanic Stone FDVS Wood Surround Wall SUR 5PW Wood Surround Corner SUR 5PC Brass Louver Kit BRLK 5C BSK 5 Brass Surround Kit BRLK CS Squar...

Page 13: ...940 mm 36 914 mm 30 762 mm 31 1 2 800 mm 15 381 mm Front View Left Side View Right Side View Opposite Gas Line Opening J Box Opening 8 203 mm 3 3 4 95 mm 3 1 2 89 mm Top View 27 686 mm 36 914 mm 15 1...

Page 14: ...e failure detector from shutting off the gas while the probe is warming up 10 Release the control knob while turning counterclockwise to the HI or LOW Position If the knob does not pop out when releas...

Page 15: ...E DIAGRAMS ILLUSTRATION NOT TO SCALE 15 Figure 22 Pilot Location Figure 23 Pilot Turn Control Knob to OFF Position Figure 24 Turn Control Knob to IGN Position O F F I G N L O W H I O F F I G N L O W H...

Page 16: ...STOP Read the safety information above on this page 2 Access left side louver 3 Turn remote wall switch to OFF 4 Verify main line shut off valve is open 5 Push in gas control knob slightly and turn c...

Page 17: ...orifice Replace burner Replace gas regulator Problem will stop after a few hours of operation SFC recommends running the heater with excess ventilation for the first few hours Turn control knob to LO...

Page 18: ...0345 1 110344 1 Pilot Propane LPG 110341 1 901915 1 4 Regulator Natural 110351 1 903218 1 Regulator Propane LPG 110352 1 112081 1 5 Front Burner 110281 1 110281 1 6 Rear Burner Natural 113301 1 113301...

Page 19: ...NOTE DIAGRAMS ILLUSTRATION NOT TO SCALE 19 REPLACEMENT PARTS 9 10 15 14 4 7 6 5 12 1 12 13 13 2 8 3 CH Models CM Models CH Models CM Models SIT Valve Shown 11...

Page 20: ...03590 REV N 12 2007 The manufacturer reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult...

Reviews: