Superior CR-3835R Installation Instructions Manual Download Page 5

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

5

Note:

 Install the hearth extension only as illus-

trated.

The safety strips should extend from front of
the fireplace at least 1 

¹⁄₂

" and should extend to

be at least flush with the sides. In the event a
wooden support is used to elevate the fireplace
above the floor, a “Z” type safety strip should be
fabricated and used to protect the front surface
of the wood support as well as the floor beneath
the hearth extension (

Figures 8 and 9 ). The

safety strips should be tacked down to prevent
possible movement.

Note:

 The “Z” type safety strip is not supplied.

2.

 Measure the square footage of the floor

space to be occupied by the system, surrounds
and hearth extensions.

3.

 Note the floor construction, i.e. 2 x 6’s, 2 x 8’s

or 2 x 10’s, single or double joists, type and
thickness of floor boards.

4.

 Use this information and consult your local

building code to determine if you need addi-
tional support.

CAUTION: DO NOT BLOCK THE HEAT-CIRCU-
LATING AIR INLET AND OUTLET PORTS ON
CIRCULATING MODELS.  DOING SO MAY RE-
SULT IN A POTENTIAL FIRE HAZARD.

If you plan to raise the fireplace and hearth
extension, build the platform assembly then
position fireplace and hearth extension on top.
Secure the platform to the floor to prevent
possible shifting.

CLEARANCES

Minimum clearance to combustibles for the
appliance is as follows: sides and back - 

¹⁄₂

" (13

mm), floor - 0" (0 mm), adjacent wall - 12" (305
mm), ceiling - 37 

¹⁄₂

" (953 mm).

INSTALLING THE FIREPLACE

Step 1.

 Slide the fireplace into prepared fram-

ing or position fireplace in its final position and
frame later.

The fireplace may not be recessed into a com-
bustible floor. Maintain the floor to hearth clear-
ance established by the fireplace lower front face.

Step 2.

 Insert the provided metal safety strips,

beneath the fireplace as illustrated (

Figures 6, 7

and 8 ). The safety strips should overlap 

¹⁄₂

" for

continual coverage of the floor.

Note:

 Safety strips are not required when fire-

place rests on a noncombustible surface.

ASSEMBLY STEPS

Note:

 The following steps represent the normal

sequence of installation. Each installation is
unique, however, and might require a different
sequence.

1.

 Position firebox prior to framing or into

prepared framing.

2.

 Install the chimney system.

3.

 Connect house wiring to the fireplace for

later attachment of optional blower.

4.

 Install optional outside combustion air kit.

5.

 Plumb gas line if a decorative gas appliance

will be used. (Gas connections should only be
performed by an experienced, licensed/certi-
fied tradesman.)

6.

 Complete the installation, finish wall mate-

rial, surround and hearth extension to your
individual taste.

7.

 Assemble and attach optional glass door

assembly.

Study the three dimensional illustration (

Fig-

ure 1 ) to get a general idea of each element of
your fireplace system.

PRE-INSTALLATION NOTES

The fireplace may be installed directly on a
combustible floor or raised on a platform of an
appropriate height. Do not place fireplace on
carpeting, vinyl or other soft floor coverings. It
may, however, be placed on flat wood, ply-
wood, particle board or other hard surfaces.
Be sure fireplace rests on a solid continuous
floor or platform with appropriate framing for
support and so that no cold air can enter the
room from under the fireplace.

The fireplace may be positioned and then the
framing built around it, or the framing may be
constructed and the fireplace positioned into
the opening.

Usually, no special floor support is needed for
the fireplace, however, to be certain:

1.

 Estimate the total weight of the fireplace

system including chimney and surround ma-
terials such as brick, stone, etc., to be in-
stalled.  Shipping weights for the fireplace may
be found on page 18.

Figure 7

Figure 6

1/2" (13mm)

Clearance To

Back And Sides

Combustible

Wall

Metal

Safety Strip

Hearth

Extension

Floor

Fireplace And

Hearth Extension

On Floor

1/2"

(13mm)

Figure 8

Metal

Safety Strip

2"

(51mm)

2"

(51mm)

Special “Z”

Metal Safety Strip

2"

(51mm)

2"

(51mm)

Blocking

Figure 9

Step 3.

  Refer to fireplace drawings and specifi-

cations on pages 6 and 7 for framing dimensions
and details. Frame appliance enclosure as illus-
trated in 

Figures 11 through 14 on page 8.

1/2" (13mm)

Clearance To

Back And Sides

Combustible

Wall

Metal

Safety Strip

Hearth

Extension

Floor

Platform

Fireplace And

Hearth Extension

On Raised Platform

1/2"

(13mm)

Summary of Contents for CR-3835R

Page 1: ...ents under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories may void the warranty listings and app...

Page 2: ...l provided with the fireplace TOOLS AND BUILDING SUPPLIES NORMALLY REQUIRED Tools should Include Phillips screwdriver Hammer Saw and or sabersaw Level Measuring tape Plumb line Electric drill and bits...

Page 3: ...s such as the BOCA Basic National Codes the Standard Me chanicalCodeandtheUniformBuildingCodes When complete these fireplace systems con sists of five basic sub systems 1 The Fireplace 2 The Chimney a...

Page 4: ...r Chase Opening Optional Insulation In Outside Walls Of Chase Solid Continuous Surface Outside Base Insulation Thermal Barrier 8 Level Note Do not insulate the chase cavity with blown or fill type ins...

Page 5: ...h installation is unique however and might require a different sequence 1 Position firebox prior to framing or into prepared framing 2 Install the chimney system 3 Connect house wiring to the fireplac...

Page 6: ...02 mm Class 0 air duct provided to the collar on the chimney collarenclosurewiththescrewsprovidedinthe hardware kit IMPORTANT UNDER NO CIRCUMSTANCES CAN THE FIREPLACE TOP SPACERS FIGURE 6 BE REMOVED O...

Page 7: ...mm 432 mm 483 mm 483 mm 6 12 16 19 17 19 19 21 419 mm 483 mm 432 mm 483 mm 483 mm 533 mm 12 12 16 23 17 24 19 26 419mm 597mm 432mm 610 mm 483mm 660 mm Perpendicular to roof ridge A B Ceiling Framing...

Page 8: ...EY AIR SPACE TO COMBUSTIBLE FRAMING MEMBERS THROUGHOUT VERTI CAL OR OFFSET CHIMNEY INSTALLATION SEE NOTE A minimum 2 51 mm air space must be reserved for all combustible materials ex tending for any c...

Page 9: ...And Room Above 10 Max Room Above 2 Min Air Space 2 Min Air Space Figure 24 Outer pipe section installs in just the opposite way the lanced end goes down and each new section goes OVER the outside of...

Page 10: ...Note Do not caulk or seal the ventilating open ings Step 7 Secure flashing by nailing along the perimeter into roof using 8d nails If shingled roof slide upper end and sides of roof flashing under shi...

Page 11: ...smoke free opera tion Trees buildings adjoining roof lines ad verse wind conditions etc may require a taller chimney should the fireplace not draft properly see Figure 33 MULTIPLE TERMINATIONS If more...

Page 12: ...ng Do not puncture the inner flue Maximum offset of chimney system is 30 Two offsets must not be assembled to form a 60 offset However two sets of offset and return elbows may be used on a single flue...

Page 13: ...imney Components Chimney Only Inches Feet Inches 12 18 24 36 48 S4 Meters 247 20 7 0 1 0 0 5 6 29 253 21 1 0 0 1 0 5 6 44 257 21 5 1 1 0 0 5 6 55 263 21 11 1 0 1 0 5 6 70 269 22 5 0 1 1 0 5 6 85 275 2...

Page 14: ...hes Feet Inches 12 18 36 MM M 461 38 5 0 1 13 11722 11 72 465 38 9 2 0 13 11824 11 82 471 39 3 1 1 13 11976 11 98 479 39 11 0 0 14 12179 12 18 489 40 9 1 0 14 12433 12 43 495 41 3 0 1 14 12586 12 59 4...

Page 15: ...1 1073 2064 44 85 1 1 0 1 1 1 0 1124 2159 45 86 1 1 0 0 1 0 1 1149 2197 47 90 1 1 0 0 2 1 0 1200 2286 48 91 1 1 0 0 0 2 0 1226 2330 49 93 1 1 0 2 1 1 0 1251 2381 51 97 1 1 0 1 4 0 0 1308 2470 53 100 1...

Page 16: ...59 1 0 0 1 1 743 1505 31 63 1 0 2 0 1 794 1600 32 65 1 0 4 1 0 826 1651 34 68 1 0 1 1 1 870 1734 36 71 1 0 3 0 1 921 1822 37 73 1 0 0 2 1 946 1861 38 75 1 0 0 0 2 972 1905 39 77 1 0 2 1 1 997 1956 41...

Page 17: ...pitch of the roof Offset Elbow Assembly Offset elbows install the same as chimney sections First snap the inner section INTO the preceding inner section of flue Check connec tion by pulling up slightl...

Page 18: ...across a 90 corner no wall shields are required Glass Doors If glass doors are to be installed on these fireplaces refer to specific installation instruc tions packed with the glass doors Use only the...

Page 19: ...Thick Materials k r TM Wonderboard 1 92 0 56 1 Common brick 5 00 0 20 4 Cement mortar 5 00 0 20 4 Ceramic tile 12 5 0 08 11 Marble 11 0 0 09 10 Micore CV230 0 43 2 33 U S Gypsum Ceraform 126 0 27 3 7...

Page 20: ...kept within the shaded areas illustrated in Figure 46 Model Part Number Weight CR 3835R P N 015014 210 lbs CR 3835L P N 015013 210 lbs 63L30 F8FS30 63L32 F8FS30 2 Firestop Spacer 30 63L37 F10FS30 2 6...

Page 21: ...Outside Combustion Air Kits with duct 81L87 FOAK without duct 81L88 FOAK LD 63L25 FTF8 S4 Stabilizer 63L26 FTF10 S4 Chimney Pack Conventional 63L70 FTF8 CP7 Contains 3 FTF8 36 1 F8FS 1 F8F6 1 FTF8 CT...

Page 22: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 22...

Page 23: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 23...

Page 24: ...700 024M REV N C 05 2004 1110 West Taft Avenue Orange CA 92865 The manufacturer reserves the right to make changes at any time without notice in design materials specifications prices and also to disc...

Reviews: