Superior VF18NBTB Installation And Operation Instructions Manual Download Page 7

SuperiorFireplaces.us.com

126857-01B

7

AIR FOR COMBUSTION AND VENTILATION

Continued

installed is confi ned or unconfi ned space. The 
standard method defi nes a confi ned space as 
a space whose volume is less than 50 cubic 
feet per 1,000 Btu/hr (4.8 m

3

 per kw) of the ag-

gregate input rating of all appliances installed 
in that space and an unconfi ned space as 
a space whose volume is not less than 50 
cubic feet per 1,000 Btu/hr (4.8 m

3

 per kw) of 

the aggregate input rating of all appliances 
installed in that space. Rooms communicating 
directly with the space in which the appliances 
are installed*, through openings not furnished 
with doors, are considered a part of the un-
confi ned space.
Where the air infi ltration rate of a structure is 
known, the Known Air Infi ltration Rate Method 
may be used. Follow The National Fuel Gas 
Code, ANSI Z223.1/NFPA 54 to use this 
method to determine if the space is confi ned 
or unconfi ned.
* Adjoining rooms are communicating only if 
there are doorless passageways or ventilation 
grills between them.

DETERMINING FRESH-AIR FLOW 
FOR HEATER LOCATION

Determining if You Have a Confi ned or 
Unconfi ned Space Using the Standard 
Method

Use this work sheet to determine if you have 
a confi ned or unconfi ned space.

Space: 

Includes the room in which you will install 

fi replace plus any adjoining rooms with door-
less passageways or ventilation grills between 
the rooms.

1.  Determine the volume of the space (length 

x width x height).

 

Length x Width x Height =__________cu. ft. 
(volume of space)

 

Example:

 Space size 20 ft. (length) x 16 ft. 

(width) x 8 ft. (ceiling height) = 2560 cu. ft. 
(volume of space)

 

If additional ventilation to adjoining room 
is supplied with grills or openings, add the 
volume of these rooms to the total volume 
of the space. 

2.  Multiply the space volume by 20 to determine  

the maximum Btu/Hr the space can support.

 

  ________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)

 

Example:

 2560 cu. ft. (volume of space) x 

20 = 51,200 (maximum Btu/Hr the space can 
support)

3.  Add the Btu/Hr of all fuel burning appliances 

in the space.

 Vent-free 

fi replace 

 __________ Btu/Hr

 

Gas water heater* 

 __________ Btu/Hr

 Gas 

furnace 

 

__________ Btu/Hr

 

Vented gas heater 

 __________ Btu/Hr

 Gas 

fi replace logs 

 __________ Btu/Hr

 

Other gas appliances* + _________ Btu/Hr

 Total 

 

_________ Btu/Hr

 

* Do not include direct-vent gas appliances. 
Direct-vent draws combustion air from the 
outdoors and vents to the outdoors.

 

Example:

 

 

Gas water heater 

 __________ Btu/Hr

 Vent-free 

fi replace 

+ _________ Btu/Hr

 Total 

_________ Btu/Hr

4.  Compare the maximum Btu/Hr the space can 

support with the actual amount of Btu/Hr used.

 

  _______ Btu/Hr (maximum can support) 

 

  _______ Btu/Hr (actual amount used)

 

Example:

 51,200 Btu/Hr (maximum the 

space can support) 

 

 

73,000 Btu/Hr (actual amount of 
Btu/Hr used)

The space in the above example is a confi ned 
space because the actual Btu/Hr used is more 
than the maximum Btu/Hr the space can sup-
port. You must provide additional fresh air. Your 
options are as follows:

A.  Rework worksheet, adding the space of an 

adjoining room. If the extra space provides 
an unconfi ned space, remove door to adjoin-
ing room or add ventilation grills between 
rooms. See 

Ventilation Air From Inside 

Building, Page 8.

B.  Vent room directly to the outdoors. See 

Ventilation Air From Outdoors, Page 8

.

C.  Install a lower Btu/Hr fi replace, if lower Btu/

Hr size makes room unconfi ned.

If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support,

 

the space is 

an unconfi ned space. You will need no additional 
fresh air ventilation.

 40,000

 33,000

 73,000

Summary of Contents for VF18NBTB

Page 1: ...nted gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ventilation sect...

Page 2: ...ordance with ANSI Z21 11 2 Exception DO NOT install this appliance in a factory built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs W...

Page 3: ...It is your guide to safe and proper operation of this fireplace Due to high temperatures the ap pliance should be located out of traffic and away from furniture and draperies Do not place clothing or...

Page 4: ...his heater needs fresh outside air ven tilation to run properly This heater has an oxygen depletion sensing ODS pilot light safety system The ODS shuts down the heater if not enough fresh air is avail...

Page 5: ...y from carton NOTE Do not pick up heater base as sembly by burners This could damage heater Always handle base assembly by grate CAUTION Donotremovethe data plates from the grate as sembly The data pl...

Page 6: ...iances This will ensure proper venting of vented fuel burning appliances PROVIDING ADEQUATE VENTILATION The following are excerpts from National Fuel Gas Code ANSI Z223 1 NFPA 54 Air for Com bustion a...

Page 7: ...r openings add the volume of these rooms to the total volume of the space 2 Multiply the space volume by 20 to determine the maximum Btu Hr the space can support ________ volume of space x 20 Maxi mum...

Page 8: ...ining Room Option 2 Ventilation Grills Into Adjoining Room Option 1 12 12 Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two perma nent ope...

Page 9: ...top or sides of the heater in high traffic areas in windy or drafty areas NOTICE This appliance is in tended for supplemental heat ing Use this heater along with yourprimaryheatingsystem Do notinstal...

Page 10: ...Rear Width 18 17 14 24 20 24 17 14 28 22 Measured at 14 depth Figure 4 Minimum Clearance for Combustible to Wall Minimum 16 from Side Wall Example WARNING This appliance is equipped for either natura...

Page 11: ...t be at least 1 2 thick With sheet metal you must have noncombustible ma terial behind it Noncombustible material must extend at least 8 up for all models If noncombustible material is less than 12 yo...

Page 12: ...ace temperatures of adjacent walls and mantels become hot during operation Walls and mantels above the firebox may become hot to the touch If installed properly these temperatures meet the requirement...

Page 13: ...lacement INSTALLING HEATER BASE ASSEMBLY WARNING If installing in a sunken fireplace special care is needed You must raise the fireplace floor to allow access to heater control panel This will ensure...

Page 14: ...gas pressure to between 11 and 14 of water If you do not reduce incoming gas pressure heater regula tor damage could occur Install external regu lator with the vent pointing down as shown in Figure 1...

Page 15: ...ter see Figure 13 IMPORTANT Install equipment shutoff valve in an accessible location The equipment shutoff valve is for turning on or shutting off the gas to the appliance WARNING Use pipe joint seal...

Page 16: ...ing main gas valve located on or near gas meter for natural gas or using compressed air 3 Check all joints from gas meter to equip ment shutoff valve for natural gas or propane LP supply to equipment...

Page 17: ...a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS WARNING If fireplace has glas...

Page 18: ...tch see Manual Lighting Procedure Page 19 8 Keep control knob pressed in for 30 sec onds after lighting pilot After 30 seconds release control knob If control knob does not pop out when released conta...

Page 19: ...es Transmitter requires 12V A 23 and 3V button cell for LCD both included Remote receiver requires 4 AA 1 5V alkaline batteries included Operating Frequency 303 875 MHz REMOTE CONTROL OPERATION 1 Afte...

Page 20: ...ct pilot flame pat tern The incorrect pilot flame is not touching the thermocouple When the thermocouple cools the heater will shut down If pilot flame pattern is incorrect as shown in Figure 21 turn...

Page 21: ...he unit every three months during operation and have heater inspected yearly by a qualified service person We also recommend that you keep the burner tube clean and free of dust and dirt We rec ommend...

Page 22: ...ed by any metal or tubing Keep igniter cable dry 3 Replace battery 4 Replace igniter cable 5 Replace electronic igniter 6 Replace pilot assembly When igniter button is pressed there is spark at ODS pi...

Page 23: ...S pilot see Cleaning and Mainte nance Page 21 or re place ODS pilot assembly 6 Hand tighten until snug then tighten 1 4 turn more 7 Replace pilot assembly 8 Replace control valve Burner does not light...

Page 24: ...gas line checked by local natural or propane LP gas company 3 Observe minimum instal lation clearances see Pages 10 through 12 4 Clean burner see Clean ing and Maintenance Page 21 or replace burner or...

Page 25: ...ve 2 Low fuel supply propane LP only 3 Gas leak See Warning statement at top of Page 1 Open window to ventilate room Stop using odor causing products while heater is running 2 Refill supply tank pro p...

Page 26: ...too low If so contact your local propane LP or natural gas supplier TECHNICAL SERVICE You may have further questions about instal lation operation or troubleshooting Please contact your IHP dealer fo...

Page 27: ...21 12 13 16 10 6 14 2 15 18 17 22 19 Installed in BTB Models Only 17 Remote Control and Receiver CAT NO MODEL F1715 VF18NBTB F1716 VF18PBTB WARNING Failuretopositiontheparts inaccordancewiththesediag...

Page 28: ...4722 Elbow Orifice 1 11 J4701 Valve NG 1 J4702 Valve LP 1 12 J5239 Valve Bracket 1 13 J4596 Electronic Igniter 1 14 J3840 Control Knob Extension 1 15 J3841 Control Knob Extension 1 16 J3656 Fan Switch...

Page 29: ...m 126857 01B 29 PARTS MODELS VF24NBTB AND VF24PBTB 1 4 24 23 5 3 25 9 11 6 12 7 16 20 8 10 21 22 19 13 10 6 14 15 18 17 Installed in BTB Models Only 2 17 Remote Control and Receiver CAT NO MODEL F1717...

Page 30: ...Extension 1 16 J3656 Fan Switch 1 17 J4871 Remote Control and Receiver 1 18 J4872 Remote Bracket 1 19 J4712 Flextube 3 16 1 20 J4684 Pilot Shield 1 21 J4806 Pilot 1 J3830 Pilot 1 22 J4736 Compression...

Page 31: ...ct heat away from mantel or wall above fireplace Fits openings 28 to 48 wide VENT FREE FIREBOXES Available in 32 36 and 42 models FLOOR MEDIA KIT Cat No F1762 Model FM100 For all models Includes volca...

Page 32: ...lled mode Remote is programmable for your convenience and has a large bright LCD Touch Screen for easy use MODE SET PROG ON OFF REMOTE AND RECEIVER WITH WHITE WALL PLATE Cat No F2236 Model RCKIT 4001...

Page 33: ...________________________________________ ______________________________________________________ ______________________________________________________ _________________________________________________...

Page 34: ...________________________________________ ______________________________________________________ ______________________________________________________ _________________________________________________...

Page 35: ...produce excessive temperatures and could result in a re hazard c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product d dam...

Page 36: ...ributor for fireplace code information Printed in U S A 2014 Innovative Hearth Products P N 126857 01 Rev B 05 2017 1508 Elm Hill Pike Suite 108 Nashville TN 37210 SuperiorFireplaces us com Record the...

Reviews: