18

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Support 

Brackets

Building

Support

Framing

SV4.5E90

Elbow

Ceiling

Fireplace

SV4.5L6/12/24/36/48

Vent Sections

Vertical

Rise

Support Bracket Spacing

Every 5 ft (1.52 m)

See 

Figure 17 

on 

Page 13

 or 

Figure 20

 on 

Page 14 

 for vertical vent section support.

TYPICAL HORIZONTAL VENT INSTALLATION

u

 When Using Secure Flex™, 

Use Firestop / Spacer SF4.5VF

u

 Firestop / Spacer

SV4.5VF

Figure 28

Typical

Termination

Shown

Typical

Termination

Shown

Exterior

Wall

Horizontal / Inclined Run

SUPERIOR DIRECT-VENT GAS FIREPLACES  •  MODELS SLDVT-30/35/40/45  •  INSTALLATION INSTRUCTIONS

Push the vent component against the previous 

section  until  it  fully  engages,  then  twist  the 

component clockwise running the dimples down 

and along the incline channels until they seat at 

the end of the channels. 

This seating position 

is indicated by the alignment of the arrow and 

dimple as shown in

 Figure 19 

on 

Page 14.

F.

 

Install firestop/spacer at ceiling - 

When using 

Secure Vent

, use SV4.5VF firestop/

spacer at ceiling joists; when using Secure Flex, 

use SF4.5VF firestop/spacer. If there is living 

space above the ceiling level, the firestop/spacer 

must  be  installed  on  the  bottom  side  of  the 

ceiling. If attic space is above the ceiling, the 

firestop/spacer must be installed on the top side 

of the joist. Route the vent sections through the 

framed opening and secure the firestop/spacer 

with 8d nails or other appropriate fasteners at 

each corner.

Remember to maintain 1" (25 mm) clearance 

to combustibles, framing members, and attic 

or  ceiling  insulation  when  running  vertical 

chimney sections

.

G.

 

Support the vertical run sections - 

See Section E

 

on

 

Page 15.

H.

 

Change vent direction  -

 At transition from or 

to a horizontal/inclined run, install the SV4.5E45 

and SV4.5E90 elbows in the same manner as 

the straight vent sections.  

The  elbows  feature  a  twist  section  to  allow 

them to be routed about the center axis of their 

initial collar section to align with the required 

direction of the next vent run element.

  Twist 

elbow sections in a clockwise direction only 

so as to avoid the possibility of unlocking any 

of the previously connected vent sections (see 

Figure 19 

on

 Page 14).

I.

 

Continue installation of horizontal/inclined 

sections -

  Continue with the installation of the 

straight vent sections in horizontal/inclined run 

as described in 

Step E

. Install support straps 

every 5 ft. (1.52 m) along horizontal/inclined vent 

runs using conventional plumber’s tape. 

See Figure 28. It is very important that the 

horizontal/inclined  run  be  maintained  in  a 

straight (no dips) and recommended to be in 

a slightly elevated plane, in a direction away 

from the fireplace of 1/4" rise per foot (20 mm 

per meter) which is ideal, though rise per foot 

run ratios that are smaller are acceptable all the 

way down to at or near level.

It is important to maintain the required clear-

ances to combustibles: 1" (25 mm) at all sides 

for all vertical runs; and 3" (76 mm) at the top, 

1" (25 mm) at sides, and 1" (25 mm) at the 

bottom for all horizontal/inclined runs.

Use  a  carpenters  level  to  measure  from  a 

constant surface and adjust the support straps 

as necessary.

D.

 

Attach vent components to appliance - 

To 

attach a vent component to the appliance collar, 

align the dimpled end over the collar, adjusting the 

radial alignment until the four locking dimples are 

aligned with the inlets of the four incline channels 

on the collar (see Figure 19 

on 

Page 14).

Push  the  vent  component  against  the  collar 

until it fully engages, then twist the component 

clockwise, running the dimples down and along 

the incline channels until they seat at the end of 

the channels.  The unitized design of the 

Secure 

Vent™ 

components will engage and seal both 

the inner and outer pipe elements with the same 

procedure.  Sealant and securing screws are 

not required.

Note: An elbow may also be attached to the 

appliance collar.  Attach in the same manner 

as you would a vent section. 

E.

 

Attach  vent  components  to  each  other 

-

 Other vent sections may be added to the pre-

viously installed section in accordance with the 

requirements of the vent tables.  To add another 

vent component to a length of vent run, align the 

dimpled end of the component over the inclined 

channel end of the previously installed section, 

adjusting the radial alignment until the four lock-

ing dimples are aligned with the inlets of the four 

incline channels of the previous section.

Summary of Contents for SLDVT Series

Page 1: ...death WARNING AVERTISSEMENT AVISO HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS UNE SURFACE VITR E CHAUDE PEUT CAUSER DES BR LURES LAISSER REFROIDIR L...

Page 2: ...system Noexternalelectricalpowerisrequired to operate these appliances These vented gas fireplace heaters are sealed combustion air circulating gas fireplaces de signed for residential applications Ap...

Page 3: ...supplied by the manufacturer shall be used in the installation of this ap pliance Seules les trousses de garniture fournies par le fabricant doivent tre utilis es pour l installation de cet appareil T...

Page 4: ...USA the National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition or in Canada the CAN CSA B149 1 latest edition REQUIREMENTS FOR THE COMMON WEALTH OF MASSACHUSETTS Thesefireplacesareapprovedforinstal...

Page 5: ...entirebottomsurface must be used Cold Climate Insulation For cold climate installations seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room It...

Page 6: ...6 12 1 0 0 3 6 12 to 7 12 1 25 0 38 7 12 to 8 12 1 5 0 46 8 12 to 9 12 2 0 0 61 9 12 to 10 12 2 5 0 76 10 12 to 11 12 3 25 0 99 11 12 to 12 12 4 0 1 22 12 12 to 14 12 5 0 1 52 14 12 to 16 12 6 0 1 83...

Page 7: ...r e t e m t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e...

Page 8: ...houldberoutedinawaytominimizeobstructions to the space above the appliance Do not insulate the space between the appliance and the area above it see Figure 8 The minimum height from the base of the ap...

Page 9: ...nttothenailingflanges areEXEMPTfromthe 1 2 clearance to combustible requirements for the firebox outer wrapper Combustible framing may be in direct contact with the nailing flanges and may be located...

Page 10: ...ming Dimensions Model A B C D SLDVT 30 in 30 1 4 35 1 4 39 1 4 16 mm 768 895 997 406 SLDVT 35 in 35 1 4 35 1 4 39 1 4 16 mm 895 895 997 406 SLDVT 40 in 40 1 4 40 1 4 44 1 4 16 mm 1022 1022 1124 406 SL...

Page 11: ...anty Proper Sizing of Gas Line Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel G...

Page 12: ...xigences du foumisseunde gaz Useonlyapprovedventingcomponents See Approved Vent Components on Page 2 These fireplaces must be vented directly to the outside The vent system may not service multiple ap...

Page 13: ...1 1 4 0 5 2 4 1 0 0 1 0 1 2 1 5 1 1 5 5 2 6 2 4 0 0 0 0 1 1 1 1 5 0 2 5 5 7 3 3 4 0 2 0 1 1 1 4 1 1 3 5 5 2 4 4 0 2 2 0 1 1 5 1 5 8 3 5 5 7 8 4 4 1 0 0 2 1 1 4 1 9 4 5 5 7 5 4 1 0 2 1 1 1 5 1 8 5 5 5...

Page 14: ...ations Where required a telescopic vent section SV4 5LA may be used to provide the installer withanoptionininstallingintightand confined spaces or where the vent run made up of fixed length pieces dev...

Page 15: ...ion to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction onlysoastoavoidthepossibilityofunlocking any of the previously connected vent sectio...

Page 16: ...smaller are accept able all the way down to at or near level SV4 5VF Secure Vent SF4 5VF Secure Flex firestop spacer must be used anytime vent pipe passes through a combustible floor or ceiling SV4 5H...

Page 17: ...Max Figure 27 Top Vent three elbows SUPERIOR DIRECT VENT GAS FIREPLACES MODELS SLDVT 30 35 40 45 INSTALLATION INSTRUCTIONS VERTICAL VENT FIGURES TABLES continued Horizontal Outside Wall Termination S...

Page 18: ...possibility of unlocking any ofthepreviouslyconnectedventsections see Figure 19 on Page 14 I Continue installation of horizontal inclined sections Continue with the installation of the straight vent...

Page 19: ...on is hot while in operation and for a period of time following the use of the fireplace To prevent contact with hot surfaces we recommend the use of a Termina tion Guard See Page 37 This can be purch...

Page 20: ...VERTICAL COMPONENT IN THE SYSTEM See Figure 31 Use Table 8 as an aid in venting component selection for a particular range of exterior wall thicknesses Figure 32 Top Vent ONE 90 DEGREE ELBOW ELBOW CON...

Page 21: ...ELBOWS SUPERIOR DIRECT VENT GAS FIREPLACES MODELS SLDVT 30 35 40 45 INSTALLATION INSTRUCTIONS See Table 8 on Page 20 as an aid in venting component selection for a particular range of exterior wall th...

Page 22: ...V4 5HF Ceiling Firestop Spacer SV4 5VF When using Secure FlexTM use Firestop Spacer SF4 5VF When using Secure Flex use Firestop Spacer SF4 5HF Wall Firestop Spacer SV4 5HF See Table 8 on Page 20 as an...

Page 23: ...inner flexible vent pipe 4 Slidetheinnerflexpipeovertheadaptorcol lar Ensure the flexible vent pipe completely engages the adaptor collar to a distance of 1 3 4 inches from the end and that it is fre...

Page 24: ...N ORANGE THTP BLACK TP GREEN TH TO WALL SWITCH OR THERMOSTAT Refer to Section A for millivolt appliances and Section B for electronic appliances The gas valve is set in place and pre wired at the fact...

Page 25: ...0 After the wiring is complete replace the cover plate Note No batteries to be installed in the battery holder until a power outage or if the appli ance is to be operated solely with two 2 D batteries...

Page 26: ...s Proceed as follows Acquire the shut off valve and gas lex line and pull the assembly forward out of the compart ment Separate the shut off valve from the gas flex line Determine the length of pipe n...

Page 27: ...at the right and left sides of the burner Positionanyceramicfiberlinersbefore placing the stone Logs can be positioned after the volcanic stone SUPERIOR DIRECT VENT GAS FIREPLACES MODELS SLDVT 30 35...

Page 28: ...ing instructions 1 Place the left front log 1 as shown Posi tion it on the two left front log brackets 2 Placetherightfrontlog 2 asshown Posi tion it on the two right front log brackets 3 Place the le...

Page 29: ...ign the hole at the bottom of log 4 over the Nub of log 2 as shown 4 2 1 Right Rear Bracket Rockwool Do Not Place Rockwool Over Burner Slots 1 Right Front Brackets Left Front Brackets 3 1 Right Front...

Page 30: ...n the hole at the bottom of log 5 over the Nub of log 3 as shown 3 5 Left Rear Bracket Right Rear Bracket Right Front Brackets Left Front Brackets Place Ember Chunk Here Align hole at the bottom of le...

Page 31: ...om of left front log 1 over the left front brackets and the right front log 2 over the right front brackets 5 2 1 3 4 5 Left Rear Brackets Right Rear Bracket Right Front Brackets Left Front Brackets C...

Page 32: ...two latches located underneath the firebox floor to the door s vee flange Close both the latches securely 8 Installthehood Notethelocationofthethree clipsinsidethetopairchannelabovethedoor Theclipsare...

Page 33: ...st air shutter to the standard set ting as shown in Figure 54 adjustment rod is located in the lower control compartment Note Move the adjustment rod down to decrease air and up to increase 2 Light ap...

Page 34: ...g flush with the finished wall position framework to accommodate the thickness of the finished wall Figure 55 See Page 5 for Cold Climate Insulation and Page 8 for Clearances Top Of Appliance 3 76 mm...

Page 35: ...s proporcionadas con estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor o el termostato de pared quecontrolalachimenea verifiquequeelinterruptor opera la chimenea encend...

Page 36: ...id 3 1 1 spacing 10 Pack H2247 SV4 5VF 10 Firestop Spacer Vertical rigid 1 1 1 spacing 10 Pack 96K92 SV4 5SP Support Plate SUPERIOR DIRECT VENT GAS FIREPLACES MODELS SLDVT 30 35 40 45 INSTALLATION INS...

Page 37: ...SFGC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pack H7748 H7748 36 Flex Connector Kit 36 offlexwithtwoadapters formatingtworigidsections of vent together Listed Secure Vent Components Cat Model Descri...

Page 38: ...LEC TRIQUE Step 2 Remove the front glass door frame Step 3 Carefully remove the logs Exercise care so as not to break the logs Step 4 Refer to Figure 56 Remove the burner assembly with attached ventu...

Page 39: ...ot hoodassemblytoaccessthehexedpilotorifice Remove and replace the orifice with the one provided with the kit Figure 57 Figure 58 Pressure Regulator Remove These Components Pilot Orifice Figure 59 Dex...

Page 40: ...e changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information 1508 Elm...

Reviews: