Piazzetta Pellet Stove Guide to Setting Flue Parameters (Installer Information Only) 

 
This guide is supplementary to the Installation Instructions, which should be read before setting the flue fan   
parameters. It must only be carried out by an authorised installation engineer with the correct equipment. Whilst 
the appliance will normally operate as set in the factory, for optimum performance the flue gas fan must be     
adjusted to allow for variations in individual flues. 
 

General 

Before starting ensure the hopper contains enough pellets. Pellets must be fresh and dry. Remove any unburnt 
pellets and ash from the grate. 
 
Ensure any controls (boiler stove) are calling for heat. 
 
Note that the first ignition attempt may fail to ‘No lit’ as the auger takes time to fill before dropping pellets into the 
grate. If this happens restart the stove.  
 
Connect a suitable micromanometer / draught gauge to the pressure tapping point on the rear of the stove 
(remove brass cap nut). The draught gauge needs to measure values of up to about 120 Pascals (Pa) with 1 Pa 
steps. (A gas CO / CO2 analyser such as the Anton Sprint usually have a suitable pressure scale). Note the 
pressures are negative. 
 
Record the pressure at each setting after adjustment for future reference. 
 

See relevant section as to using the remote or the keypad (always use the remote where it is supplied) 

 
 

Setting Parameters using the Remote Control 

 
Start the appliance. 
 
Open the flap on the remote and follow the procedure in sequence 

 
Note:

 

esc

 returns you to the previous memory, 

set

 confirms the menu or setting 

  

ο 

Press 

menu

 

ο 

Use the up/ down arrows to find 

menu parameter

 

ο 

Press 

set

 

ο 

Use the up/ down arrows to find 

setting smoke ext

 

ο 

Press 

set

 

ο 

Use the up/ down arrows to find 

A9

 

ο 

Press 

set

 

ο 

Use the 

set 

button to scroll through the parameters and adjust each one as necessary as you get to it. If you 

pass the parameter you need to adjust press 

esc

 to return to the previous menu and start again.

 

Check and adjust if necessary parameter 16P. 

Note

 this must be done during 

Phase 1

 

 

Note:

 The setting value of the parameter is adjusted using the up/ down arrows and watching the                   

micromanometer to obtain the correct pressure. Changes to the pressure are immediate but wait for it to settle 
and record the final result (Pa). 
 

ο 

Press 

set

 to confirm the setting and move to the next parameter

 

Parameter 17P must be set during 

Phase 2

 adjusting as above to obtain the correct pressure

 

 
The rest of the parameters must be set when the whole flue system is up to temperature. For boiler stoves the 
water temperature must also be at least 60 deg C. 
 
Note the parameters 18P to 22P are the settings for the different power output levels 1-5, or for stoves with 4 
power levels 18P to 21P 
 

ο 

Access the highest power level (22P or 21P) first using the method above

 

ο 

Adjust the setting to obtain the correct pressure and 

set

 to confirm

 

Adjust the other parameters in reducing order 21P, 20P, 19P, 18P and 

set

 each to confirm

 

Summary of Contents for SABRINA THERMO 11

Page 1: ...1 SAMANTA THERMO 11 SABRINA THERMO 11 SVEVA THERMO 11 SIRIA THERMO 11...

Page 2: ...nts of the Health and Safety at Work Act are met Handling Adequate facilities must be available for loading unloading and site handling Fire Cement Some types of fire cement are caustic and should not...

Page 3: ...w fumes into the house Remedial action should be taken if required seeking expert advice if necessary If it is found necessary to line the chimney then a flue liner suitable for solid fuel must be use...

Page 4: ...ment J An opening window is not appropriate for this purpose IMPORTANT NOTE If applicable and the appliance is being fitted within a fireplace recess specialist advice should be sought before fitting...

Page 5: ...and windows to ventilate room and then leave the premises c When safe to do so check for flue or chimney blockage and clean if required d Do not attempt to relight the stove until the cause of the fum...

Page 6: ...and emit smoke and fumes into the room Aerosol sprays Do not use an aerosol spray on or near the stove when it is alight Chimney Fires If the chimney flue is thoroughly and regularly swept chimney fir...

Page 7: ...and the controls are working satisfactorily The installer will have explained use of the controls The stove can be lit and programmed using the keypad on the stove or where applicable the remote contr...

Page 8: ...8...

Page 9: ...T 26 4 6 INSTALLING THE AUX THERMOSTAT 27 4 7 FILLING THE SYSTEM 27 4 8 SIDE FLUE GAS OUTLET OPTIONAL 28 5 0 FUEL 30 5 1 LOADING THE PELLETTS 30 6 0 USE 31 6 1 CONTROL PANEL 31 6 2 SETTING THE LANGUAG...

Page 10: ...10 N O T F O R U K U S E...

Page 11: ...11...

Page 12: ...12...

Page 13: ...13...

Page 14: ...14...

Page 15: ...15...

Page 16: ...16 N O T F O R U K U S E N O T F O R U K U S E...

Page 17: ...17...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...24...

Page 25: ...25...

Page 26: ...is designed for connection to an external room thermostat NOT SUPPLIED To connect an external thermostat use a 2x0 5mm2 cable clamped with a PG7 cable gland inserted in the appropriate hole in the re...

Page 27: ...27...

Page 28: ...28...

Page 29: ...29...

Page 30: ...30 Do not allow sawdust to accumulate on the bottom of the hopper Do not leave leftover pellets on top of the stove they could catch fire...

Page 31: ...31...

Page 32: ...32...

Page 33: ...33...

Page 34: ...34...

Page 35: ...35...

Page 36: ...36...

Page 37: ...37...

Page 38: ...38...

Page 39: ...39...

Page 40: ...40...

Page 41: ...41...

Page 42: ...42...

Page 43: ...43...

Page 44: ...44...

Page 45: ...45...

Page 46: ...46...

Page 47: ...47...

Page 48: ...48...

Page 49: ...49...

Page 50: ...50...

Page 51: ...51...

Page 52: ...52...

Page 53: ...53...

Page 54: ...54...

Page 55: ...55...

Page 56: ...56...

Page 57: ...57...

Page 58: ...using the Remote Control Start the appliance Open the flap on the remote and follow the procedure in sequence Note esc returns you to the previous memory set confirms the menu or setting Press menu U...

Page 59: ...tely at this stage set the pressure between 110 and 120 Pa using keys 1 and 2 and watching the micromanometer to obtain the correct pressure To check if the new setting is correct it will be necessary...

Page 60: ...60 Robeys Ltd Goods Road Belper Derbyshire DE56 1UU Tel 01773 820940 Fax 01773599309 Email info robeys co uk www robeys co uk...

Reviews: