Superior CR-3835R Installation Instructions Manual Download Page 8

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

8

Step 8.

 Fireplace should be secured to side

framing members using the full length nailing
tabs at the top and bottom of the fireplace front
face.  Use 8d nails (

Figure 18 ).

Figure 18

Note:

 The nailing tabs and the area directly

behind the nailing tabs are exempt from the
clearances described on page 5.  Maintain at
least 1/2" clearance from the firebox wrapper to
the framing at the closest point of contact,
directly adjacent to the flange.

Figure 19

8d Nail

Step 3.

 Position appropriate firestop spacer at

ceiling and nail temporarily with two (2) 8d
nails. If chimney penetrates ceiling vertically,
use flat firestop spacer, Model F8FS-2 for FTF8
system and Model F10FS-2 for the FTF10
system*. If chimney penetrates ceiling at 30

°

angle (offset chimney), use 30

°

 firestop spacer,

Model F8FS30-2 for FTF8 and Model F10FS30-
2 for FTF10 system*. Use one nail on opposite
sides to hold firestop spacer in position. Nail
permanently, using at least two (2) more 8d
nails, after chimney sections have been as-
sembled through the firestop spacer and after
any necessary adjustments have been made.
Firestop spacer must be secured by at least
four (4) 8d nails when completely installed.

Note:

 If there is a room above ceiling level,

firestop spacer must be installed on the bottom
side of the ceiling. If an attic is above ceiling
level, firestop spacer must be installed on top
side of ceiling joist (Figures 20 and 21 ).

Figure 20

Figure 21

Firestop Spacer

Room Above

Firestop Spacer

Attic Above

INSTALLING THE CHIMNEY SYSTEM

Step 1.

 Before continuing, check the operation

of the damper, as described on page 4, (

refer

to Figure 3 ).

Step 2.

 Using standard construction framing

techniques, construct opening for chimney
route up through the ceiling(s) and roof or
through an outside chase.

Framing must maintain adequate minimum air
space clearance at all times.

CAUTION: ALLOW MINIMUM 2" (51 MM)
CHIMNEY AIR SPACE TO COMBUSTIBLE
FRAMING MEMBERS THROUGHOUT VERTI-
CAL OR OFFSET CHIMNEY INSTALLATION
(

SEE **NOTE).

A minimum 2" (51 mm) air space must be
reserved for all combustible materials ex-
tending for any continuous length surround-
ing the chimney (

See **Note).

Reference 

Figures 15 and 16 and charts Fram-

ing Dimensions for Ceiling and Roof, which
specify minimum ceiling and roof dimensions.

To determine chimney center line in new con-
struction, use plumb line from roof or ceiling
above fireplace to center of flue collar on
fireplace.

For remodeling, plumb to center of flue collar
from ceiling above, drive nail through ceiling
from below to mark position, then mark and
cut to passage from above ceiling (around
nail) (

Figure 19 ). Then plumb from ceiling or

roof level directly above hole which has just
been completed.

Step 6.

 Route the Class 0 air duct out the back

wall or side wall, up through the ceiling or floor
joists to an outside wall. The air duct should be
located above snow level.

Note:

 If the fireplace is installed against an

inside wall, the Class 0 air duct may be ex-
tended into a ventilated attic space at least 18"
(457 mm) above the attic floor. Secure the duct
hood to a vertical post with the inlet positioned
downward. Ensure nothing blocks the hood
opening. This air duct must never terminate
higher than the chimney.

Step 7.

 Cut or frame hole through the outside

wall for the installation of the duct inlet hood.
A 4 

¹⁄₄

" (114 mm) diameter hole is sufficient.

Feed the loose end of the flexible air duct
through the hole cut for the inlet hood and
attach to collar on inlet hood using two (2)
screws. Insert hood into opening. Secure in
place with nails driven through holes in hood
flange. Seal with noncombustible waterproof
silicon type caulking. If additional air duct is
needed, use Class 0 metallic air duct.

*Note:

 Use Models F10FS or F10FS30 when

installing FTF10 chimney in the U.S. only.

** Note:

 1"  (25 mm) when installed with FTF10

in the U.S. only.

Plumb Line

Note:

 If installing the optional collar duct kit, it

should be installed after the chimney has been
attached to the flue collar.

Summary of Contents for CR-3835R

Page 1: ...ents under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories may void the warranty listings and app...

Page 2: ...l provided with the fireplace TOOLS AND BUILDING SUPPLIES NORMALLY REQUIRED Tools should Include Phillips screwdriver Hammer Saw and or sabersaw Level Measuring tape Plumb line Electric drill and bits...

Page 3: ...s such as the BOCA Basic National Codes the Standard Me chanicalCodeandtheUniformBuildingCodes When complete these fireplace systems con sists of five basic sub systems 1 The Fireplace 2 The Chimney a...

Page 4: ...r Chase Opening Optional Insulation In Outside Walls Of Chase Solid Continuous Surface Outside Base Insulation Thermal Barrier 8 Level Note Do not insulate the chase cavity with blown or fill type ins...

Page 5: ...h installation is unique however and might require a different sequence 1 Position firebox prior to framing or into prepared framing 2 Install the chimney system 3 Connect house wiring to the fireplac...

Page 6: ...02 mm Class 0 air duct provided to the collar on the chimney collarenclosurewiththescrewsprovidedinthe hardware kit IMPORTANT UNDER NO CIRCUMSTANCES CAN THE FIREPLACE TOP SPACERS FIGURE 6 BE REMOVED O...

Page 7: ...mm 432 mm 483 mm 483 mm 6 12 16 19 17 19 19 21 419 mm 483 mm 432 mm 483 mm 483 mm 533 mm 12 12 16 23 17 24 19 26 419mm 597mm 432mm 610 mm 483mm 660 mm Perpendicular to roof ridge A B Ceiling Framing...

Page 8: ...EY AIR SPACE TO COMBUSTIBLE FRAMING MEMBERS THROUGHOUT VERTI CAL OR OFFSET CHIMNEY INSTALLATION SEE NOTE A minimum 2 51 mm air space must be reserved for all combustible materials ex tending for any c...

Page 9: ...And Room Above 10 Max Room Above 2 Min Air Space 2 Min Air Space Figure 24 Outer pipe section installs in just the opposite way the lanced end goes down and each new section goes OVER the outside of...

Page 10: ...Note Do not caulk or seal the ventilating open ings Step 7 Secure flashing by nailing along the perimeter into roof using 8d nails If shingled roof slide upper end and sides of roof flashing under shi...

Page 11: ...smoke free opera tion Trees buildings adjoining roof lines ad verse wind conditions etc may require a taller chimney should the fireplace not draft properly see Figure 33 MULTIPLE TERMINATIONS If more...

Page 12: ...ng Do not puncture the inner flue Maximum offset of chimney system is 30 Two offsets must not be assembled to form a 60 offset However two sets of offset and return elbows may be used on a single flue...

Page 13: ...imney Components Chimney Only Inches Feet Inches 12 18 24 36 48 S4 Meters 247 20 7 0 1 0 0 5 6 29 253 21 1 0 0 1 0 5 6 44 257 21 5 1 1 0 0 5 6 55 263 21 11 1 0 1 0 5 6 70 269 22 5 0 1 1 0 5 6 85 275 2...

Page 14: ...hes Feet Inches 12 18 36 MM M 461 38 5 0 1 13 11722 11 72 465 38 9 2 0 13 11824 11 82 471 39 3 1 1 13 11976 11 98 479 39 11 0 0 14 12179 12 18 489 40 9 1 0 14 12433 12 43 495 41 3 0 1 14 12586 12 59 4...

Page 15: ...1 1073 2064 44 85 1 1 0 1 1 1 0 1124 2159 45 86 1 1 0 0 1 0 1 1149 2197 47 90 1 1 0 0 2 1 0 1200 2286 48 91 1 1 0 0 0 2 0 1226 2330 49 93 1 1 0 2 1 1 0 1251 2381 51 97 1 1 0 1 4 0 0 1308 2470 53 100 1...

Page 16: ...59 1 0 0 1 1 743 1505 31 63 1 0 2 0 1 794 1600 32 65 1 0 4 1 0 826 1651 34 68 1 0 1 1 1 870 1734 36 71 1 0 3 0 1 921 1822 37 73 1 0 0 2 1 946 1861 38 75 1 0 0 0 2 972 1905 39 77 1 0 2 1 1 997 1956 41...

Page 17: ...pitch of the roof Offset Elbow Assembly Offset elbows install the same as chimney sections First snap the inner section INTO the preceding inner section of flue Check connec tion by pulling up slightl...

Page 18: ...across a 90 corner no wall shields are required Glass Doors If glass doors are to be installed on these fireplaces refer to specific installation instruc tions packed with the glass doors Use only the...

Page 19: ...Thick Materials k r TM Wonderboard 1 92 0 56 1 Common brick 5 00 0 20 4 Cement mortar 5 00 0 20 4 Ceramic tile 12 5 0 08 11 Marble 11 0 0 09 10 Micore CV230 0 43 2 33 U S Gypsum Ceraform 126 0 27 3 7...

Page 20: ...kept within the shaded areas illustrated in Figure 46 Model Part Number Weight CR 3835R P N 015014 210 lbs CR 3835L P N 015013 210 lbs 63L30 F8FS30 63L32 F8FS30 2 Firestop Spacer 30 63L37 F10FS30 2 6...

Page 21: ...Outside Combustion Air Kits with duct 81L87 FOAK without duct 81L88 FOAK LD 63L25 FTF8 S4 Stabilizer 63L26 FTF10 S4 Chimney Pack Conventional 63L70 FTF8 CP7 Contains 3 FTF8 36 1 F8FS 1 F8F6 1 FTF8 CT...

Page 22: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 22...

Page 23: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 23...

Page 24: ...700 024M REV N C 05 2004 1110 West Taft Avenue Orange CA 92865 The manufacturer reserves the right to make changes at any time without notice in design materials specifications prices and also to disc...

Reviews: